| 1 | Wiring for light point / Fan point / Exhaust Fan point / Call bell point with 1.5 mm2 FR PVC insutated copper conductor single core cable in PVC casing & capping with modular type switch, modular plate suitable size, G.I-box and earthing the point with 1.5 mm2 FR PVC insulated copper conductor single core cable etc. as reqd. |
| 2 | a) Light point ( Group B) - 11 Point |
| 3 | b) ceiling fan point ( Group B) - 3 Point |
| 4 | c) Exhaust fan point ( Group B) - 1 Point |
| 5 | Total |
| 6 | Wiring for light point / Power Plug point with 2 x 4 mm2 FR PVC insutated copper conductor single core cable in PVC casing & capping along with 1 no. 4 mm2 FR PVC insulated copper conductor single core cable for loop earthing etc. as reqd. |
| 7 | Wiring for circuit / Sub - main wiring along with wire with ( the following size of ) PVC insulated copper conductor single core cable in PVC cassing & capping etc. as reqd. |
| 8 | 1. 2 x 1.5 mm2 + 1 x 1.5 mm2 earth wire |
| 9 | 2. 2 x 2.5 mm2 + 1 x 2.5 mm2 earth wire |
| 10 | 3. 2 x 4 mm2 + 1 x 4 mm2 earth wire |
| 11 | Wiring for circuit / Sub - main wiring along with wire with ( the following size of ) PVC insulated Alconductor single core cable in PVC cassing & capping etc. as reqd. |
| 12 | 7. (3 x 25 mm2 + 1 x 16 mm2 ) + 2 x 16 mm2 as eartg wire |
| 13 | Providing and Fixings ( following capacity TP & N ) dis-connector fuse switch unit inside the existing cubical panel board with ISI marks HRC fuses including drilling holes in the cubical panel board, making connection as reqd. |
| 14 | 2. 100 amp TP & N |
| 15 | S/F Bus bar chamber with 4 strips bus bar of length 300 mm suitable for 100 amp capacity complete with all accessories i/c connection, earthing the body etc. as reqd. |
| 16 | S/F wall mounted metal board of welded construction with minimum 35 mm x 35 mm x6 mm angle iron frame work with 25 mm x 6 mm flat iro as intermediate members i/c painting etc as reqd. |
| 17 | S/F ( following way), single / double pole and neutral, sheet steel MCB distribution board, 240 V on surface / recessed complete with tinned copper bus bar neutral bus bar, earth bar, din bar, detachable gland plate, interconnection, phosphatized and powder painted including earthing etc. as reqd. ( but without MCB / RCCB / Isolator) |
| 18 | 3. 8 way single door |
| 19 | S/F ( following rating) double pole 240 V isolator in the existing MCB DB complete with connection, testing and commissioning as reqd. |
| 20 | 2. 63 amp |
| 21 | Supplying and fixing 5 amp to 32 amp rating 230 V 'B' series MCB for lighting and other load of (following poles) in the existing MCB DB complete with connection, testing and commissioning etc. as reqd. |
| 22 | 1. Single Pole |
| 23 | S/F 48 \\" sweep (1200 mm) A.C ceiling fan complete with down rod, canopy, 3 (three ) blades but without regulator etc. as reqd. ( Make Bajaj / Usha or similar ) |
| 24 | Supplying & Fixing stepped type electronic Fan Regulator on the existing modular plate switch box i/c connection but excluding modular plate etc. as reqd. |
| 25 | S/F 305 mm sweep exhaust fan complete with all accessories i/c connection etc. as reqd. |
| 26 | S/F 280 mm dia ceiling fitting with 11 W CFL Lamp cpmplete with carrier and back plate i/c connection etc. As reqd. |
| 27 | S/F suitable size G.I box with modular plate and cover in front on surface or in recess i/c P/F 3 pin 5/6 amp modular socket 5/6 amp modular switch, connection painting etc. as reqd. ( for light plug to use in non - residential building ) |
| 28 | S/F suitable size G.I box with modular plate and cover in front on surface or in recess i/c P/F 6 pin 15/16 amp modular socket outlet and 15/16 amp modular switch, connection painting etc. as reqd. ( for light plug to use in non - residential building ) |
| 29 | S/F 3 pin 5 amp ceiling rose on the existing junction box / wooden block i/c connection etc. as reqd. |
| 30 | Earthing with copper plate 600 mm x 600 mm x 6 mm thick i/c accessories and providing masonary enclosure with cover plate having locking arrangement and watering pipe etc. ( but without charcoal or coke and salt ) as reqd. |
| 31 | Extra for using salt and charcoal for G.I or copper plate earth electrode as reqd. |
| 32 | P/F 25 mm x 5 mm copper strip in 40 mm dia G.I pipe from earth electrode as reqd. |
| 33 | P/F 4 mm dia copper wire on surface or in recessed for loop earthing as reqd. |
| 34 | Sub-Head : I ( Internal Electrification ) |
| 35 | Single piece cast Al. with full glass cover integral luminaries ( IP66) HPSV - 70 W grey powder coated die-cast Al. housing complete with all accessories ( BGEST - 70 SV FG SHN WOB / BJOS 70 SV / MH ) ( 188505 / 160270 ) |
| 36 | S/F integarl HID lamp post top lantern HTMV 80 W with mushroom shape roto mould diffuser complete with accessories i/c connection etc. ( Ref code no. BJMPTI 80 MVLPF / 524810 ) |
| 37 | 3 Meter Mild Steel decorative Lighting pole for outdoor |
| 38 | 7 Meter Mild Steel street lighting single arm pole for outdoor |
| 39 | Sylix PVC 50 mm - 1.5 inch heavy garden water suction pipe 30 meter ( 100 feet approx) roll for garden, agriculture use, ultra light and flexible with PVC spiral ribbed. |
| 40 | Erection of street light standard pole of length ecceeding 4.5 metre but not exceeding 6.5 metres in cement concrete 1;3;6 ( 1 cement: 3 cource sand and 6: graded stone aggregate 40 mm nominal size) foundation i/c excavation and refilling etc. as reqd. |
| 41 | S/F 10 mm2 2 core PVC/XLPE insulated heavy duty armoured cable 1.1 KV grade. |
| 42 | S/F 1.5 sq. mm ISI marked, FR PVC insulated, single core copper conductor cable |
| 43 | S/F 1 or 2 module (75mm x75mm ) G.I box along with modular base and cover plate for modular switch in recess as reqd. |
| 44 | Supplying and fixing 5 amp to 32 amp rating 230 V 'B' series MCB for lighting and other load of single poles in the existing MCB DB complete with connection, testing and commissioning etc. as reqd. Please Enable Macros to View BoQ information |