| 1 | Attending complaints for checking of existing electrical points wiring in any Buildings/Pole for continuity ,no light including carrying out minor repairs etc as required to make the item functional and replacing burnt wire ends, small pieces of wire, tightning of loose connections etc all as specified. Note - Contractor has to deploy Qualified Electrician and Helper with all necessary tools on all days to the complaint cell and complaints will be attended on the same day itself. Recovery for non attending complaints will be three times rate quoted by the Contractor. |
| 2 | Dismantling and taking down the existing defective street light/security light fitting of any type and any capacity fixed at any height by replacing UNSV part including perpex cover checking loose connection etc, restroration of electric supply, detecting and repair of UG cable fault whenever required round the clock all as directed at site on daily complaint basis. |
| 3 | S&F in repairs 45 watt of new street light/security light incl making electric connection using two run of 1.5 sqmm single core unarmoured wire from junction box complete all as specified and directed by Engr-in-Charge. |
| 4 | S&F in repairs 60 watt of new street light/security light incl making electric connection using two run of 1.5 sqmm single core unarmoured wire from junction box complete all as specified and directed by Engr-in-Charge. |
| 5 | S&F in repairs 100 watt of new street light/security light incl making electric connection using two run of 2.5 sqmm single core unarmoured wire from junction box complete all as specified and directed by Engr-in-Charge. |
| 6 | S&F in repairs 100 watt of new LED Flood light fitting incl making electric connection using two run of 2.5 sqmm single core unarmoured wire from junction box complete all as specified and directed by Engr-in-Charge. |
| 7 | M&L for repair to existing LED street light fitting 45 Watt to 60 Watt of any make including supply and replacement of driver and other minor allied items required at site to make the light fitting serviceable complete all as specified and directed by Engineer-in-Charge. |
| 8 | M&L for repair to existing LED street light fitting 90 Watt to 100 Watt of any make including supply and replacement of driver and other minor allied items required at site to make the light fitting serviceable complete all as specified and directed by Engineer-in-Charge. |
| 9 | M&L for repair to existing LED Flood light fitting 100 Watt of any make including supply and replacement of driver and other minor allied items required at site to make the light fitting serviceable complete all as specified and directed by Engineer-in-Charge. |
| 10 | S&F Sub main wiring with two single core PVC insulated unshesthed cable copper conductor(FRLS-H) of size 2.5 sqmm multistranded and one run of 2.5 sqmm PVC insulated unsheathed copper conductor(FRLSH) as earth continuty conductor drawing in and including non-metalic PVC rigid conduit 25 mm dia ISI marked with all conduit accessories concealed in wall, cutting of chases in walls, floors, ceilings, beams etc and making good the disturbed surfaces as directed including taking down old unservicable wiring complete all as specified and directed. (Two run of single core cable and one run of earthing cable and one run of PVC conduit shall be measured as one length.) |
| 11 | Supply and fixing in repairs Rigid non-metallic PVC conduit 25mm dia (Heavy duty) in concealed exclusive of boxes (junction/terminal) but inclusive of all tees, bends,elbows, reducers, bell mouth tube ends and fixing accessories such as couplers, lock nuts, saddles, pipe hooks etc. including taking out old conduit complete all as specified and directed. |
| 12 | S&F PVC insulated sheathed service wire twin core 6 Sqmm aluminium solid conductor 1100 volts grade incl taking down old unserviceable one. |
| 13 | S&F PVC insulated sheathed service wire twin core 10 Sqmm aluminium solid conductor 1100 volts grade incl taking down old unserviceable one. |
| 14 | Supply and fixing MCCB 160 amps 4 pole 25 KA adjustable thermal and fixed magnetic setting, complete all as specified and directed. |
| 15 | Supply and fixing MCB TPN 40 Amp to 100 amps four pole C curve 25 KA including taking dwon old UNSV one complete all as specified and directed. |
| 16 | Supply and fixing MCB single pole 06 amp to 32 amps C curve 25 KA with sheet metal encloser, including taking dwon old UNSV one complete all as specified and directed. |
| 17 | Preparation of old painted surface of 9 m steel tubular poles above the top of PCC coping. Painting of pole from top of coping to a height of 1.5m (bottom portion of pole) with two coats of synthetic enamel paint in black and yellow alternate strip and painting the rest portion of pole of (approx length 7 m)including painting of cross arms/clamps/GI pipe breaket etc complete with two coats of synthetic enamel aluminium paint and to the entire satisfaction of Engineer-in-Charge complete all as specified and directed |
| 18 | M & L for preparation of old cement based painted surfaces of RCC pole 9 m by cleaning of deposited materials, and painting with one coat of exterior emulsion weather coat paint of approved make and colour including painting of cross arms/clamps/GI pipe breaket etc complete all as specified and directed by Engineer-in-Charge |
| 19 | S & F in repairs LT cable joining kit straight through heat shrinkable complete with jointing materials suitable for LT armoured cable 4 core of size 16 to 35 Sqmm all as directed |
| 20 | S &F in repairs LT cable joining kit straight through heat shrinkable complete with jointing materials suitable for LT armoured cable 4 core of size 50 to 95 Sqmm all as directed |
| 21 | Supply, installation , commissioning and testing LT feeder pillar box in replacement of suitable size,outdoor cubical type floor mounted factory made of CPRI approved factory, totally enclosed vermin proof with front and rear opening with IP-54 protection as per IS - 8623 duly powder coated , fabricated out of 2.0 mm thick mild steel sheet mounted on frame of mild steel angle iron 60 cm x 60 cm x 6mm and , 45 cm above ground level duly supported with mild steel angle iron struts 60 cm x 60 cm x 6mm thick and embedded in PCC foundation in PCC 1:2:4, type B-1 , using 20 mm graded crushed stone aggregate , with suitable 415 Volt, 3 phase, four wire copper bus bar of rating capacity 400 Amps duly drilled holes for connections, R-Y-B-N insulated with different colour code and sleeved mounted on insulators complete prewired and cable connection with copper conductor wire upto Aluminium bus bars including all incoming and outgoing cable connections with suitable size of copper lugs/ gland including supply and fixing of MCCB four pole, 415V,I/C- 250 Amp. 25KA-01No Outgoing 63 Amp 4 pole- 04 Nos. including taking out old unserviceable, complete all as specified and directed by Engr - in- Charge. |
| 22 | Supply and fixing in repairs change over switchs off-load 320 amps 4 pole sheet metal encloser including taking down old UNSV one complete all as specified and directed. |
| 23 | Supply and fixing fixed in repairs cable Junction Boxes with terminals` IP 66 \\"halogen free and weather proof” for outdoor installation (with metric knockouts for cable entry - Black Colour) Cable Size 16/25 Sqmm, Box Dimensions-200 x160 x 98, Catalog No-KF 9255(hensel) complete taking out of loop of cable from ground by neccessary earth work all as spcefied and directed by Engr-in- charge. |
| 24 | Supply and laying & testing UG cable XLPE Insulated, screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (Heavy duty) 1100 Volts grade with stranded aluminium conductor of size 25 sq mm, 4 core, complete including disconnecting and taking out old existing unserviceable cable all as specified and directed by Engr-in-Charge. |
| 25 | Description all as per item No-24 but size 16 sq mm, 4 core complete all as specified and directed by Engr-in-Charge. |
| 26 | Re-Laying only of serviceable LT UG cable of size 10 sqmm and type in trenches, floors, across road crossing, or fixed on poles, walls with clam, or passing through pipe, complete all as specified and as directed.Note:-i). Handling of UG cable to working site as ordered shall be carried out by the firm and rate for the same shall deem to be included in the unit rate . |
| 27 | Supply and laying of DWC (Double Wall Corrugated) HDPE Pipe, ISI Marked IS 16205 Part-II, of outer dia of 63 mm and inner dia 50 mm with smooth internal and profiled external surface for non pressure under ground cable including all connected accessories like coupler, 'O' Ring etc, for protection of cable complete all as specified and as directed. |
| 28 | M & L for Cutting through existing road surfaces i.e. surfacing PCC soling etc, and making trench of minimum 500mm wide 100cm in depth along the cross section of road for laying of pipes or UG cables, including returning filing in, well ramming & removal of surplus spoil to a distance not exc. 50 m & repairs to road surfaces to match with existing specification after laying the pipes/cable etc. all as specified & directed. |
| 29 | Supply and Fixing GI tubing light grade 50mm dia along the wall/in trenches/in duct/in culvert/road crossing and including provisioning of suitable mild steel flat iron clamps and bolts, nuts and double washers etc for holding of GI pipe alongwith poles including taking out old broken GI pipes, complete all as specified and as directed by Engr-in-Charge. |
| 30 | Dismantling steel or concrete poles/struts any size complete. |
| 31 | Supply, install and erect in true vertical position (or to be fixed in an inclined position as strut pole) steel tubular swaged poles complete with MS base plate of 6 mm thick of size 300 mm x 300 mm, finial taper plug, pole cap, bolts, nuts and washers and screwed pole made out of FRW MS tubing conforming to IS-2713 (Part-II) 1980 type 410-SP-31 ( 9 meters long ) pole including drilling of holes of required size and Nos for fixing of cross arms, painting with one coat of red oxide primer and two coats of aluminium paint for exposed surfaces and two coats of black bituminous paint for portion embeded in concrete, etc complete all as specified and directed |
| 32 | Excavation in trenches not exceeding 1.5m wide and not exceeding 1.5m in depth and getting out in any type of soil for laying of LT UG cables complete all as specified and as directed by Engr in charge. Note:- The Rate quoted deemed to including cutting and removal of PSP Sheets wherever occured during excavation and the same shall be staged at desired location as directed at site |
| 33 | Returning, filling in, including spreading levelling, watering and well ramming in layers not exceeding 25 cm thick in hard dense soil complete all as specified and as directed by Engr in charge. |
| 34 | Removing excavated material not exceeding 50m and depositing where directed at a level not exceeding 1.5m above the starting point complete all as specified and as directed by Engr in charge. |
| 35 | M&L for PCC 1:4:8 type D-2 using 40mm graded aggregate, mechanically crushed stone for mass filling in pole pit and foundation etc including provision of necessary form work to achieve fair finished surfaces complete all as specified and as directed. |
| 36 | M&L for PCC 1:3:6 type C-2 using 20mm graded crushed stone aggregate as in pole pole foundation, coping, stay pits etc including provision of necessary form work i.e road cutting to aachieve fair finishes surfaces, complete alal as specified and directed. |
| 37 | Taking down UNSV fuel pump and repair/replacement /overhauling and calibration of fuel pump complete with replacement of burn out part such as bearing ,plunger,impeller and oil seal ring etc including calibration of 32.5 KVA to 160 KVA DG Set ,complete all as specified and directed by Engr-in-charge. |
| 38 | Taking down injectors assembly for repair/replacement/overhauling and calibration of injectors assembly complete by replacing of burn out part suitable for 32.5 to 160 KVA DG SET ,complete all as specified and directed by Engr-in-charge. |
| 39 | M&L for asbestos rope of suitable size and superier quality for heat insulation including rapping arround the exhaust pipe and winding with wire mess and plastering with plaster of peris /white cement for smooth finishing all as specified and directed by Engr-in-charge. |
| 40 | Servicing of diesel engine generating set capacity upto 160 KVA repair/replacement of the following defective parts through authorised service engineer/mechanic . (a) Drain out the lubricanting oil from sump and refilling after proper cleaning. (b) Replace Engine Oil filter cartidge with same size. (c) Renew Fuel filter cartridge with same size. (d) Check tightness of all nuts and bolts. (e) Check adjustment of V belt for driving engine water pump and alternator. (f) Assembling complete old serviceable parts and replacement of old unserviceable parts by new one as per direction of Engr-in-Charge. (g) Testing of DG set after servicing as per Engr-in-Charge. (h) Cleaning of air cleaner filter after period of hrs run as specified by manufactures in manual. (Note : (i) Any minor parts such as screw, washers , split pin , circlip etc shall be supplied by the firm , rate for the same shall be deemed to be included in the unit rate quoted. (ii) The job shall be carried out after two, hundred hrs run/ as when required directed by Engr-in-Charge of DG set and shall be measured and paid separately, no of times carried out during entire period of contract . (iii) During servicing of engine oil shall be issued by Department. |
| 41 | Fuel filter |
| 42 | Engine oil filter |
| 43 | Air filter |
| 44 | Draining out old engine oil and refilling by multigrade engine oil 15W-40 (Servo) |
| 45 | Battery terminal |
| 46 | Fuel pipe |
| 47 | Hose pipe |
| 48 | Self starter repair |
| 49 | Oil seal and timing set |
| 50 | Control KVAR 3U2 Part No KVAR3U200000 |
| 51 | Radiator cleaning with acid and fins repair |
| 52 | Coolant |
| 53 | Battery leads |
| 54 | Fan belt |
| 55 | Fan belt for alternator |
| 56 | Taking out UNSV and supply and installing as in replacement of 12 volt 150 AH lead acid wet maintenance free battery including initial charging with necessary material connecting with battery lead of DG Set at sitecomplete all as specified and as directed by Engr-in-Charge. |
| 57 | Taking out UNSV and S&F new alternator 12/24 V DC Make:-Lucas.TVS,all including dismantling of defective alternator and replacement of burn outs, bolts, mounting clamp etc all as specified and directed by Engr-in-Charge |
| 58 | Repair/replacement of relay for capacity DG set 40 KVA to 160 KVA all as specified and directed by Engr-in-Charge. |
| 59 | Rewinding of Alternator Complete Including And Supply and replacement of copper Wire including suitable winding material rewinding the stator winding with exsting size,guage &wieght of super enamelled copper wire of approved make including replacement of all insulating material varneshing with approved grade and quality of insulating varnish during up,and heating the stator winding in the heat chamber ,insulating , assembling the alternator Complete.all as specified and directed by Engr-in-charge. |
| 60 | S&F in repair controller control module panel for diesel generator DSE7320 with manual /auto electronics suitable for 40 to 160 KVA DG Set complete all as specified and as directed by Engr-in-Charge. |
| 61 | Earthing complete with galvanised steel earth plate electrode 60 cm x 60 cm x 6.0mm thick buried directly in ground, (Earth pit not less than 2.25 mtr deep below ground level) with top edge of plate not less than 1.5 mtr below normal ground level, connected to and including 4 mm dia galvanised earth lead wire by means of bolts, nuts, check nuts and washers of galvanised standard iron or steel all as specified or indicated in electrical plate no 3 of MES Part-I, including testing on completion including the M&L of the following :- (a) Excavation and earth work for drilling hole for electrode in any type of soil. (b) PCC pit in cement concrete 1:2:4 type B-1 .c) Precast RCC cover with suitable handle 40 mm thick in PCC 1:2:4 type B-1, reinforced with welded steel wire fabric weighing not less than 1.87 Kg/Sqm. (d) Funnel with watering pipe of GI 20 mm nominal bore medium grade and copper lugs etc all as specified. (e) 15 mm nominal bore light grade GI protection pipe 5 mtr long for protection of earthing lead from mechanical injury or tempering. (f) Requisite quantity of common salt and charcoal. (g) Testing of earthing. Note : (a) On testing after completion of earthing, if the desired earth resistance is not obtained, the earthing will be re-done by the contractor at his own risk and cost to the entire satisfaction of the Engineer-in-Charge.(b) The contractor shall quote his rate considering taking down cost of existing unserviceable earthing. |
| 62 | Earthing complete with galvanised steel earth plate electrode 60 cm x 60 cm x 6.0mm thick buried directly in ground, (Earth pit not less than 2.25 mtr deep below ground level) with top edge of plate not less than 1.5 mtr below normal ground level, connected to and including 25 x 4 mm galvanised earth strip by means of bolts, nuts, check nuts and washers of galvanised standard iron or steel all as specified or indicated in electrical plate no 3 of MES Part-I, including testing on completion including the M&L of the following :a) Excavation and earth work for drilling hole for electrode in any type of soil. (b) PCC pit in cement concrete 1:2:4 type B-1. (c) Precast RCC cover with suitable handle 40 mm thick in PCC 1:2:4 type B-1, reinforced with welded steel wire fabric weighing not less than 1.87 Kg/Sqm(.d) Funnel with watering pipe of GI 20 mm nominal bore medium grade and copper lugs etc all as specified. (e) 40 mm nominal bore light grade GI protection pipe 5 mtr long for protection of earthing lead from mechanical injury or tempering. ( f) Requisite quantity of common salt and charcoal.(g) Testing of earthing. Note : (a) On testing after completion of earthing, if the desired earth resistance is not obtained, the earthing will be re-done by the contractor at his own risk and cost to the entire satisfaction of the Engineer-in-Charge.(b) The contractor shall quote his rate considering taking down cost of existing unserviceable earthing. |
| 63 | Earthing of machinery/equipment Installed at power house/substation complete with copper earth plate electrode 60×60cm.× 3.15mm thick, buried directly in ground (earth pit not less than 2.25 metres deep below ground level) with top edge of the plate not less'than 1.5 metres below normal ground level, connected to galvanised earth lead 20x3 mm Copper strip by means of bolts, nuts, check nuts and washers of galvanised iron or steel all as shown in electrical plate No. 3 connected to earthing test point all as specified or indicated including testing on completion. |
| 64 | Chemical Earthing complete with copper bonded electrode 17.2 mm directly in ground, earth pit not less than 3 mtr deep below ground level including 25 x 3 mm copper earth strip by means of bolts, nuts, check nuts and washers of all as specified, including testing on completion including the M&L of the following :a) Excavation and earth work for drilling hole for electrode in any type of soil. (c) pit cover with poly plast , testing of earthing result should be less than 1 to 2 ohm Note : On testing after completion of earthing, if the desired earth resistance is not obtained, the earthing will be re-done by the contractor at his own risk and cost to the entire satisfaction of the Engineer-in-Charge. |
| 65 | Repair/replacement of industrial RO CPVC pipe 15mm complete with accessories complete all as specified and directed by Engr-in-Charge. |
| 66 | Supply and fixing PVC clamps for CPVC including aasy complete all as specified and directed by Engr-in-Charge. |
| 67 | Servicing of industrial RO at Shashithar and Salyrachatta 23 Wing AF including carrying out maintenance and check alongwith following repairs (a) Drain out the pipe and Replace new pipe and fixing the same.(c) Cartridge (d) Check tightness of all fitting Note:- Any minor/major parts such as screws,fillet,membrane, washers,PVC fitting etc shall be supplied by the firm, rate for the same shall be deemed to be excluded in the unit rate quoted. |
| 68 | Supply membrane for industrial RO complete all as specified and as directed by Engr-in-Charge. |
| 69 | Supply and fixing UB for industrial RO complete all as specified and as directed by Engr-in-Charge. |
| 70 | Supply and Fixing in repair of dimmer stat 60 amps oil cooled single phase complete all as specified and as directed by Engr-in-Charge. |
| 71 | S&F in repairs copper wire 1.5 Sqmm FRLS green/red colour single core complete all as specified and as directed by Engineer-in-Charge |
| 72 | S&F in repairs copper wire 2.5 Sqmm FRLS green/red/black colour single core complete all as specified and as directed by Engineer-in-Charge. |
| 73 | M & L for industrial type metal socket enclosure with 240 volt MCB 20 Amps, with metal plug top complete all as specified incl taking down old unserviceable one. |
| 74 | Supply, Install, Testing and Commissioning of Factory fabricated Outdoor type totaly enclosed Sub LT Panel of size 0.9m x 0.7m x 0.45m made out of 3.15 mm thick CRCA sheet and angle iron of size 40 x 40 x 3 mm floor mounted type with aluminium bus bar of capacity 200 Amp - 04 Nos including two coats of spray synthetic enamel paint over a coat of red oxide, including Voltmeter, Ammeter with necessary CTs & PTs, Selector Switiches, Phase indication Lamps for Three Phase System, Control Panel & Power Panel Wiring, confirming to IS : 8623, IEC:60439 & CPRI Approved, protection class IP65 with the following accessories :- (a) MCCB FP, Thermal Magnetic Release, 415 Volts, 63 Amps16 KA-01 Outgoing- MCB TPN-02, Outgoing MCB SPN-03, 15 Amp socket with switch -03 Nos (b) Voltage stabilizer for automatic operation, single phase naturally air cooled indoor type & designed for input variation between 170 V to 250 V with output voltage stabilized at 230 V with accuracy of ± 2.5% and of capacity 5 KVA Please Enable Macros to View BoQ information |
| 75 | Supply, Install, Testing and Commissioning of Factory fabricated Outdoor type totaly enclosed Sub LT Panel of size 0.9m x 0.7m x 0.45m made out of 3.15 mm thick CRCA sheet and angle iron of size 40 x 40 x 3 mm floor mounted type with aluminium bus bar of capacity 200 Amp - 04 Nos including two coats of spray synthetic enamel paint over a coat of red oxide, including Voltmeter, Ammeter with necessary CTs & PTs, Selector Switiches, Phase indication Lamps for Three Phase System, Control Panel & Power Panel Wiring, confirming to IS : 8623, IEC:60439 & CPRI Approved, protection class IP65 with the following accessories :- (a) MCCB FP, Thermal Magnetic Release, 415 Volts, 63 Amps16 KA-01 Outgoing- MCB TPN-02, Outgoing MCB SPN-03, 15 Amp socket with switch -03 Nos (b) Voltage stabilizer for automatic operation, single phase naturally air cooled indoor type & designed for input variation between 170 V to 250 V with output voltage stabilized at 230 V with accuracy of ± 2.5% and of capacity 5 KVA Please Enable Macros to View BoQ information |