| 1 | Providing and fixing of 9 Mtrs long hot dip galvanized octagonal pole with base plate made in single section, including erection of the pole on provided RCC Foundation with galvanized nuts, bolts etc as required. The following specifications should be adhered to for the pole & accessories:-a) Pole Top diameter - 70mmb) Pole bottom diameter - 155 mmc) Thickness of sheet - 3mmd) Galvanized Base plate of size - 260mm X 260 mm X 16 mme) Set of foundation nut & bolts - 4 Nos EN 8 grade galvanized 750 mm length having 24mm dia with galvanized nuts, washers and spacer plate . The pole shall be fixed using double nuts.f) The galvanization shall be more than 65 micron DFT both internally and externally and the pole shall be designed fora min wind speed of 169 km/hour.g) The steel used for manufacturing the pole shall conform to BS EN 10025 GRADE SJ355JO or equivalent and for base plate steel shall be Fe-410 conforming to IS 226 / IS 2062. h) The pole top should be suitably fixed to the bracket using Galvanized nuts and bolts of suitable length and dia. |
| 2 | Supplying, Fabricating & fixing of GI bracket of size 100 mm X 50 mm X 4 mm thick (NS) 'U' shaped channel having 1300 mm length with provision for fixing 04 Nos. LED flood lights with 04 Nos. holes, suitable size nuts, bolts and washers. Each hole shall have 02 Nos. slots for adjustment, including fixing of bracket on 70mm top dia octagonal pole, etc. as required as per direction of engineer-in-charge. |
| 3 | Installation, testing and commissioning of 1 set ( consisting of 04 Nos LED Fittings) on new octagonal pole after dismantling the existing luminaries from the old pole, including wiring with 3 core 1.5 sqmm PVC insulated copper cable from loop box to each LED fitting seperatly. The work includes dismantling and refixing of gear box and SPD box, if required, complete with suitable size with nuts, bolts, washers and flexible conduit on exposed portion, etc as required as per direction of engg-in-charge. |
| 4 | Providing and laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of 4 core X 25 sqmm size armoured cable laid directly in ground including excavation and refilling the trench etc as required, but excluding sand cushioning and protective covering. Make: Havells / KEI / R R Kabel / Polycab |
| 5 | Providing and laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of 3½ X 70 sqmm size armoured UG cable laid directly in ground including excavation and refilling the trench etc as required, but excluding sand cushioning and protective covering. Make Havells / KEI / R R Kabel / Polycab |
| 6 | Providing and laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of 3½ X 120 sqmm size armoured UG cable laid directly in ground including excavation and refilling the trench etc as required, but excluding sand cushioning and protective covering. Make : Havells / KEI / R R Kabel / Polycab |
| 7 | Providing and laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of 4 core X 25 sqmm size armoured cable in the existing RCC/ HUME/ METAL pipe as required.. Make: Havells / KEI / R R Kabel / Polycab |
| 8 | Providing and laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of 3½ X 70 sqmm size armoured UG cable in the existing RCC/ HUME/ METAL pipe as required. Make: Havells / KEI / R R Kabel / Polycab |
| 9 | Providing and laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of 3½ X 120 sqmm size armoured UG cable in the existing RCC/ HUME/ METAL pipe as required.. Make: Havells / KEI / R R Kabel / Polycab |
| 10 | Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 kV grade as required. 3.5 X 35 sq. mm (32 mm) |
| 11 | Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 kV grade as required. 3.5 X 70 sq. mm (38 mm) |
| 12 | Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 kV grade as required. 3.5 X 120 sq. mm (45 mm) |
| 13 | Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 kV grade as required. 4 X 25 sq. mm (28 mm) |
| 14 | Supplying and making straight through joint with cast resin compound including ferrules and other jointing materials for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required. 3½ X 35 sq. mm |
| 15 | Supplying and making straight through joint with cast resin compound including ferrules and other jointing materials for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required. 3½ X 70 sq. mm |
| 16 | Providing, laying and fixing following dia G.I. pipe (medium class) in ground complete with G.I. fittings including trenching (75 cm deep) and re-filling etc as required ( 50 mm dia ) |
| 17 | Supplying and laying of following size DWC HDPE pipe ISI marked along with all accessories like socket, bend, couplers etc. conforming to IS 14930, Part II complete with fitting and cutting, jointing etc. in the existing trench, complete as required. 40 mm dia |
| 18 | Supplying and laying of following size DWC HDPE pipe ISI marked along with all accessories like socket, bend, couplers etc. conforming to IS 14930, Part II complete with fitting and cutting, jointing etc. in ground (75 mm below ground level) including excavation and refilling the trench etc as required, but excluding sand cushioning and protective covering etc. complete as required. 90 mm dia (OD-90 mm & ID-75 mm nominal) |
| 19 | Supplying and laying of 40 mm size PVC pipe ISI marked along with all accessories like socket, bend, couplers etc. complete with fitting and cutting, jointing etc. from pole coller to loop box to protect the cable and dismentaling and reconnectioning with fresh thimbling etc complete as required. |
| 20 | Earthing with G.I. earth pipe 4.5 metre long, 40 mm dia including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe etc. with charcoal/ coke and salt as required. |
| 21 | Providing and laying earth connection from earth electrode with 6 SWG dia G.I. Wire in 15 mm dia G.I. pipe from earth electrode including connection with G.I. thimble excavation and re-filling as required. |
| 22 | Supplying and laying 6 SWG G.I. wire at 0.50 metre below ground level for conductor earth electrode, including connection/ termination with GI thimble etc. as required. |
| 23 | Providing and fixing 6 SWG dia G.I. wire on surface or in recess for loop earthing as required. |
| 24 | Providing and fixing 25 mm X 5 mm G.I. strip on surface or in recess for connections etc. as required. |
| 25 | Supply, installtion, testing and commissioning of an outdoor-type feeder panel made of 2 mm thick CRCA sheet, of desired size with minimum 400 mm depth, suitable for 415 V, 3-phase, 50 Hz power supply. The panel shall include hinged doors with locking arrangement, a detachable 3 mm thick gland plate at the bottom, earth bar/stud, cable alley, and aluminium busbars/ Copper cable of suitable size as per CPWD norms. All sheet metal parts shall be separately chemically treated via a 7-tank process and finished with powder coating in Siemens Grey shade (RAL 7032). Supply the panel with a suitable pedestal frame including 4 nos. 600 mm long legs of minimum 6 mm thick angle and a suitable apron all around. Embed the panel in a 1:3:6 cement concrete foundation of required shape and size, 30 cm below ground level, including finishing as required, as per the direction of the Engineer-in-Charge.(Make of panel: CPRI approved only)(Drawings to be approved by the department before fabrication.) |
| 26 | Supply, installtion, testing and commissioning of an outdoor-type feeder panel made of 2 mm thick CRCA sheet, of desired size with minimum 400 mm depth, suitable for 415 V, 3-phase, 50 Hz power supply. The panel shall include hinged doors with locking arrangement, a detachable 3 mm thick gland plate at the bottom, earth bar/stud, cable alley, and aluminium busbars/ Copper cable of suitable size as per CPWD norms. All sheet metal parts shall be separately chemically treated via a 7-tank process and finished with powder coating in Siemens Grey shade (RAL 7032). Supply the panel with a suitable pedestal frame including 4 nos. 600 mm long legs of minimum 6 mm thick angle and a suitable apron all around. Embed the panel in a 1:3:6 cement concrete foundation of required shape and size, 30 cm below ground level, including finishing as required, as per the direction of the Engineer-in-Charge.(Make of panel: CPRI approved only)(Drawings to be approved by the department before fabrication.) |
| 27 | Supply, Installation, Testing, and Commissioning (SITC) of Pole-Mounted Outdoor Looping Box Fabricated from 2 mm thick (non-sprinkling) CRCA/MS sheet, size 550 mm (W) x 325 mm (H) x 100 mm (D), with hinged front door, mounted on existing MS BFL pole using suitable nut bolts. Includes powder coating with approved shade. Supply and fix the following accessories (drawing to be approved by the department prior to fabrication)(Old Material will retained by contractor )i) 04 Nos. 20 mm x 5 mm aluminium bus bars on suitable insulator bases with sleeving.ii) 02 Nos. 40 mm x 5 mm MS flats welded to the box for mounting.iii) Din Bar for mounting of double pole MCB. |
| 28 | Supply installation testing and commissioning of 250A, 36kA breaking capacity Four Pole MCCB having Ics = 100%Icu, with thermal magnetic trip unit. Includes interconnections with suitable size aluminium bus bar/ copper cable and suitable size spreader link assembly etc complete as required as per direction of enggineer-in-charge. Make : Legrand/ Schnieder / Siemens/ABB |
| 29 | Supplying, installation, testing and commissioning of 160A, 36kA breaking capacity Four Pole MCCB having Ics = 100%Icu with thermal magnetic based releases, interconnections with suitable size aluminium bus bar and suitable size spreader link assembly etc complete as required as per direction of enggineer-in-charge. Make : Legrand/ Schnieder / Siemens/ ABB/ L&T |
| 30 | Supplying, installation, testing and commissioning of 160A, 36kA breaking capacity Four Pole MCCB having Ics =100% Icu, with thermal magnetic trip unit. Includes interconnections with suitable size aluminium bus bar/ copper cable and suitable size spreader link assembly etc complete as required as per direction of enggineer-in-charge. Make : Legrand/ Schnieder / Siemens/ABB / L&T |
| 31 | Supplying, installation, testing and commissioning of 125A, 36kA breaking capacity Four Pole MCCB having Ics = 100%Icu with thermal magnetic based releases, interconnections with suitable size aluminium bus bar and suitable size spreader link assembly etc complete as required as per direction of enggineer-in-charge. Make : Legrand/ Schnieder / Siemens/ ABB/ L&T |
| 32 | Supply, Installation, Testing, and Commissioning (SITC) of 100 A TPN Switch Disconnector Fuse Unit 100 A rating, open execution type, Three Pole and Neutral (TPN) switch disconnector fuse unit, fixed in existing panel. Includes connections with suitable rating bus bar/ copper wire and all associated accessories as required, complete as per the directions of the Engineer-in-Charge .( Old Material willretain by the contractor) Make : C&S/ Havells / Siemens/ ABB/ L&T |
| 33 | Supply, Installation, Testing, and Commissioning (SITC) of 100 A Enclosed TPN Switch Disconnector Fuse Unit 100 A rating, Three Pole and Neutral (TPN) switch disconnector fuse unit with sheet steel enclosure, fixed in existing panel. Includes connections with suitable rating bus bar/copper wire and all associated accessories as required, complete as per the directions of the Engineer-in-Charge. (Old Material willretain by the contractor) Make : C&S/ Havells / Siemens/ ABB/ L&T |
| 34 | Supply, Installation, Testing, and Commissioning (SITC) of 63 A Enclosed TPN Switch Disconnector Fuse Unit 63 A rating, Three Pole and Neutral (TPN) switch disconnector fuse unit with sheet steel enclosure, fixed in existing panel. Includes connections with suitable rating bus bar/copper wire and all associated accessories as required, complete as per the directions of the Engineer-in-Charge. (Old Material will retain by the contractor) Make : C&S/ Havells / Siemens/ ABB/ L&T |
| 35 | Supply, Installation, Testing, and Commissioning (SITC) of 32 A TPN Switch Disconnector Fuse Unit having 32 A rating, Three Pole and Neutral (TPN) switch disconnector fuse unit with sheet steel enclosure, fixed in existing panel. Includes connections with suitable rating bus bar/copper wire and all associated accessories as required, complete as per the directions of the Engineer-in-Charge. (Old Material willretain by the contractor) Make : C&S/ Havells / Siemens/ ABB/ L&T |
| 36 | Supply, Installation, Testing, and Commissioning (SITC) of 250 A rating, 4-Pole Manual Changeover Switch with open execution type, complete with operating handle kit and interconnections using suitable size aluminium bus bars, etc., as required per the directions of the Engineer-in-Charge. ( Old Material willretain by the contractor) Make : Legrand/ Schnieder / Siemens/ ABB/ L&T /C&S |
| 37 | Supplying and fixing of 5 amp to 32 Amp rating 240 volts 'C' series MCB of single pole in the existing junction box complete with connection, testing and commissioning etc as required. Make: Havells/ Legrand / Schneider / L&T |
| 38 | Supplying and fixing of 5 amp to 32 Amp rating 240 volts 'C' series MCB of single pole and neutral pole in the existing junction box complete with connection, testing and commissioning etc as required. Make: Havells/ Legrand / Schneider / L&T |
| 39 | Earth work in excavation by mechanical means (Hydraulic excavator) / manual means in foundation trenches or drains (not exceeding 1.5 m in width or 10 sqm on plan), ncluding dressing of sides and ramming of bottoms, lift upto 1.5 m, including getting out the excavated soil and disposal of surplus excavated soil as directed, within a lead of 50 m. All kind of soil |
| 40 | Filling available excavated earth (excluding rock) in trenches, sides of foundations etc. in layers not exceeding 20 cm in depth, consolidating each deposited layer by ramming and watering, lead up to 50 metres. |
| 41 | 1:4:8 (1 Cement : 4 coarse sand (zone-III) derived from natural sources : 8 graded stone aggregate 40 mm nominal size derived from natural sources) |
| 42 | Providing and laying in position specified grade of reinforced cement concrete, excluding the cost of centering, shuttering, finishing and reinforcement - All work up to plinth level : 1:1.5:3 (1 cement : 1.5 coarse sand (zone-III) derived from natural sources : 3 graded stone aggregate 20 mm nominal size derived from natural sources) |
| 43 | Centering and shuttering including strutting, propping etc. and removal of form work for :Foundations, footings, bases for columns |
| 44 | Steel reinforcement for R.C.C. work including straightening, cutting, bending, placing in position and binding all complete upto plinth level. Thermo-Mechanically Treated bars of grade Fe-500D or more |
| 45 | 12 mm cement plaster of mix : 1:4 (1 cement: 4 fine sand) |
| 46 | Credit for dismantled Sp-56 MS pole, pole bracket with looping box as is where is basic including dismentalig of old pole. Please Enable Macros to View BoQ information |