| 1 | Supply & fixing of 12.5 Mtr. high mast shaft of appproved make with rising system hot dip galvanized, inside and outside, dip heaving pole sheet thickness 3 mm. Top dia minimum 150 mm, bottom dia 310 mm base plate 25 mm thick suitable for wind velocity as per IS 875 part 3. There and having no circumferntial weld, with accessories for high mast such as head frame suitable for 6 luminaries and its control gear boxes 0.75 H.P. power toll motor, 3 point suspension system with steel wire rope 6 mm dia double drem winch, including makingsuitable foundation as per manufacture drawing/site reuiment along with foundation bolts, nuts, washers, anchor plates etc. complete in all respect. Ele SOR 2024 SI No. 21.3 |
| 2 | Supply and fixing of factory wired integral LED flood light luminaires with die cast aluminium housing built with dirver set suitable for 170 to 200 Watt. Confirming to IP 66 protection complete in all respect. ElE SOR 2018 SI No. 1455 CAT - AAA |
| 3 | Supply and burring of Safe Earthing Electrode T-39, (Hot Dip Galvanized), Length up to 3000 mm, Outer pipe 76 mm, inner Dia 38mm, terminal Dia 12 mm, outer G.I. pipe of 16 swg and inner G.I. pipe of 12 swg with Hot Dip Galvanization up to 100 micron filled with crystalline conductive mixture (CCM) having anti corrosive & conductive property with 50 kgs activated soil (BFC) capable of reducing the soil resistivity with good mixture of retaining capacity along with 30 cm squra GI Frame with Hinged cover and masonary housing (from electrod turminal to switch board, cost of 25 × 3 GI strip will be extra) Make : As approved in UPPWD & CPRI Certified. Ele. SOR 2018 725D |
| 4 | Supply & Laying of 25 mm x 3 mm G.I. Strip from earth electrode directly in the ground as required complete in all respect. ElE SOR 2018 SI No. 716 |
| 5 | Supply & Laying of Aluminium conductor PVC insulated armoured served sheathed cables 1100 Volts grade at a depth of 750 mm below ground level over a cushion of 75 mm thick sand all around and protected with burnt bricks on sides and on top. On surface the cable run shall be fixed on M.S. clamps etc. of suitable size or as directed by the Engineer-Incharge, complete in all respect. The armouring of the cable shall be properly connected with the earth conductor by clamps etc. ElE SOR 2024 SI No. 20a-1 |
| 6 | 16 sq.mm x 4 core. SI No. 20a. 1.9 |
| 7 | Supply and fixing following capacity of automatic street light cubicle control panel painted with anti corrosive alkali and acid proof paint consisting of time switch TSO 100 series with contactors, HRCfuses, isolating switch metering instrument & instrument box with CTs etc. in case of TPN, complete in all respect. 40 A TPN Ele SOR 2018 807 (f) II |
| 8 | Supply and fixing of single unit LED aviation obstruction light complete with transformer and LED spiral etc complete in all respect. ElE SOR 2018 SI No. 409CAT-AAACAT-A |
| 9 | S/F following rating double pole 240 V isolator in the existing MCB DB complete with connections,testing and commissioning etc. as required 40A (Sch No DSR 2025 Ele & Mach. 2.12.1) Rate 472×0.789 |
| 10 | Retro Reflective Signs (Type-XI Sheet). Providing and fixing retro-reflective signboards comprising of customized modular PU Epoxy Coated MS angle iron frame work, aluminum composite panel (ACP) as base board, micro prismatic retro-reflective sheet and electro cut coloured overlay film/ atex printing. The horizontal and vertical members including inclined outer members of the MS frame module shall be made of pair MS angle iron. No panel size shall be more than one Sqm and each panel shall be braced diagonally (one way only) with MS angle. The MS frame module shall have length not more than 3 mtr. The aluminum composite panel (ACP) shall have a thickness of 4mm with 0.5mm thick skin of aluminum on both sides. The ACP shall be fixed on the MS frame with pop riveting or with self taping SS screws 5mm dia spaced not more than 300mm centre to centre ensuring that no riveting is seen on either face of the frame. On the front visible face of the ACP, micro prismatic retro-reflective sheet conforming to Type-XI of ASTM: D 4956-09 shall be pressure fixed. The retro reflective sheeting shall be tested for 3 year outdoor weathering test in Indian conditions as per IRC 67:2012 & proof of the same in form of government report shall be uploaded while quoting tender. The rate shall include all materials, labour, equipments, fabrication, transportation, erection, installation and incidents all complete as per direction of the Engineer-in-Charge. Signage on MS angle frame of (35×35×5)mm LKO SOR 2020-21 Cha-26 Trafffic Signs, Marking Work (Size 0.90*1.00=0.90 sqm |
| 11 | S/F of 3 KVA Automatic Volage stabilizer Input working Range: 160V-285V AC=5V, 50 HZ Output Voltage Stabilized (MR) |
| 12 | 2 KW Connection Charge (MR) Please Enable Macros to View BoQ information |