| 1 | Pump set and connected Works |
| 2 | OD341230/2025-2026:Supplying, installing, testing and commissioning of vertical inline centrifugal pump-set( Aquatex/Lubi/CRI or eq make ), VFD drive (Danfoss), Pressure tank(100L) and control panel . Each pump shall have TEFC 15HP, three phase electric motor. The pump set shall have cast iron head, base plate SS Shaft / Impeller / Intermediate chamber, suction and delivery manifold. float switch, pressure switch, ball valve, NRV, pressure relief valve, pressure gauge etc. Pump shall be provided with mechanical seal. The pump shall be suitable for auto/ manual operation.. The installation shall be complete with all necessary ancillaries & accessories including base plate complete as required. Scope includes three year warranty. Flow rate : 8 LPS each (1 Working + 1 Standby), Head : 90 Mts, |
| 3 | OD341647/2025-2026:Providing and fixing motorized valve including control wiring upto panel & ON/OFF arrangement and all other accessories required to make the system complete including control unit to be made of good quality PVC box, as per IP 65 with cable gland also as per IP 65 and suitable for outdoor installation complete with suitable wiring. This unit should be suitable to operate solenoid valve, float switch and consisting of contactors, control transformer, MCB, Potential free contacts for BMS, indicating lamp for automatic operation of filling OH tank with level to be maintined between 70% (low) to 100% (full) or as directed by supervising engineer 65mm nominal bore |
| 4 | OD301924/2025-2026:SITC of underground water tank level monitoring system with status display , visual and audible warning system with 5 year warranty on system |
| 5 | OD341761/2025-2026:Supply and fixing junction box with premoulded cable entry of Syntex type suitable for housing valve controller and providing cable termination (SIL EX 322 or equivalent) |
| 6 | OD195397/2024-2025:Supplying and installation including all manner of supports/ suspenders, anchor bolts etc for cable trays made out of suitable size channel sections, slotted angles, flats, MS plates etc as required including painting with 2 coats of synthetic enamel paint over a coat of zinc chromate primer, making good the damages, colour washing etc as required. |
| 7 | OD297072/2025-2026:Providing, laying, testing & commissioning of 'C' class heavy duty GI pipe conforming to IS 3589/IS 1239 including Welding, fittings like elbows, tees, flanges, tapers, nuts bolts, gaskets etc. and fixing the pipe for supply and delivery manifold in existing pump painting with two or more coats of synthetic enamel paint with two coats primer of required shade complete as required 100mm dia |
| 8 | 1.21.1:Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/ recess including cutting the wall and making good the same in case of recessed conduit as required.20 mm |
| 9 | 1.17.3:Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.3 X 1.5 sq.mm |
| 10 | 1.24.1:Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.5/6 amps switch |
| 11 | 1.24.4:Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.3 pin 5/6 amp socket outlet |
| 12 | 1.27.2:Supplying and fixing following size/ modules, GI box alongwith modular base & cover plate for modular switches in recess etc as required.3 Module (100mmX75mm) |
| 13 | OD298361/2025-2026:Supplying and fixing Multi function meter to read: V, A, F, 3 phase accuracy class 1 |
| 14 | OD298366/2025-2026:supply and fixing Red, Green, blue, Yellow, Orange colors LED indicator, AC/DC, as required |
| 15 | OD298384/2025-2026:Supply and fixing if resin cast type metering CT 250/5A, 5 VA , class 1 accuracy in existing panel |
| 16 | 2.1.2:Providing and fixing following capacity TP&N disconnector fuse switch unit inside the existing panel board with ISI marked HRC fuses including drilling holes in cubicle panel, making connections, etc. as required.63 Amp TP & N |
| 17 | OD298403/2025-2026:Supplying and fixing 2A, HRC Fuse with HRC Fuse link with connections, in existing panel board |
| 18 | 90.14.6:Supply and providing copper bus bars including finger type SMC bus bar supports in the bus chamber, suitable size nut & bolt, providng heat shrink sleeves etc. as required. |
| 19 | 90.12.7.42:Supply, laying and clamping of 1 no. PVC insulated and PVC sheathed armoured aluminium power cable, 1.1 KV grade of the following sizes using clamps noted along with the cables, spacing of clamps not exceeding 60cms, making good the damages , colour washing etc. as required.4 core 25 sq mm with factory made clamp |
| 20 | 14.10:Providing and laying in position reinforced cement concrete 1 :2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size) in foundation of pump, DG set etc. including form work etc. as required (excluding reinforcement). |
| 21 | 14.8:Providing and laying in position cement concrete 1 :3:6 (1 cement : 3 coarse sand : 6 graded stone aggregate 20 mm nominal size) in foundation of pump, DG set etc. including form work etc. as required. |
| 22 | OD300831/2025-2026:Steel reinforcement for RCC Work including straightening, cutting, bending, placing in position and binding all complete. |
| 23 | 9.1.34:Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.4 X 25 sq. mm (28mm) |
| 24 | 90.16.1.4:Supply and drawing bare earthing conductors of the following sizes along with wiring/ cables and giving connection as required4.00 mm copper conductor ( 8 SWG) |
| 25 | 90.16.5.4:Supply of superior quality copper earth socket for the following size of earth conductor including crimping etc. as required.4.00 mm (8 SWG) |
| 26 | OD344747/2025-2026:Carrying out control wiring for panel with normal meters and indication lamps alone with 650/1100 V grade PVC insulated stranded single core copper conductor cables conforming to IS 694 part I 1990 for interconnecting the control devices/ equipments including providing suitable size insulated sockets at the termination points or soldered properly, providing numbering ferrules for the proper identification of the wiring, keeping the wiring firm by suitable tie/ tie mounts/ PVC duct etc as required. 1.50 sq mm single run with required sockets Please Enable Macros to View BoQ information |