| 1 | Note : 1. The contractor should visit at site before quoting the tender to know the working condition of the station.2. All requisite safety measures adopted by contractor on site. 3. The contractor shall provide and deploy sufficient electrician ( as approved by GE/ Engineer in charge) shall report at 9.00 hrs to JE E/M / Engineer in charge to collect the complaints job card in working days and complete the same complaintwithin 24 Hrs. 4. The complaints shall be rectified with in 24 Hrs if the complaints is/ are not attended / not completed with in 24 Hrs ( except repair/ replacement of major items) recovery will be done Rs 500 per complaint per day. 5. For major parts like rplacement of MCB Dbs, MCCBs should be rectified within 5 working days, if the contractor not rectify within time then recovery will be done Rs 1000 per complaint per day.6. If contractor failed to provide their electrician or attend the complaints then recovery will be done Rs 1000 per day. |
| 2 | Material and Labour in replacement of old unserviceable sub main wiring using 4 runs of 10 sq mm FRLS ,IS 694 PVC insulated copper conductor 1100 Volts grade conforming to IS specification drawn through and existing conduit along with 1 runs of 10 sq mm PVC insulated copper conductor FRLS cable as earth lead connected to common earth dolly including making good the existing disturbed surface using wall putty and matching colour emulsion paint complete all as specified and directed. |
| 3 | All as per item No.2 here-in-before but of sub main wiring using 4 runs of 6 sq mm along with 1 runs of 6 sq mm as earth lead complete all as specified and directed. |
| 4 | All as per item No.2 here-in-before but of sub main wiring using 4 runs of 4 sq mm along with 1 runs of 4 sq mm as earth lead complete all as specified and directed. |
| 5 | All as per item No.4 here-in-before but with and including pvc casing and caping of suitable size:-Note for item No.2 to 5 :-(i) 5 runs of respective size of PVC insulated copper conductor cable including casing capping(as applicable) will be measured as one unit.(ii) Proper colour code to be followed strictly |
| 6 | All as per item no.2 here-in-before but for 2 run of 10 sqmm with 1 run of 10 sqmm for earth lead. |
| 7 | All as per item no. 2 here-in-before but for 2 run of 6 sqmm with 1 run of 6 sqmm for earth lead. |
| 8 | All as per item no. 2 here-in-before but for 2 run of 4 sqmm with 1 run of 4 sqmm for earth lead. |
| 9 | All as per item No.8 here-in-before but in pvc casing and caping of suitable size Note for item No.6 to 9 :-(i) 3 runs of respective size of PVC insulated copper conductor cable including casing capping(as applicable) will be measured as one unit.(ii) Proper colour code to be followed strictly |
| 10 | Material and Labour in replacement of old unserviceable sub main wiring using 2 runs of 2.5 sq mm FRLS ,IS 694 PVC insulated copper conductor 1100 Volts grade conforming to IS specification drawn through and including PVC conduit of suitable size not less than 20mm dia medium grade surface on wall along with 1 run of 2.5sq mm PVC insulated copper conductor FRLS cable as earth lead connected to common earth dolly including taking down old unserviceable wiring. And including making good the existing disturbed surface using wall putty and matching colour emulsion paint. complete all as specified and directed |
| 11 | All as per item No.10 above but in pvc casing and caping of suitable size:-Note for item No.10 to 11 :-(i) One run of PVC conduit/casing and caping along with 3 runs of respective size of PVC insulated copper conductor cable will be measured as one unit.(ii) Strictly follow the proper colour code red/yellow/blue for phase ,black for neutral and green for earth. |
| 12 | Supply and Fix in replacement MCB protected socket PVC plastic Base model with one single pole MCB, AC 240 Volts, 20 Amps including making good the existing disturbed surface using wall putty and matching colour emulsion paint complete all as specified and directed |
| 13 | Supply and Fix in replacement of old unserviceable MCB DB SPN 240V double door outdoor type with bush bar of appropriate current carrying capacity, neutral link, earth bar and din rail including making good the existing disturbed surface using wall putty and matching colour emulsion paint complete all as specified and directed |
| 14 | 4 way |
| 15 | 8 way |
| 16 | 12 way |
| 17 | Supply and Fix in replacement MCB DB TPN double door 200 Amps rated bus bar 415 Volts, AC supply fixed to the existing wall after removing the unserviceable MCB DB and reconnecting the electrical connections and making good the disturbed portion surfaces with same as existing wall complete all as specified and directed |
| 18 | 4 way |
| 19 | 8 way |
| 20 | Supply and Fix in replacement MCB tripple pole & neutral AC 415 Volts, 50 Hz , C series 10 kA breaking capacity, 25/32 Amps complete all as specified and directed |
| 21 | Supply and Fix in replacement MCB TPN 415 Volts 40-63 Amps ,C series, 415 volts ,50 Hz, 10 Ka breaking capacity complete all as specified and directed |
| 22 | Supply and Fix in replacement MCB single pole 6 to 32 Amps capacity,C series 230 Volts complete all as specified and directed |
| 23 | Supply and Fix in replacement MCB single pole and neutral 25/32 Amps capacity, C series, 10 KA, 50 Hz ,230 Volts complete all as specified and directed by Engineer in charge. |
| 24 | Supply and Fix in replacement MCB single pole and neutral 40 Amps capacity, C series, 10 KA, 50 Hz ,230 Volts complete all as specified and directed |
| 25 | Taking down carefully copper/ aluminium point wiring (light, fan and power socket etc) complete including fittings such as switches ceiling roses, pendent, regulators, sockets, etc and making good matching to the existing colour to the disturbed surface. |
| 26 | Material and Labour colour code point wiring FRLS PVC insulated and unsheathed cable with 1.5 sqmm copper conductor single core multistandred 1100 volt grade conforming to IS 694 drawn through PVC conduit of suitable size not less than 20mm dia medium grade concealed /open as per site reuirement including suitable size modular flush box fitted with modular cover plate with frame (inner/ outer plate) for mounting switches,regulators etc including FRLS 1.5 sqmm earth wire copper insulated wire connected to common earth dolly all including making good the existing disturbed surface using wall putty and matching colour emulsion paint complete all as specified and directed for the following:- |
| 27 | (a) One Light/ fan point controlled by one switch |
| 28 | (b) One 3 pin socket outlet outlet 5 Amps on the same board with other switches |
| 29 | (c) 5 Amps socket point on independent board |
| 30 | Material and Labour colour code point wiring FRLS PVC insulated and unsheathed cable with 1.5 sqmm copper conductor single core multistandred 1100 volt grade conforming to IS 694 drawn through PVC Casing and caping of suitable size, suitable size modular flush box fitted with modular cover plate with frame (inner/ outer plate) including FRLS 1.5 sqmm earth wire copper insulated connected to common earth dolly including making good the existing disturbed surface using wall putty and matching colour emulsion paint complete all as specified and directed for the following:- |
| 31 | (a) One Light/ fan point controlled by one switch |
| 32 | (b) One 3 pin socket outlet outlet 5 Amps on the same board with other switches |
| 33 | (c) 5 Amps socket point on independent board |
| 34 | All as per item no 22 here in before but 1.5 sqmm for 5/6 Amps socket on independent board. |
| 35 | All as per item no 22 here in before but 2.5 sqmm for 5/15 Amps socket on independent board. |
| 36 | Supply and fix in repair lamp holder,PVC/Polycarbonate type with back plate suitable to batten fittings. |
| 37 | Supply and Fix in replacement calling bell, ding dong AC 230 Volts, single pole complete all as specified and directed |
| 38 | Supply and Fix in replacement ceiling rose 3 terminal/PVC/polycarbonate isolated body |
| 39 | Supply and Fix in replacement modular switch one way 6 Amps 1 module .complete all as specified and directed |
| 40 | Supply and Fix in replacement modular socket 6 Amps 2/3 pin 2 module. complete all as specified and directed |
| 41 | Supply and Fix in replacement modular socket 6 Amps/16 Amps 3 pin 2 module multipurpose , complete all as specified and directed |
| 42 | Supply and Fix in replacement modular switch one way 16 Amps 1 way 1 module ,complete all as specified and directed |
| 43 | Supply and Fix in replacement modular two way switch 6 Amps 1 module,complete all as specified and directed |
| 44 | Supply and Fix in replacement modular bell push 6 Amps 1 module,complete all as specified and directed by Engineer in charge. |
| 45 | Supply and Fix in replacement modular fan step regulator, 2 module. complete all as specified and directed |
| 46 | Supply and Fix in replacement 16 Amps 3 pin Plug top complete all as specified and directed |
| 47 | Supply and Fix in replacement Switch socket combination 6A with box complete all as specified and directed |
| 48 | Supply and Fix in replacement Switch socket combination 15A with box complete all as specified and directed by Engineer in charge. |
| 49 | Supply and Fix in replacement Switch piano, flush type single pole, one way 5 Amp complete all as specified and directed |
| 50 | Supply and Fix in replacement Modular white cover plate with frame, 1 module. all as specified and directed |
| 51 | All as per item 39 here-in-before but 2 module.all as specified and directed |
| 52 | All as per item 39 here-in-before but 3 module.all as specified and directed |
| 53 | All as per item 39 here-in-before but 4 module.all as specified and directed |
| 54 | All as per item 39 here-in-before but 6 module.all as specified and directed |
| 55 | All as per item 39 here-in-before but 8 module.all as specified and directed |
| 56 | All as per item 39 here-in-before but 12/18 module.all as specified and directed |
| 57 | Supply and Fix in replacement modular box suitable for fixing 1/2 module all as specified and directed by Engineer in charge. The rate quoted for replcing of modular box deemed to be necessary cement/putty work and finishing work for white wash /colur wash matching with existing surface. |
| 58 | All as per item 46 here-in-before but 3 module.all as specified and directed |
| 59 | All as per item 46 here-in-before but 4 module.all as specified and directed |
| 60 | All as per item 46 here-in-before but 6 module.all as specified and directed |
| 61 | All as per item 46 here-in-before but 8/12 module.all as specified and directed |
| 62 | Disconnect electric connections and taking down carefully unserviceable flood light/ Highbay light fittings of different capacities at any location etc.opening of cover and body for repair/ replacement of electrical items and refixing the same or fixing only new items /fittings including connecting/ testing complete.Note(a) Fitting are fitted at up to 12 mtr height.The contractor shall arrange ladder/ scaffolding of required height at his own arrangement.The rates quoted are deemed to be included for the above provision. |
| 63 | Supply and Fix in replacement Energy saving, enviormental friendly, long life, exclusive innovative die cast aluminium IP 66 flood light 150 W LED complete all as specified and directed |
| 64 | Supply and Fix in replacement of old unserviceable wall mounted 20 W LED 4ft white batten with all accessories pre-wired and including connecting up 3 core flexible copper conductor cable suitable size from fitting to ceiling rose/connection terminals all as specified and directed |
| 65 | Supply and Fix in replacement old unserviceable wall mounted 10 W 2 ft LED batten, making connection to ceiling rose to fitting with 3 core 1 sqmm copper conductor complete all as specified and directed |
| 66 | Supply and Fix in replacement LED flat downlighter 18W white/warm white in round / square profile including connecting up 3 core 1 sqmm copper conductor cable from fitting to ceiling rose/connection terminals all as specified and directed |
| 67 | Supply and Fix in replacement LED flat downlighter 15W white / warm white in round / square including connecting up 3 core 1 sqmm copper conductor cable from fitting to ceiling rose/connection terminals all as specified and directed |
| 68 | Supply and Fix in replacement LED flat downlighter 12W white / warm white in round / square profile including connecting up 3 core 1 sqmm copper conductor cable from fitting to ceiling rose/connection terminals all as specified and directed |
| 69 | Supply and Fix in replacement 10 W white/warm white Environmental friendly, ultra modern, energy saving, surface mounted, decorative bulk head edge-lit LED making connection to ceiling rose to fitting with 3 core 1 sqmm copper conductor complete all as specified and directed |
| 70 | Supply & Fix in replacement High efficacy 1'x1' LED 18 watt recess type/surface full lit with suitable size from fitting to ceiling rose/connection all connected accessories with all accessories pre-wired and including connecting up with three core twisted flexible copper conductor cable with suitable size from fitting to ceiling rose/connection terminals and adjusting rings for fixing etc. |
| 71 | Supply and Fix in replacement Recess/Surface full 36 W (2'x2') with all accessories pre-wired and including connecting up with three core twisted flexible copper conductor cable with suitable size from fitting to ceiling rose/ connection terminals complete all as directed. |
| 72 | Supply and Fix in replacement capacitors 4 mfd, AC 440 Volts suitable for Exhaust fan. |
| 73 | Supply and Fix in replacement capacitors 2.5mfd, AC 440 Volts suitable for celling fan/exhaust fan all as specified and directed |
| 74 | Supply and Fix in replacement Decorative wall light (Globe Type ) fixture made up of poly carbonate suitable up to 1 x 9/10 W LED Bulb (B-22 base ) making connection to ceiling rose to fitting with 3 core 1 sqmm copper conductor complete all as specified and directed |
| 75 | Supply and Fix in repair 9 W LED lamp, BEE rated white/warm white with base B22 all as specified and directed |
| 76 | Supply and Fix in replacement of old unserviceable MCCB 3 pole 100 Amps 16/18 kA 415 Volts, 50 Hz suitable for existing busbar size complete all as specified and directed |
| 77 | Supply and Fix in replacement of old unserviceable single phase electronic meters temper proof LCD display with polycarbonate cover 230 V, 10- 60Amp, accuracy class-I 50Hz, IP-54, with parameters to show data, time, current reading, load, PF, voltage and KWH including taking down of old meter and deposit at MES. Note : Contractor has to deposit Old energy meters to MES for safe custody and it will be MES property and contractor has to submit the old meter Sl no, final reading of old meter, New meter Sl No, initial reading of the new meter for proper accounting of revenue. Please Enable Macros to View BoQ information |