| 1 | Excavation in trenches not exc 1.5 m wide and not exc 1.5 m in depth and getting it out for laying of cable / pole etc in hard/dense soil complete all as specified. |
| 2 | Excavation in trenches exceeding 1.5 mtr wide and not exceeding 1.5 mtrs in depth for laying of cables including getting out in hard soil complete all as specified and directed. ( for pole ) |
| 3 | Returning, filling in, including spreading, leveling watering, and well ramming in layers not exc 25 cm in hard/dense soil all as directed. |
| 4 | Removing excavated material (soils) n.exc 50m and depositing where directed at a level exc. 1.5 cm above the starting point all as directed. |
| 5 | Supply and fix in repair GI Pipe Light grade with all connected accessories of sizes 100 mm dia completed as directed for cable protection. |
| 6 | M&L for taking up tilted/leaned steel tubular pole 09/11 Mtr pole by breaking the coping , PCC foundation , securing the pole with rope for safety, shifting the pole from public highway/valley side and stacking in safe location for refixing the same in original/ new suitable location all as specified and directed.Note: Rate for fouondation PCC and coping will be measured and paid seperately as relevent item of schedule. |
| 7 | Supply and erection in truely vertical position steel tubular swaged pole complete with cast iron base plate finial taper plug, bolts, nuts and screws as specified type 410 SP-55 (09.0 mtr long), complete all as specified and directed by Engr-in-Charge. ( For intermediate poles and for converting single pole to two pole structure ) |
| 8 | M&L for refixing the Electric pole 11 Mtr long retrieved from item No 06 here in above , bringing the HT pole from stacked area, placing in trenches, alignment of pole for truly vertical position , securing the pole with rope for safety provding PCC incl proper ramming complete with PCC coping all as specified and directed at site .Note: The work will be executed at mountain areas.PCC and earth work will be measured and paid seperately as per relevent item of this schedule. |
| 9 | M&L for dismadling of tilted two pole structure including removal of all channels , nut bolt and washers, removing insulators and taking down HT 09/11 mtr poles( 02 nos) from ground incl taking out from original location and stacking all materials in safe custudy for refixing complete all as specified and directed.Note: The work will be executed at mountain areas. |
| 10 | M&L for dismadling of tilted 4 pole structure including removal of all channels, nut bolt and washers, removing insulators and taking down HT 09/11 mtr poles( 04 nos) from ground incl taking out from original location and stacking all materials in safe custudy for refixing complete all as specified and directed.Note: The work wl be executed at mountain areas. |
| 11 | Labour only for rejointing brocken ACSR conductor between HT single poles , connecting to insulator restretching the coductor on pole incl jumper wire complete all as specified and directed.Note: The work willl be executed at mountain areas. |
| 12 | Labour only for rejointing brocken ACSR conductor between HT two pole/4 pole structure single poles , connecting to insulator restretching the coductor on pole incl jumper wire complete all as specified and directed.Note: Min span will be 300 Mtr between mountains .The work will be executed at mountain areas. |
| 13 | M&L for Cross arms, bracings, supports, clamps and back plates abricated from structural steel sectionsincluding nuts, bolts, washers, welding, bending cold or hot, drilling holes for bolts, in any shape or size as indicated or directed and inclusive of one primer coat, one under coat and one finishing coat of paint complete |
| 14 | Labour only for taking out XLPE cable any size/type complete all as specified and directed. Note : Excavation and earth work will be measured and paid seperately. |
| 15 | S&F XLPE insulated, screened, PVC bedded,galvanised steel strip or wire armoured,electric power cables (heavy duty) with aluminium conductor, 11000 volts earthed, grade cross sectional area 95 sq. mm, 3 core all as specified and direected. |
| 16 | M&L for cable jointing kit for 11 KV (Earthed) grade cable for outdoor termination heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 50 sqmm to 95 sqmm. |
| 17 | S&F stay assembly complete with accessories as shown in electrical plate No 1 and diameter of stay rod 16 mm (loop type insulator, stay clamps, excavation and concrete measured separately). |
| 18 | Taking down defective unserviceable GOD from pole and supply and fix gang operated air break switches incl 12 insulators mounted on MS Channel with operating mechanism worked from ground level suitable 11000 volts, 200 Amps including GI pipe handle clamps bolts, nuts, jumper wire connecting with stranded conductors complete with locking arrangements. |
| 19 | S&F in repair lighteing arrestor non linear resister type (Surge) suitable for 11000 volt grade conforming to IS-3070 Part-I with discharge capacity 65 Kilo Amps including stranded coloured sleeved jumper connection with PG clamps mounted on steel mounting fabrication of MS clamps, bolts, nuts, washers etc all as specified and directed. |
| 20 | S&F in repair Aluminium conductor, steel reinforced, of size 6/211 to 6/3010mm (Squirrel to Ferret) straining properly on polymer insulators with and including aluminium tape/winding wire, clamps & jumpers etc. complete all as specified.Note : 3% for sag shall be added in measurement . |
| 21 | S&F in repair pin type porcelain vitreous white, brown insulator 150 mm height and 150 mm dia for working pressure 11000 volts complete all as specified. |
| 22 | M&L for disc type insulator, porcelain, vitreous 145 mm high and 255 mm dia ball and socket type, white, brown or green two in series assembly for tension clamps for conductors for working pressure 11000 volts grade,including taking out existing unserviceable insulator of any type/description etc complete all as specified and directed. |
| 23 | Cement concrete 1:2:4 type B-1 using 20 mm graded crushed stone aggregate in coping padestal to poles including provision of necessary form work finishing the exposed surface even and smooth complete all as specified. ( for pole) |
| 24 | Cement concrete 1:3:6 type C-2 using 40 mm graded crushed stone aggregate in foundation filling & mass concrete for poles/struts/stays assembly including provision of necessary form work finishing the exposed surface even and smooth in cement mortar 1:3 complete all as specified. ( for pole) |
| 25 | Cement concrete 1:4:8 type D-2 using 40 mm graded crushed stone aggregate in foundation filling & mass concrete for poles/struts/stays assembly including provision of necessary form work finishing the exposed surface even and smooth in cement mortar 1:3 and applying two coats of white wash to the portion of PCC muffs above ground level complete all as specified. ( for pole and stay) |
| 26 | M&L for removing LT/HT over head conductor from the insulator where ever required and restretching the same without any kink/bend upto permissible sag, binding it on insulator by means of binding wire and testing the LT/HT overhead line after completion as directed.(Note: Three/four runs of HT/LT overhead conductor for three phases and neutral shall be measured as one Span and required ACSR conductor shall be measured and paid seperately as per relevent items in schedule) |
| 27 | M&L for repairing coping of pole with Cement concrete 1:2:4 type B-1 using 20 mm graded crushed stone aggregate in coping padestal to poles including provision of necessary form work finishing the exposed surface even and smooth complete all as specified. |
| 28 | M&L for painting of steel tubular pole upto 09/11 mtr length incl MS clamp , bracket, cross arms with two coat of alumnium paint after preparation of old painted surface and applying metallic primer , providing 03 nos alternative strip of 30 cm wide with black and yellow super quality enamel paint above embedded level and writing pole nos with 02 inch wide letter complete all as specified and directed. Note : Necessary electric shutt down will be taken from the Dpt before commencing the work . |
| 29 | M&L for taking up tilted/leaned steel tubular pole 09/11 Mtr pole by breaking the coping , PCC foundation , securing the pole with rope for safety, shifting the pole from unit area and stacking in safe location including refixing the same location all as specified and directed. Note : Rate for foundation PCC and coping include excavation and earth work deemed to be included in the quated rate. |
| 30 | Supply and errection of Truly vertical position steel tubular swaged pole complete with cast iron base plate finial taper plug, bolts, nuts and screws as specified type 410SP-31(9 mtr long) , complete all as specified and directed by Engineer in Charge ( For intermediate LT poles and for converting single pole to two pole structure) |
| 31 | Supply and fix in replacing LT Pin type, porcelain, vitreous, white, brown or green insulator including one galvanised mild steel spindle, two gavanised iron washers and one galvanised iron nut, 50mm height, 65mm dia for 550 volts complete all as specified and directed. |
| 32 | Supply and fix in replacing Shackle Type, Porcelain, vitreous, white, brown or green insulator working voltage 1100 volt, height 75 mm and dia 90mm including galvanised mild steel straps, washers, insulator bolts, washers and nuts. |
| 33 | M&L in replacing LT line seperator made of PVC 4 line complete with screws, bolts , nuts all as specified and direted. |
| 34 | S&F in repair danger notice plate of 1.6 mm thick mild steel sheet,vitreous enamelled white with letters,figures and conventional skul and bones in signal red colour and fixed with MS clamps,bolts and nuts of approved size,for HT, 25x20 cm in size. |
| 35 | M & L for replacement of earthing continuity conductor or main earthing lead fixed to wall on batten or recess or chases or buried in ground or drawn in conduit/piope or fixed to poles or any other indicated situation for loop earting etc as required 32x6 mm galvanised iron strip . |
| 36 | Earthing complete with galvanised steel earth plate electrode 60×60cmx6mm thick, buried directly in ground (earth pit not less than 2.25 metres deep below ground level) with top edge of the plate not less'than 1.5 metres below normal ground level, connected to galvanised earth lead wire 4.0mm dia by means of bolts, nuts, check nuts and washers of galvanised iron or steel all as shown in electrical plate No. 3 connected to earthing test point all as specified or indicatedincluding testing on completion (for poles). |
| 37 | Earthing complete with galvanised iron earth plate electrode 600 mm x 600 mm x 6mm as earthing lead buried directly in ground vertically to a depth not less than 2.25 Mtr deep below ground level with top edge of the plate not less than 1.5 Mtr below normal ground level connected to and including galvanised iron strip 32X6 mm as earthing lead by means of bolts, nuts, check nuts & washers etc made of GI and connected to earthing test point all as shown in electrical plate No. 3 of SSR Part I of 2009.00 & as specified or indicated and testing on completion including exaction/earth work in any type of strata PCC ( 1:3:6 ) type C1 earthing chamber, pre cast slab 50 mm thick in cement concrete ( 1: 2 : 4 ) type B-1 (reinforced with welded steel wire fabric (XPM) weight not less than 4 Kg / Sqm), funnel with wire mesh, I watering pipe of 20 mm bore medium grade and lugs, including galvanised iron strip 32X6 mm with GI protection pipe of 40 mm medium grade 7.5 meter long, etc complete all as specified. |
| 38 | Note:-The accepted amount will be arrived after deducting the Sch of credit i.e. Rs 40,992.00 and any other reduction if any from quoted amount. Please Enable Macros to View BoQ information |