| 1 | Servicing of following ac installed in DLVGC by using foam and jet spray for both indoor and outdoor unit complete etc as required as per satisfaction of Engineer In-charge. |
| 2 | a) Tower AC |
| 3 | b) Split/Window |
| 4 | Charging of Refrigerent/Gas in Tower/Window/Split ac and removing any leakage in piping complete as required. |
| 5 | Repairing and servicing of 4/6 feet air curtain installed in club house complete as required. |
| 6 | Dismanteling, shifting and reinstalling the existing 10 mtr GI Octagonal pole at preferred location as given by secretary on the existing foundation complete as required. ( The existing foundation should be disposed out of golf course.) |
| 7 | Providing and laying in position (1:2:4) reinforced cement concrete foundation of size 500 mm long x 500 mm wide and 1600 mm deep ( Lengh and width may change according to existing pole PCD) i/c excavation of earth, providing cutting, bending and placing in position reinforcement of cold twisted bar of 12 mm dia 1650mm long (approx.) -8 Nos. and reinforcement ring of cold twisted bar of 8 mm dia 1800 mm long (approx.)-10 Nos. (with 150 mm spacing) i/c supplying of 4 Nos. M-24 x 750 mm long (150 mm top threaded portion) GI foundation bolt (EN- 8 grade) with 3 Nos. nuts and 2 Nos. washer, bolt along with 2 Nos. templates/ Anchor plate of size 320 mm x 320 mm x 4 mm thick having 4 Nos. 26 mm dia holes to match with PCD of poles base plate with positioning of foundation bolts and providing 63 mm (OD) 2 Nos DWC pipe for cable entry and exit as required. (Drawing to be approved by Engineer in charge.) |
| 8 | Supplying and inastallation of Ring/round type bracket of 1000 mm dia made out of 48mm dia pipe suitable for to house 4 Nos of fitting with a canopy of 400mm on the existing 10 mtr GI octagonal pole complete as required. |
| 9 | Supplying and replacement of 200 Watt Flood Light, powder coated pressure die cast aluminium body with built in or separate driver as per the requirement with Driver efficiency >85%, Input voltage: Input voltage: 140-270 Volt AC,frequency 50/60 hz, Operating temp range -5 0C to50 0C, internal surge protection of 5 KV L,N,E as per IEC 61000-4-5, Driver efficiency >85%,THD < 10% as per IEC 61000-3-2, P. F.≥0.95, IP-66,IK-10, CRI >70, under voltage and over voltage protection, EMI-EMC as per CISPR -15, lenses for beam angle 30 deg-120deg as per the application and the project requirement., suitable tilt able fitting, life time (LED, Driver & electrical circuitry) of minimum 50000 Burning Hours with 70% of initial Lumen maintained till life ends as per LM80 extrapolation IES TM-21-11 report, CCT 3000°K / 4000°K / 5700°K /6500°K (As per ANSI Bin) SDCM(Standard Deviation Color Matching) <5, Maximum power consumption should not more than the specified rating and Fixture shall be of relevant BIS standard complete in all respect i/c external connections with 1.5 sq mm FRLS/HFFR, PVC insulated copper conductor single core cable and earthing etc. as required with Minimum 5 year OEM warranty. System lumen efficacy ≥105 <120 lm/Watt output .LM79 & LM80 Test report and all testing required for LED fixtures as per BIS shall be submitted.. Shape size and CCT shall be as approved by Engineer-in Charge as per requirement. (Thermal management: heat sink of aluminium housing such that LED junction temperature shall not rise above 90°C). |
| 10 | Supplying and drawing following sizes of FRLS/HFFR PVC insulated copper conductor, single core cable in the existing surface/ recessed steel/ PVC conduit as required. |
| 11 | 3 x 2.5 sq.mm |
| 12 | Supply of PVC insulated and PVC sheathed / XLPE armoured aluminium conductor power cable (As per IS 7098 (Part-1) of 1.1 KV grade i/c connection testing etc.as required. |
| 13 | 2 x 16 sq. mm |
| 14 | Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size in the existing RCC/ HUME/ METAL pipe as required |
| 15 | Up to 35 Sq mm |
| 16 | Supplying and laying of following size DWC HDPE pipe ISI marked along with all accessories like socket, bend, couplers etc. conforming to IS 14930, Part II complete with fitting and cutting, jointing etc.direct in ground (75 cm below ground level) including excavation and refilling the trench but excluding sand cushioning and protective covering etc., complete as required. |
| 17 | 63 mm dia (OD-63mm & ID-51 mm nominal) |
| 18 | Providing and fixing 6 SWG dia G.I. wire on surface or in recess for loop earthing along with existing surface/ recessed conduit/ submain wiring/ cable as required. |
| 19 | Supply and replacement of heavy duty exhaust fan of following size , single phase, fixing the same on wall with suitable nut bolt fixture and connection testing etc. as required. |
| 20 | 230 mm |
| 21 | 300 mm |
| 22 | Supplying of PVC Sheathed, PVC Insulated Industrial Round Multicore Flexible Copper Conductor cable of 4x16 sq. mm size including connection, testing etc. as reqd. |
| 23 | Supply and replacement of Penadant lights made out of aluminium with sanded black painted finish in club house complete as required. |
| 24 | Earthing with G.I. earth pipe 4.5 metre long, 40 mm dia including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe etc. with charcoal/ coke and salt as required. |
| 25 | Providing and fixing 25 mm X 5 mm G.I. strip on surface or in recess for connections etc. as required. |
| 26 | Supplying, installation, Testing & Commissioning of LED Recessed/ surface Down lighter (Round/ square/ Rectangular) COB Type of following body material and construction as per IS : 10322 with driver as per the requirement with Driver efficiency >85%, Operating voltage AC 140-270 Volt, frequency 50/60 hz, Operating temp range -5 0C to 40 0C, internal surge protection of 2.5 KV with Short & Open circuit protection ,THD < 10% , P. F.≥0.95, IP20, CRI >80, UGR (Unified Glare Rating) < 19, Flicker free (flicker should be below 5%), life time (LED, Driver & electrical circuitry), of minimum 50000 Burning Hours with 70% of initial Lumen maintained till life ends, CCT 3000°K / 4000°K / 5700°K / 6500°K (As per ANSI Bin), SDCM (Standard Deviation Color Matching) <3, Maximum power consumption should not more than the specified rating and Fixture shall be confirming to relevant BIS standards. Manufactures Word Mark/ Name Engraved/ Embossing/ Screen printing on housing Complete in all respect i/c external connections with 1.5 sq.mm FRLS/HFFR, PVC insulated copper conductor single core cable and earthing etc. as required with Minimum 5 year OEM warranty. System lumen efficacy ≥105 and <120 lm/Watt output . LM79 & LM80 Test report and all testing required for LED fixtures as per BIS shall be submitted. Shape size and CCT shall be as approved by Engineer-in-Charge as per requirement. (Thermal management: heat sink of aluminium housing such that LED junction temperature shall not rise above 90°C) Powder coated die cast Extruded aluminium Body including trim with Aluminium Reflector. |
| 27 | a)12 -15 watt |
| 28 | b)22 watt |
| 29 | Supplying, Installation, Testing and Commissioning of Air Cooled Floor standing Tower type split Air conditioners complete with Indoor unit(IDU), Out door unit (ODU), surface / concealed copper Refrigerant piping with insulation (closed cell elastomeric nitrile rubber tubular pipe section) upto 5 Mtr (IDU to ODU), copper power cable upto 5.5 Mtr (IDU to ODU), i/c drain pipe of suitable length and size.R-32/R-410/R-407C Green Refrigerant, wireless Remote control, suitable for working between 180-260V with low & high voltage cutoff and 50 hz ,1 phase AC supply capable of performing cooling, dehumidification, air circulation of following capacity with Scroll / rotary with min 5 year Original Equipment Manufacturer (OEM) warranty both compressor and Printed Circuit Board (PCB). as specified. The system shall be able to deliver 100% of the rated capacity as per relevant IS Code. The lab testing reports as per IS: 1391 shall be submitted from National Accreditation Board for Testing and Calibration Laboratories (NABL) accredited as per International Electrotechnical Commission (IEC) 17025 standards / Central Power Research Institute (CPRI)/ Electrical Research and Development Association (ERDA)with Original Equipment Manufacturer (OEM) etc. complete as per CPWD specification and as per IS: 1391 as required. |
| 30 | 4.6 TR BEE 4 Star Rating Please Enable Macros to View BoQ information |