| 1 | Wiring of light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq. mm nominal size FR PVC insulated unsheathed flexible class 2 copper conductor 1.1 kV grade and 1.5 sq. mm nominal size FR PVC insulated unsheathed flexible class 2 copper earth conductor 1.1 kV grade (IS:694) in recessed ISI marked MMS ( IS:9537 P - III ) PVC conduit & it's ISI marked (IS:3419-1988) accessories, Aluminum round tiles, 1.2 mm thick Hot Dipped Galvanized Modular Box with earth terminal, 6 A Modular switch, Modular face plate with grid plate, 3 pin ceiling rose / Holder /3 way connector, screws, making connections, testing etc. as required. |
| 2 | Short point (up to 3 mtr.) |
| 3 | Medium point (up to 6 mtr.) |
| 4 | Long point (up to 10 mtr.) |
| 5 | Wiring of 3/5 pin 6 amp. Light plug point with 1.5 sq. mm nominal size FR PVC insulated unsheathed flexible class 2 copper conductor 1.1 kV grade and 1.5 sq. mm nominal size FR PVC insulated unsheathed flexible class 2 copper earth conductor 1.1 kV grade(IS:694) in recessed ISI marked MMS ( IS:9537 P - III ) PVC conduit & it's ISI marked (IS:3419-1988)accessories, Hot Dipped Galvanized Modular box of 1.2 mm thick with earth terminal, 6 A modular switch, 3/5 pin 6 A modular socket, Modular face plate with grid plate, screws, making connections, testing etc. as required. |
| 6 | On board |
| 7 | S&F following sizes (dia.) of ISI marked MMS ( IS:9537 P - III ) PVC conduit along with ISI marked (IS:3419-1988) accessories as required in recess including making jhiri in the wall,clamps at suitable spacing, covering conduit and making good the same as required. |
| 8 | 20 mm |
| 9 | 25 mm |
| 10 | Supplying and laying FR PVC insulated & unsheathed flexible copper conductor of following nominal sizes with ISI marked (IS:694) and as per IS 8130 : 2013 of 1.1 kV grade . Wire should be made from copper, stranding in acc. to IS:8130/IEC 60228 for lower watt loss , oxygen free for less chances of oxidization, insulation PVC type A/C/D , flame retardant as per IS 10810-53, better amperage rating as per IS:3961 part 5, in existing surface or recessed PVC/ MS conduit/casing capping making connections with Copper Lugs of suitable size, Ferrules,testing etc. as required. |
| 11 | 3x 1.5 sq.mm |
| 12 | 2 x 2.5 sq. mm. + 1x1.5sqmm |
| 13 | 2 x 4.0 sq. mm. + 1 x 2.5 sq. mm. |
| 14 | Providing & Laying XLPE insulated & P.V.C. sheathed Armoured Aluminium cable confirming to IS :7098 P - I of 1.1 KV with H4- Grade electrolytic aluminium conductor confirming to IS 8130 of purity >99.6 %, round / flat strip armouring of cables, Inner / outer sheath confirming to IS:5831 in existing RCC / Hume / Stoneware / PVC pipe/ open duct/cable trench / Cable tray(with cable tie) including testing commissioning etc. as required of following size. |
| 15 | 70.0 Sq. mm |
| 16 | 3.5 core |
| 17 | 50.0 Sq. mm |
| 18 | 3.5 core |
| 19 | 16.0 Sq. mm |
| 20 | 4 core |
| 21 | Providing & Fixing of 240/415 V AC MCB with positive isolation of 10 kA breaking capacity (B/ C/D tripping characteristic as per type of load and site requirement) 4 KV impulse withstand voltage, ISI marked IS 8828(1996) / conforming to IEC 60898-1 2002, IEC 60947-2, low watt losses, trip free mechanism , energy limiting of class 3 as per IEC, minimum phase termination capacity of 25 sq.mm., conductor line load reversibility , IP 20 contact protection and fitted in existing distribution board/sheets, minimum electrical operation 20,000 upto 20 A rating, 10,000 upto 63 A, 5000 for 80 A & above rating including making connections, testing etc. as required. |
| 22 | Single pole MCB (With B / C curve tripping characteristics) |
| 23 | 6 A to 32 A rating |
| 24 | Triple pole MCB (With B / C curve tripping characteristics) |
| 25 | 40 A rating |
| 26 | Four pole MCB (With B / C curve tripping characteristics) |
| 27 | 50/63 A rating |
| 28 | Providing & Fixing of Recessed/surface mounting heavy duty horizontal type Double Door (Metal / Glazed / Acrylic) Distribution board with Metal end box made out from Galvanized steel / CRCA sheet, powder coated conforming to IS-8623-1 & 3 / IEC 61439- 1 & 3, complete with 100 amp. insulated copper bus bar/shorting link , brass neutral link with shrouds, brass earth link , door earthing arrangement, color coded interconnecting wire set of minimum 10.0 sqmm size and din bar,masking sheet, making internal DB terminations with copper lugs, Ferrules, detachable gland plate, including making connections, testing etc. as required. |
| 29 | Metal door (Three phase) Per phase isolation, Horizontal IK-09 and IP-43 with Metal end box |
| 30 | 6Way {8 Incomer + 6 Sub Incomer (2+2+2) + 18 out going } |
| 31 | Providing & Fixing of ISI marked (IS:302) gong bell with CM/L no. printed including making connection testing etc. as required. |
| 32 | Providing & Fixing of single / multi tone electronic call bell / remote bell including making connection testing etc. as required. |
| 33 | Providing & Fixing of ISI marked (IS:302) ding dong/musical chime bell including making connection testing etc. as required. |
| 34 | Providing & Fixing of modular type switch/ bell push duly ISI marked (IS :3854) with CM/L no. printed and made out of unbreakable and fire retardant virgin UV Stabilized Polycarbonate with brass terminals and captive screws & silver alloy contact tip with IP-20 rating ,minimum width of switch toggle( PUSH PART ) should not less then 20mm, including making connections, testing etc as required. |
| 35 | 6 A bell push |
| 36 | Providing & Fixing of modular type 100W Step Fan regulator duly ISI marked (IS 11037) with CM/L no. printed made out of unbreakable and fire retardant virgin poly carbonate with brass terminals and captive screws & silver alloy contact tip with IP-20 rating , including making connections, testing etc as required. |
| 37 | 5 step fan regulator 2 Module |
| 38 | Providing & Fixing of modular type switch/ bell push duly ISI marked (IS :3854) with CM/L no. printed and made out of unbreakable and fire retardant virgin UV Stabilized Polycarbonate with brass terminals and captive screws & silver alloy contact tip with IP-20 rating ,minimum width of switch toggle( PUSH PART ) should not less then 20mm, including making connections, testing etc as required. |
| 39 | 32 Amp. 2 Module switch With Led Indicator |
| 40 | Providing & Fixing of IS:1293 marked modular type lockable feature socket with CM/L no. printed duly made out of unbreakable and fire retardant virgin poly carbonate with brass terminals and captive screws & silver alloy contact tip with IP-20 rating, including making connections, testing etc as required. |
| 41 | 6/16 A shuttered socket |
| 42 | Providing & Fixing of following modular accessories, made out of unbreakable and fire retardant virgin poly carbonate with brass terminals and captive screws & silver alloy contact tip with IP-20 rating, including making connections, testing etc as required. |
| 43 | RJ-11 telephone jack single line |
| 44 | T.V. coaxial socket |
| 45 | LED Skirting /Foot Light 2 Module |
| 46 | Modular MCB 6 A to 32 A SP |
| 47 | Modular MCB 6 A to 32 A DP |
| 48 | Providing & Fixing of Recessed/surface mounting heavy duty Enclosure made out from Galvanized steel / CRCA sheet, powder coated conforming to IS-8623-1 & 3 / IEC 61439- 1 & 3. complete with din rail making internal DB terminations with copper lugs, detachable gland plate, including making connections, testing etc. as required. |
| 49 | Suitable for Two / Three / Four module for MCB |
| 50 | Supplying and Laying PE Insulated & PVC Sheathed unarmoured telephone cable with 0.5 mm dia. Solid Annealed electrolytic grade bare Copper Conductor as per IS: 8130/84 & confirming to TEC specification GR / WIR/06-03 March 2002 in existing surface or recessed conduit/casing capping. including ferruling on each pair for Identification etc. as required. |
| 51 | 2 pair |
| 52 | Providing & Fixing of following size cover plates made from fire retardent UV established high performance engineering plastic suitable for all universal metal boxes for front installation & removal direct fit type complete in all respect. |
| 53 | 3 Module |
| 54 | Providing & Fixing of Hot dipped Galvanized metal box of 1.2 mm thick with earthing terminal and adjustable floating clamp in recess/ surface suitable for modular accessories as required. |
| 55 | 3 Module |
| 56 | Supplying and fixing of power plug point with Modular accessories on hot dipped galvanized modular box of 1.2 mm thick with earthing terminal/connector on surface or in recessed with suitable size of modular face place with grid plate and cover plate including cost of ISI marked modular 16 amp. Switch (IS :3854) and 6/16 amp. socket outlet (IS:1293) making connection , testing , etc. as required. |
| 57 | SITC of Copper Bonded rod Earthing with high tensile strength (more than 600 N / sq.mm low carbon steel rod molecularly bonded with Copper thickness (250 microns) and confirming to UL 467 of following size and length and as per point mentioned (a), (b), [c), (d), (e) below :- |
| 58 | (a) Bore a hole of dia. 100 mm of required length, Place the rod in the centre of Hole |
| 59 | (b)Earth enhancing compound to ensure the moisture content and electrical conductivity, 25 kg for 3000 mm. The compound shall be tested form NABL accredited lab for low resistivity (less than 0.12 Ohm - meter) & high conductivity in nature with carbon as a major content in accordance with IEC 62561-7 |
| 60 | © Connect the rod with copper Strip/Conductor/Wire with suitable clamp made from tinned copper and SS 304 Bolt |
| 61 | (d) Place Heavy duty weather proof poly-propylene earth inspection chamber as per requirement of IS/IEC 62305 and tested as per IEC 62561-5 with lockable Jam free lid suitable for safe working load 60 kN of round / square size 250 mm, and Height 250 to 300 mm. |
| 62 | (e) Testing of earth resistance for value of 5 ohms or less as required. |
| 63 | (f) Test certificates for confirming above standards from OEM is mandatory. |
| 64 | 17.2 mm thick and 3 Mtr. Long |
| 65 | Supply & Laying following size earth strip in horizontal or vertical run in surface by means of Earth strip DMC Insulator including riveting/ soldering/ welding, Jointing shall be done by overlapping double the width of strip and with 2 set of Brass (for Cu strip) / GI (for GI Strip) nut bolt & spring washer spaced at 50cm making connection etc. as required. |
| 66 | 25mm x 6mm G.I. ( Hot Dipped ) Strip |
| 67 | Supply & Laying following size earth wire in horizontal or vertical run in ground/surface/recess including riveting, soldering, saddles, making connection with GI/Cu purity purity >95% thimble etc. as required. |
| 68 | 10 SWG G.I. ( Hot Dipped ) Wire |
| 69 | Providing & Fixing of BEE Star rated copper wounded with class of Insulation 'F', double ball bearing capacitor start, aluminium body & aluminium blade ceiling fan conforming to all the performance requirements laid down in IS 374:2019 with down rod up to 30 cm with secondary support safety cable ( steel rope) , cotter pin, shackle kit with 3 x 1.5 sq.mm pvc insulated flexible copper conductor and making connection testing etc. as required. |
| 70 | 1200 mm Sweep BEE 2 Star rated (service value >=4.5 to < 5 ) |
| 71 | P & F 1.2 mm thick M.S. Recessed fan box and top lid screwed on Box, hexagonal/ round of size 130 mm dia, depth 75mm, 12 mm dia rod fan hook with 150 mm length extended on each side as required. |
| 72 | Providing & Fixing of of Double ball bearing, copper wounded capacitor start single phase metallic blade fresh air fan, in existing opening including cost of hardware , flexible 3 core 1.5 Sq.mm copper conductor ,making connections, testing etc. as required. |
| 73 | 300 mm sweep Minimum air delivery 1600 Cum / hour |
| 74 | Providing & Fixing of Wall mounting / Pedestal type Heavy duty Air Circulator , Double ball bearing and with metal sturdy mesh guard; Aluminium alloy one piece blade and conforming to IS:2997, including fixing with anchor bolts, making connection testing etc. as required. |
| 75 | 450 mm sweep Wall mounting and three speed regulator with Minimum Air Delivery 150 Cum. / Minute |
| 76 | Providing & Fixing of extra down rod of 15 mm dia . ERW (Electrical resistance welded ) of 1.6mm nominal thick medium duty steel pipe including cutting, threading, drilling, fixing quarter pin etc as required. |
| 77 | P & F of Gravity Louver shutter of superior quality made out of frame of 18 swg M.S. sheet & Louvers made from 24 swg MS Sheet with enamel paint including cost of nuts, bolts, etc as required. |
| 78 | Up to 380 mm size |
| 79 | Providing & Fixing of Vertical(BEE 5 star rated) / Horizontal( BEE 3 star rated) storage water heater with outer casing made of Engineering Plastic sheet (Upto 25 Ltr) / Metal rust proof Body (35 & 50 Ltr), Glass - line / Titanium Enamel coated Pressure Pump Compatible 8 bar pressure Inner tank, Glass Line Coated , mineral filled heating element, stem type, snap action adjustable thermostat , Dual indicating lamps Injected PUF insulation, Multi Function Valve etc. as required held in position with 2/4 no. 10/12 mm anchor Fastener, duly wired with 3 core 2.5/4.0 Sqmm PVC insulated & sheathed copper conductor and 16 A/25A three pin plug top , including making inlet, outlet Flexible alloy connection, testing etc. as required. |
| 80 | 15 Ltr. |
| 81 | SITC of 3 /4 pole current limiting Moulded case circuit breaker (MCCB) made of flame retardent & heat resistant material having following current rating, short circuit breaking capacity at 440/415 V, 50 Hz; O/L & S/C settings , conforming to IS/IEC 60947 P -2 :2003 with front face and centralised adjustable, trip free mechanisum, true contact position indicator, designed for both horizontal & vertical mounting without any adverse effect on electrical performance, suitable for operation from 50 to 55 degree and without derating upto 40 degree, pollution degree 3, having positive isolation capability, push (test) to trip, trip time less then 10 ms under s/c condition, Breaking capacity Ics = 100% Icu. U imp =8 KV, rated insulation voltage 690V. provision for UVR , shunt trip , earth fault trip, door interlock, pad lock & rotary handle ( to be paid extra) , including making connections etc. as required. OEM shall have submit NABL / CPRI / ERDA/ Intertek accrediated lab type test certificate. |
| 82 | 4 pole MCCB With Thermal Magnetic release |
| 83 | up to 100 Amp , 25 kA, adjustable O/L & Fixed S/C setting, |
| 84 | 125 Amp , 25 kA, adjustable O/L & Fixed S/C setting, |
| 85 | 250 Amp , 25 kA, adjustable O/L & adjustable S/C setting, |
| 86 | 800 Amp , 50 kA, adjustable O/L & adjustable S/C setting, |
| 87 | Providing & Fixing of 240/415 V factory fitted RCBO with overload, short-circuit and earth leakage protection with ISI marked (IS12640-2)/ conforming to IEC 61009-1, breaking capacity 10 KA, provision for pad lock, min. Electrical operation 10,000 upto 63 A rating , minimum phase termination capacity of 25 sq.mm. , IP 20 contact protection with existing distribution board / sheet including making connections, testing etc. as required. |
| 88 | Two pole 30 mA sensitivity |
| 89 | 40 A rating |
| 90 | SITC of IP-43 surface mounting heavy duty modular Sub main Distribution board (SMDB) fabricated by MCCB OEM in his own factory having short circuit withstand current 35 kA (upto 400 amp.Incomer ) and 50 kA for 630 amp. Incomer with suitable bottom cabling box, 4 no. corner boxes, 2 no. side cabling boxes, metering Extension box with provision of incomer suitable for 3/4 pole MCCB and 3/4 pole MCCB as outgoing, Ammeter, Voltmeter, Indicating lamp, made out from Galvanized steel / CRCA sheet of 1.2/1.6 mm thick conforming to IEC 61439 Part 1 & 2. , U imp 8 KV, form of separation 2b, powder painted complete with insulated suitable rating tinned copper bus bar, neutral bars with shrouds, earth bar , din bar, making internal DB terminations with copper lugs, detachable gland plate, including making connections, testing etc. as required. (Without MCCB, ammeter, voltmeter, selector switch , Indicating lamp) |
| 91 | SMDB with 630 Amp. Incoming and 10 no. 100 Amps + 2 No. 250 amp. Outgoing |
| 92 | Providing & Fixing of IS: 13875 & IEC :61326/IEC:62053-22 confirming LED Digital type (up to 500) V range Volt meter / Direct- Ammeter / CT opertated ammeter/ Frequency meter / KWH meter / Multi Function Meter / Power analyzer of class 1 accuracy of size 96mm x 96 mm including making connection by PVC insulated copper conductor with PVC sleeves / channel etc. as required. |
| 93 | Three phase Ammeter with Inbuilt Selector Switch |
| 94 | Three phase Voltmeter with Inbuilt Selector Switch |
| 95 | Providing & Fixing of Current Transformer confirming IS 2705-I (1992) with secondary terminal and shorting Block , with all necessary support in existing panel including connection etc. as required Current transformer Ring Type Tape Wound/Resin Cast Wound Accuracy Cl, CT ratio and burden as specified. ISF<=5, Cu cross section of secondary wire 1.5sqmm (minimum), including all necessary support in existing panel including connection etc. as required . |
| 96 | Ring type tape wound CT |
| 97 | C T Class 1, Ratio 200/5 to 600/5, Burden 10 VA |
| 98 | Providing & Fixing of 110/220 V, unibody LED Indicating lamp IEC 60947 with integral circuit, IP 65 above panel & IP 20 terminal block, Approx. body dia for panel not less then 20 mm, length min. 50mm, front LED cover dia min. 27 mm, contact material phospher bronze for Led, PCB contacts shall be of brass (tin plated), impulse dielectric tested for 2.5 KV, Rated insulation resistance shall be 100 M ohm at 500VDC including connection etc. as required. |
| 99 | Red/yellow/Green colour |
| 100 | Providing & Fixing of CT linked selector switch of 10 A for Ampere meter (4 position ) using high grade engineering material to international standards with cam assembly insulation of glass filled polyamide with high tracking index. For reliable and stable electrical and mechanical endurance double butt contacts with silver bi-metal on copper should provided . contact assembly is of operating temp range 25 degree C to 55 degree C, frequency upto 10 KHz. switch life under standard operating conditions shall be mechanically minimum 50000 operations @300 cycles/ hour and electrically 10,000 operations at 100% rated duty for 100 cycles/ hour , including making connection etc. as required . |
| 101 | Providing & Fixing of on load change over switch, front handle operated, four pole 415 V confirming to IS/lEC 60947-3 : 1999 including connections , testing etc. as required .in the following rating. |
| 102 | 630 A |
| 103 | Supply and fixing of following accessories for Moulded case circuit breaker (MCCB) compatible to main MCCB OEM as per PWD specification for electrical Works, conforming to IS/IEC 60947 P - 2 :2003 including making connection etc complete in all respect. |
| 104 | Spreaders upto 125A, 3 Pole MCCB |
| 105 | Spreaders for 250A, 4 Pole MCCB |
| 106 | Spreaders for 800A, 4Pole MCCB |
| 107 | Providing & Fixing of 3 M Key card switch with Load capacity 20 amp, Off time delay 30 Sec. made out of unbreakable and fire retardant virgin poly carbonate, including making connections, testing etc as required. |
| 108 | SITC of following diagonal size professional Display, 4k Resolution, Brightness(Typ.) 440 nit and above , Contrast Ratio-2000:1 and above, Viewing Angle(H/V)-178/178, Response Time(G-to-G) 8ms, Input: RGB- Analog D-SUB, Video- HDMI 2.0 (2), HDCP- HDCP 2.2, Audio- Stereo mini Jack, USB- Only F/W upgrade, Outputs: RGB- DP1.2(Loop- out), Audio- Stereo mini Jack, External Control- RS232C(in/out), RJ45, External Sensor Detachable type(IR Ambient). Operation Hour 24/7. mounting bracket etc. as required. |
| 109 | Providing & Fixing of IK08 IP65 protected 600-800 mm height LED Bollard Luminarie with base plate made of powder coated die cast aluminium housing with UV stabalized PC diffuser. The System level Luminous efficacy ≥ 80 Lumen/W. SMD LEDs is to be used, System CRI>70, CCT: 3000/4000/6500 K. The integral electronic driver must be potted & has a unique BIS R number constant current and Internal/external surge protection device of min. 4KV(L-N) and efficiency > 85%, PF>0.9, THD<20% and input Voltage range of 90-270V AC at 50Hz. System life of 30000 Burning hours with 70% of Initial Lumens maintained Light output in Cool white or Warm White Colour as per engineers choice. LED driving output current <750mA. as required. |
| 110 | Minimum lumen output 800 lm Bollard |
| 111 | Supply & laying service connection with ISI marked (IS:694) 1100 Volts grade PVC insulated flat twin core sheathed solid aluminium conductor with 10 SWG G.I. Support wire duly clipped etc. as required. |
| 112 | 2.5sq.mm |
| 113 | SITC of Auto main failure (AMF) Panel fabricated from CRCA sheet steel 2 mm Thick , Powder coated finish , Engine Start & Stop commands, control Relays , Ammeter & Voltmeter with selector switches, Control & 2 nos of required size 4 pole AC1 duty Power Contactors with 2 no. of required size 4 pole MCCB with Icu=100% Ics 25KA breaking capacity upto 200KVA & 50 KA above 200 KVA rating with adjustable O/L & fixed Short circuit, Timers, Electronic Hooter ,Visual & Alarm indication for faults, UPS, operator interface panel complete in all respect suitable for following capacity DG sets: ( M S / RCC structure required for AMF panel will be paid extra ) |
| 114 | 50 to 82.5 KVA |
| 115 | Supplying and fixing of Aluminium (IEC 60105 ISO 209-1,2) / Copper (IEC 60028) bus bar by means of SMC / DMC type insulator, with short circuit withstand capacity of 31 MVA for 1 Sec. , high tensile nuts and bolts spring washers in existing panel including bending , cutting in required shape and size and colour coding with heat shrinkable PVC sleeves. |
| 116 | Electrolytic grade Aluminium bus bar 6010 grade |
| 117 | Providing & Fixing of Current Transformer confirming IS 2705-I (1992) with secondary terminal and shorting Block , with all necessary support in existing panel including connection etc. as required Current transformer Ring Type Tape Wound/Resin Cast Wound Accuracy Cl, CT ratio and burden as specified. ISF<=5, Cu cross section of secondary wire 1.5sqmm (minimum), including all necessary support in existing panel including connection etc. as required . |
| 118 | Ring type tape wound CT |
| 119 | C T Class 1, Ratio 200/5 to 600/5, Burden 10 VA |
| 120 | Providing & Fixing of 110/220 V, unibody LED Indicating lamp IEC 60947 with integral circuit, IP 65 above panel & IP 20 terminal block, Approx. body dia for panel not less then 20 mm, length min. 50mm, front LED cover dia min. 27 mm, contact material phospher bronze for Led, PCB contacts shall be of brass (tin plated), impulse dielectric tested for 2.5 KV, Rated insulation resistance shall be 100 M ohm at 500VDC including connection etc. as required. |
| 121 | Red/yellow/Green colour |
| 122 | Providing & Fixing of Recessed/surface mounting heavy duty Vertical TPN Distribution board with Metal end box with provision of incomer suitable for 3/4 pole MCCB and SP / TP MCB up to 63 Amps. as outgoing ,made out from Galvanized steel / CRCA sheet , powder coated conforming to IS-8623-1 & 3 / IEC 61439- 1 & 3. complete with insulated 125/160/200/250 Amp. copper bus bar, brass neutral bars with shrouds, brass earth bar , color coded interconnecting wire set of suitable rating and din bar, door earthing arrangement, masking sheet, making internal DB terminations with copper lugs, ferrules, detachable gland plate, including making connections, testing etc. as required. |
| 123 | Double door IP-43 & IK-09 with Provision of Incomer MCCB 200/250 A Rating with metal End Box |
| 124 | 6 Way |
| 125 | Supply & laying service connection with ISI marked (IS:694) 1100 Volts grade PVC insulated flat twin core sheathed solid aluminium conductor with 10 SWG G.I. Support wire duly clipped etc. as required. |
| 126 | 6.0 sq.mm |
| 127 | Providing, Fixing, Jointing, Testing & Commissioning of Medium duty MS B class pipes conforming to IS 3589 / 1239 part-I for DG Exhaust applications (beyond 1.5 Mtr. length) including cutting, welding etc & fittings like elbows,flanges, tapers, reducer, gaskets etc. fixing the pipe on the wall/ceiling with suitable clamps, hanger and nuts bolts . including the cost of thermal insulation with 50 mm thick layers of LRB rock wool as per IS : 8183-1993 (64 kg/m3 density) & 26 SWG aluminium sheet claddings etc complete as required complete in all respect. (Cost of Steel Structure for Exhaust pipe will be paid Extra). . |
| 128 | 100 mm dia |
| 129 | SITC of IP20 SMD Mid Power LED batten type integrated light fixture made from Powder coated Extruded aluminium housing with in built driver , System lumen efficacy ≥ 110 lm/Watt output only at CW (5700K to 6500K) , internal surge protection of 4.0 KV with Short & Open circuit protection ,THD < 10% , P. F.≥0.95, CRI >80 , life time of minimum 50000 Burning Hours with , 70% of intial Lumen maintaned till life ends , CCT 3000°K / 4000°K / 5700°K /6000°K/6500°K (As per ANSI Bin) as required. |
| 130 | 1170mm(+/-10%) LED batten with min. lumen output 2200 lm , 20W |
| 131 | SITC of IP-20 LED Recessed / Surface Mounted, Round / Square backlit & SMD Mid Power LED Downlight with power coated die-cast aluminum housing with UV Stabilized non yellowish Diffuser with BIS compliance 4.0 KV surge protected Isolated driver, with Short & Open circuit protection input 320VAC-48 hr protection, input 350VAC-2 hr protection), having efficiency > 85% . System Lumen efficacy of ≥ 110 lm / watt,at CW (5700K to 6500K) , THD < 10 % , Pf.≥0.95, CRI >80, life time of minimum 50000 Burning Hours with , 70% of intial Lumen maintaned till life ends , CCT 3000°K / 4000°K/ 5700°K /6000°K/6500°K (As per ANSI Bin) as required. |
| 132 | Surface Mounting (with extruded alumn. Housing ) |
| 133 | Minimum lumen output 2400 lm , 22W |
| 134 | Providing & Fixing of Street light bracket made out from following size of ' B ' class , Medium class G.I. Pipe confirming to IS : 1239 P - 1 ( 2004 ) with heavy duty pole clamp, Saddles suitable fastners etc. as required. |
| 135 | 25 mm Dia. |
| 136 | Providing & Fixing of IK08, IP 66 protected LED Street Light Luminaire on existing bracket/pole. Fixture made of powder coated single piece pressure die cast aluminum material with heat dissipation fins on housing with UV stabilized PC (UV stablization report submitted for UV cover ) /Toughened Glass cover and secondary lens on each LED/ integrated lens diffuser & should be High power LED of 3 to 5 watt each . The System efficacy >=125 lm/ wt and integrated metal case potted driver & has a unique BIS R number ( as per IS 15885) with Input Voltage AC 120 to 270 V AC with High voltage Cutoff @>=300 V AC & Low Voltage cutoff @>=90 V AC and Auto resetting Safety , Power Factor >0.95 driver Efficiency >85% ,THD(I) <10% Humidity 10% to 90% RH Working Temp -5C to 45C . LED driving output current <750mA. The luminaire shall be BIS certified (Fitting & driver both have separte BIS R number) and Trade mark certified. Life Expectancy Equal or more than 50000 burning hrs with Minimum 70% lumen maintened , CRI >70 and CCT 5700K +355K. Surge protection shall be min ≥ 4 KV internal and min 10 KV external inside driver compartment. driver should be Phase to phase protection of 440 V for 4 Hrs as required. |
| 137 | LED Street Light fixture with Minimum lumen output 12500 lm , 100W |
| 138 | Supply, Drawing and Testing of 4 pair, 23 AWG Solid Bare Copper wire insulated with PVC, U/UTP (Unscreened/Unshielded Twisted Pair), Category 6, Class E, 100 Ohm Impedance, Indoor Cable as per latest ammendments of ANSI/TIA/EIA-568 , The copper conductors should be balanced twisted in pairs, seperated by a cross-member fluted pair divider & protected by LSZH Jacket. Certified performance in a 4-connector configuration upto 100 Mtrs channel requirements & transmission frequencies ranging from 250 to 500 Mhz. in existing MS/PVC Conduits/casing capping including making connections to Information outlets and Patch Panels with jack & ferruling at both ends for identification with necessary tools for punching, stripping, crimping and testing etc as required complete in all respect. |
| 139 | Supply & fixing of square Faceplate for Flush / Surface Mount Information Outlets Single/Dual or Quad Aperture with dust cover, material should be High-impact, flame retardant, thermoplastic, UL listed material, Suitable for RJ45 unshielded/shielded connection modules. Should match with I. O. OEM. Dimensions should be 86mm X 86mm as required complete in all respect. All as per pre approved by Engineer in charge. |
| 140 | Single Aperture |
| 141 | Supply , Installation and Testing of 4 pair, 100 Ohm impedance, Cat 6/6A /Class E/Ea patch cords should be constructed of minimum 23/24 AWG, stranded bare Copper cable with LSZH Jacket, with an enhanced performance by factory moulded RJ45 connectors with strain relief boots as per ANSI/TIA/EIA 568-C.2 suitable for Cat 6/6A application complying to latest ammendments Category 6/6A Standards, According. to TIA568C.2, ISO/IEC 11801, EN 50173, IEC 60603-7-51, EN 60603-7, IEEE 802.3an minimum requirement for 1G BASE-T to 10G BASE-T performance. Patch cords shall be straight thru cable compatible with both T568-A and T568-B wiring schemes, should support IEEE 802.3af / IEEE 802.3at for POE applications, Minimum 750 to 1000 mating cycles in plug contacts for long durability, Should support Ethernet 10GBASE-T, 1.2 Gb/s ATM, Token ring 4/16, Digital video and broadband/baseband analog video, Voice over internet protocal (VOIP). |
| 142 | Cat 6, U/UTP (Unscreened/Un-sheilded Twisted Pair) Patch Cord |
| 143 | 1 Mtr Please Enable Macros to View BoQ information |