| 1 | WTP: Design and construction of 1.50 MLD capacity automated PLC controlled water treatment plant including providing and laying the DI / CI pipes, specials, sluice valves from inlet chamber of WTP to inter connecting piping network in WTP (The cost of these DI / CI pipes, valves and specials shall also be included in the rates quoted by the contractor) along with inlet chamber, Alum dozing, Flash mixing, Clariflocculator, filter box, over head Reservoir for back wash and waste water tank with suitable size pumping sets and panel boards, air scour equipment, chemical house with chlorination equipments, all other civil, mechanical, electric installations complete in all respects as per specifications (make of Sluice valves / NRV: IVC / VAG / Kirlosker) 1.50 MLD Capacity |
| 2 | WTP: Design and construction of 2.00 MLD capacity automated PLC controlled water treatment plant including providing and laying the DI / CI pipes, specials, sluice valves from inlet chamber of WTP to inter connecting piping network in WTP (The cost of these DI / CI pipes, valves and specials shall also be included in the rates quoted by the contractor) along with inlet chamber, Alum dozing, Flash mixing, Clariflocculator, filter box, over head Reservoir for back wash and waste water tank with suitable size pumping sets and panel boards, air scour equipment, chemical house with chlorination equipments, all other civil, mechanical, electric installations complete in all respects as per specifications (make of Sluice valves / NRV: IVC / VAG / Kirlosker) 2.00 MLD Capacity |
| 3 | 1. STP (SEWAGE TREATMENT PLANT): 2.00 MLD: Design, construction, erection, testing and commissioning of 2.00 MLD capacity Sewage Treatment Plant based on Sequential Batch Reactor (SBR) including Electrical, Mechanical, Piping and Instrumentation work with PLC and SCADA arrangement for STP integrated with MPS including furniture and laboratory equipments as per detail and specifications mentioned in attached additional documents along with following provisions: 1.1 1 High Mast of 9 mtr GI Octagonal pole of 4 mm thickness (T=100 mm, B=200mm, Base Plate = 320 x 320 x 20 mm), Window at 500 mm from Base Plate with 4 No. LED suitable size, outdoor type energy efficient lamps on each pole , 2 LED outdoor light with 6 m. high GI pole along road / path including all accessories complete in all respect. 1.2 Supply and fixing of 1 No. 3.65 m wide SS 304 main Gate along with1.25 m. wide wicket gate at STP to the entire satisfaction of Engineer-in-charge. (Total weight not less than 500 kg). 1.3 CC TV CAMERAS: Providing and Installing 6 CCTV Cameras (4 Cameras for STP and 2 Camera at MPS-1) within 96 hours of signing the agreement along with 120 days recording (DVR), 48 inch LED Screen, 16 Channel DVR at STP and MPS Site with connectors, cables, poles and power supply with online real-time output facility. The cameras at MPS and STP shall be synchronized at STP site complete in all respect. PTZ speed dome 360 degree 50X zoom camera, CP Plus Internet Protocol minimum 5 MP WDR, Night vision color mode, IR range up to 150 m. CCTV Cameras should be installed and commissioned before starting of the work.Make: Sony / Canon / Panasonic / Samsung 1.4 EWQMS (Effluent water quality monitoring system): Supply, Installation, Testing, Commissioning, Operation and Comprehensive Annual Maintenance of effluent quality monitoring system at 2.00 MLD capacity STP for online (continuous) measurement of PH, Total Suspended Solids (TSS), Chemical Oxygen Demand (COD), Biological Oxygen Demand (BOD) by single analyzer with various sensors (spectral measurement in the UV-VIS range 200-720 mm) performing reagent and chemical free analysis with automatic cleaning of censor, signal cables and power cables, local data acquisition and display of data on continuous basis for up linking the data to CPCB, HSPCB and PHED, TUV approved complete in all respect as per Central Pollution Control Board (CPCB) guidelines for online continuous monitoring system for effluents. 1.4.1 Multi-parameter measuring converter, for connecting up to 18 intelligent sensors Scope including 8 analog inputs / outputs (4 inputs and 4 outputs) (0/4-20Ma), wide- range power supply Optical COD/BOD and TSS probe with spectral processing of the UV-VIS range, for measurement in the outlet / effluent of 2.00 MLD capacity STP with integrated with automatic cleaning complete in all respect. 1.4.2 Robust digital pH/ORP sensor for pH/ORP electrodes, with built-in pre-amplifier and temperature sensor with Automatic Temperature Compensation (ATC) Cable length 100 Meter (minimum) complete in all respect. 1.4.3 Sensor adapter cable for all intelligent sensors, with IP68 water proof connection to the intelligent Sensor Net system. Cable length 100 meter (minimum) complete in all respect. 1.4.4 Data transfer to CPCB, HSPCB and PHED servers complete in all respect. 1.4.5 Providing GSM 3G, 4G modem with mobile network connectivity including network including complete in all respect. 1.5 Conveyance of treated effluent from cholorine contact tank to effluent collection tank through suitable size DI K9 pipe along with cost of pipe, sluice valves, specials, material and labour complete in all respect. |
| 4 | 1 MPS (MAIN PUMPING STATION): Design, construction and commissioning of MPS for 2.00 MLD average flow with peak factor 3 including RCC Inlet chamber, screening chamber, wet well sump complete in all respect as per detail and specifications mentioned in attached additional documents along with following provisions: 1.1 Providing, fixing and commissioning of 5 non clog sewage submersible pumping sets as per IS marked ie. 1 of 3800, 2 of 1300 and 2 of 700 LPM having minimum head of 35 m along with making all arrangement including sluice valves, Non return valves, specials, flanged individual and common delivery pipes, suitable size LT panel boards and suitable size cable from LT panel to pumps, all safety devices, automatic capacitor bank, complete in all respect as per specification mentioned in attached additional documents. 1.2 Conveyance of raw sewage from MPS to inlet chamber of STP through rising main line. ng with cost of DI pipe, sluice valves, specials, material and labour complete in all respect. 1.3 Suitable size (as per design) K9 DI pipe at MPS for interconnecting the structures including welding and screwing of flanges, ISI marked D.I. fittings, sluice valves, non returning valves as per requirements even for bye-pass arrangements complete in all respect 1.4 Suitable size (as per design and requirement) Gear Operated Sluice Gate with SS Spindle (SS 410) and seats (SS 304) for screens and partition of tank as per design. 1.5 Supply and installation of 1 mechanical and 1 manual coarse screen (SS 304) suitable for 2.00 MLD average flow with peak factor of 3.0 complete in all respect. 1.6 All the pumping machinery, panel board, Level sensor etc shall be controlled by PLC and SCADA and shall be synchronized with PLC panels at MPS and STP site through broadband internet facility. 1.7 2 No. High Mast of 9 mtr GI Octagonal pole of 4 mm thickness (T=100 mm, B=200mm, Base Plate = 320 x 320 x 20 mm), Window at 500 mm from Base Plate with 6 No. LED suitable size, outdoor type energy efficient lamps on each pole, 20 no. LED outdoor light with 7 m. high GI pole along road / path including all accessories complete in all respect. 1.8 Raw sewage will be available near boundary wall within the premises of proposed MPS but the conveyance of sewage from this terminal point to the inlet chamber of MPS through DI K9 pipe of suitable diameter as per design is included in the Turnkey contract. The Level of the MPS / STP will be as per bed level of existing incoming sewer at MPS. |
| 5 | COPPER CABLE: Supply, erection, testing and commissioning of IS marked 3 core Copper Cables, Solid Copper conductor up to 6sqmm and balance Stranded Copper, XLPE Insulated, cores laid up, PVC Inner sheathed, Armoured (Glavanised wire for cables up to 10x1.5sqmm, 8x2.5sqmm, 2x10sqmm, 3x10sqmm, 4x6sqmm and balance all galvanized steel strip), extruded PVC type ST2 Outer Sheathed, /1100 V grade as per IS 7098 (Part 1) 1988 with up to date amendments along with all accessories like thimble lugs etc for motors as per entire satisfaction of Engineer-in-charge complete in all respect. Make: Indian Cables Ltd./ Finolex / Havells / Polycab / RR Cables / CAPP / Gloster / Universal / Fort Gloster Industries Ltd./ Asian Cables Corporation Ltd10 Sqmm size |
| 6 | Providing, fixing, lointing, testing of Mechanical joints complete with rubber gaskit, Galvanized nuts and bolts including labor, tranportaion ets up to the site. 150 mm nominal diameter |
| 7 | Providing, fixing, lointing, testing of Mechanical joints complete with rubber gaskit, Galvanized nuts and bolts including labor, tranportaion ets up to the site. 200 mm nominal diameter |
| 8 | Providing, fixing, lointing, testing of Mechanical joints complete with rubber gaskit, Galvanized nuts and bolts including labor, tranportaion ets up to the site. 250 mm nominal diameter |
| 9 | Providing, fixing, lointing, testing of Mechanical joints complete with rubber gaskit, Galvanized nuts and bolts including labor, tranportaion ets up to the site. 300 mm nominal diameter |
| 10 | Providing, fixing, lointing, testing of Mechanical joints complete with rubber gaskit, Galvanized nuts and bolts including labor, tranportaion ets up to the site. 350 mm nominal diameter |
| 11 | RAW WATER PUMP: Supplying, erection, testing and commissioning of Horizontal motor pumping set for Raw water having head as per the indicated requirements of discharge in LPM and power capacity in BHP as per IS marked9200 LPM x 15.00 m Head |
| 12 | PANEL BOARDS FOR MOTORS: Supply, erection, testing and commissioning of wall mounted electrical LT Panel board, fabricated from 16 SWG CRCA sheet duly stouten with suitable angle iron frame work and completely powder coated of suitable size deep having following items for 1 Pumping set a) Main switch suitable ampere 1 No. (LandT Siemens, ABB) b) CT 100/3 = 1 Nos. (AE/ KAPPA/ LandT) c) Digital Multi function meter = 1 No. d) SPP = 1 No. of approved make e) Motor starter, star delta 1 No (LandT Siemens, ABB) f) VSS 1 No. and ASS 1 Nos. of approved make. g) Capacitor KVAR as per site requirement = 1 No. h) Indicating Lamp = One Set i) Change over switch of suitable Amp = 1 No. (Each) 9200 LPMX 15.00 Mtr. Head . |
| 13 | Providing and laying Double Flanged (Screwed/ Welded) Centrifugally (Spun) cast Iron, class B (IS 1536) complete with rubber gaskit, Galvanized nuts and bolts including labor, tranportaion etc up to the site of work.350 mm nominal diameter |
| 14 | RAW WATER PUMP: Supplying, erection, testing and commissioning of Horizontal motor pumping set for Raw water having head as per the indicated requirements of discharge in LPM and power capacity in BHP as per IS marked1500 LPM x 15.00 M Head |
| 15 | PANEL BOARDS FOR MOTORS: Supply, erection, testing and commissioning of wall mounted electrical LT Panel board, fabricated from 16 SWG CRCA sheet duly stouten with suitable angle iron frame work and completely powder coated of suitable size deep having following items for 1 Pumping set a) Main switch suitable ampere 1 No. (LandT Siemens, ABB) b) CT 100/3 = 1 Nos. (AE/ KAPPA/ LandT) c) Digital Multi function meter = 1 No. d) SPP = 1 No. of approved make e) Motor starter, star delta 1 No (LandT Siemens, ABB) f) VSS 1 No. and ASS 1 Nos. of approved make. g) Capacitor KVAR as per site requirement = 1 No. h) Indicating Lamp = One Set i) Change over switch of suitable Amp = 1 No. (Each) 3700 LPM X 35.00 Mtr. Head . |
| 16 | Supply erection testing of reputed make LED light 100 wats with fittings and accessories complete in all repects. (LED= 5 no.) |
| 17 | COPPER CABLE: Supply, erection, testing and commissioning of IS marked 3 core Copper Cables, Solid Copper conductor up to 6sqmm and balance Stranded Copper, XLPE Insulated, cores laid up, PVC Inner sheathed, Armoured (Glavanised wire for cables up to 10x1.5sqmm, 8x2.5sqmm, 2x10sqmm, 3x10sqmm, 4x6sqmm and balance all galvanized steel strip), extruded PVC type ST2 Outer Sheathed, /1100 V grade as per IS 7098 (Part 1) 1988 with up to date amendments along with all accessories like thimble lugs etc for motors as per entire satisfaction of Engineer-in-charge complete in all respect. Make: Indian Cables Ltd./ Finolex / Havells / Polycab / RR Cables.10 Sqmm size |
| 18 | COPPER CABLE: Supply, erection, testing and commissioning of IS marked 3 core Copper Cables, Solid Copper conductor up to 6sqmm and balance Stranded Copper, XLPE Insulated, cores laid up, PVC Inner sheathed, Armoured (Glavanised wire for cables up to 10x1.5sqmm, 8x2.5sqmm, 2x10sqmm, 3x10sqmm, 4x6sqmm and balance all galvanized steel strip), extruded PVC type ST2 Outer Sheathed, /1100 V grade as per IS 7098 (Part 1) 1988 with up to date amendments along with all accessories like thimble lugs etc for motors as per entire satisfaction of Engineer-in-charge complete in all respect. Make: Indian Cables Ltd./ Finolex / Havells / Polycab / RR Cables.16 Sqmm size |
| 19 | COPPER CABLE: Supply, erection, testing and commissioning of IS marked 3 core Copper Cables, Solid Copper conductor up to 6sqmm and balance Stranded Copper, XLPE Insulated, cores laid up, PVC Inner sheathed, Armoured (Glavanised wire for cables up to 10x1.5sqmm, 8x2.5sqmm, 2x10sqmm, 3x10sqmm, 4x6sqmm and balance all galvanized steel strip), extruded PVC type ST2 Outer Sheathed, /1100 V grade as per IS 7098 (Part 1) 1988 with up to date amendments along with all accessories like thimble lugs etc for motors as per entire satisfaction of Engineer-in-charge complete in all respect. Make: Indian Cables Ltd./ Finolex / Havells / Polycab / RR Cables.25 Sqmm size |
| 20 | COPPER CABLE: Supply, erection, testing and commissioning of IS marked 3 core Copper Cables, Solid Copper conductor up to 6sqmm and balance Stranded Copper, XLPE Insulated, cores laid up, PVC Inner sheathed, Armoured (Glavanised wire for cables up to 10x1.5sqmm, 8x2.5sqmm, 2x10sqmm, 3x10sqmm, 4x6sqmm and balance all galvanized steel strip), extruded PVC type ST2 Outer Sheathed, /1100 V grade as per IS 7098 (Part 1) 1988 with up to date amendments along with all accessories like thimble lugs etc for motors as per entire satisfaction of Engineer-in-charge complete in all respect. Make: Indian Cables Ltd./ Finolex / Havells / Polycab / RR Cables.35 Sqmm size |
| 21 | COPPER CABLE: Supply, erection, testing and commissioning of IS marked 3 core Copper Cables, Solid Copper conductor up to 6sqmm and balance Stranded Copper, XLPE Insulated, cores laid up, PVC Inner sheathed, Armoured (Glavanised wire for cables up to 10x1.5sqmm, 8x2.5sqmm, 2x10sqmm, 3x10sqmm, 4x6sqmm and balance all galvanized steel strip), extruded PVC type ST2 Outer Sheathed, /1100 V grade as per IS 7098 (Part 1) 1988 with up to date amendments along with all accessories like thimble lugs etc for motors as per entire satisfaction of Engineer-in-charge complete in all respect. Make: Indian Cables Ltd./ Finolex / Havells / Polycab / RR Cables.50 Sqmm size |
| 22 | COPPER CABLE: Supply, erection, testing and commissioning of IS marked 3 core Copper Cables, Solid Copper conductor up to 6sqmm and balance Stranded Copper, XLPE Insulated, cores laid up, PVC Inner sheathed, Armoured (Glavanised wire for cables up to 10x1.5sqmm, 8x2.5sqmm, 2x10sqmm, 3x10sqmm, 4x6sqmm and balance all galvanized steel strip), extruded PVC type ST2 Outer Sheathed, /1100 V grade as per IS 7098 (Part 1) 1988 with up to date amendments along with all accessories like thimble lugs etc for motors as per entire satisfaction of Engineer-in-charge complete in all respect. Make: Indian Cables Ltd./ Finolex / Havells / Polycab / RR Cables.70 Sqmm size |
| 23 | `HT Metering Panel: Supply Indoor Type 11KV VCB Control Cubical Panel with vertical Isolation Type Breaker as per Relevant IS as amended up to Date and Additional Specifications, having Capacities as Mentioned Below, Single break trip free mechanism, manually charged and Auto/Manually closing breaker suitable for use on 11kv, 3 phase 50hz AC, Supply with short circuit fault level of 500 Amps Capacity, breaker featured with local ON/OFF indicator with hand trip device, spring release coil, shunt trip coil and auxiliary switch of 2NO plus 2NC and equipped with following switchgears and accessories including making suitable structure arrangement for installation, control wiring and connections etc. as reqd. (1 IC plus 2 OG)a). VCB, 11KV, 630Amp, 50KA.b). 1ph 11KV/110 Volts PT (indoor type) Class 0.2 Accuracy and 100 VA burden -3 no’s.c). 33KV indoor dead type dual core dual ratio 3CTs of ratio 200-100/5-5 A of 15 VA burden, PS 5 P10 and accuracy class 0.2.d). Control panel- Cubicle type control panel suitable for floor mounting made out of 1.63 mm CR sheet duly powder coated and with following relays.e). Microprocessor based numerical relay for O/L, E/F and SC Protection suitable for above.f). Master trip relay -2 no’s.g). Indicator type Annunciator panel with buzzer.h). Digital Volt Meter- 0-11 KV.i). Digital Amp Meter- 0-100 Amp.j). RYB/ Trip/Closing/Spring charged indicator lamp.k). Fault Annunciator panel for O/L, WTI, OTI and Buchhloz Relay Alarm And Trip Auxiliary relay.l). TNC Switch for Operation.m). Multifunction Meter EM6400NG.n). TCS Relay for Safe |
| 24 | `RAW WATER PUMP: Supplying, erection, testing and commissioning of Horizontal motor pumping set for Raw water having head as per the indicated requirements of discharge in LPM and power capacity in BHP as per IS marked1500 LPM x 25.00 m Head (For 2nd W/W) |
| 25 | `RAW WATER PUMP: Supplying, erection, testing and commissioning of Horizontal motor pumping set for Raw water having head as per the indicated requirements of discharge in LPM and power capacity in BHP as per IS marked 1300 LPM x 12.00 m Head 25 Sqmm size |
| 26 | Less credit for old Good bricks 566.64 x 60% = 340 @ 480 brick per cum = 163191 Bricks35 Sqmm size |
| 27 | Less credit for old bricks bats @ 40% ( Cum ) Total 566.64 x 40% = 226.65 Cum |
| 28 | Providing, fixing of suitable size CI sluice gate valve complete in all respects. (700 x 700 mm) |
| 29 | Providing, fixing of suitable size CI sluice gate valve complete in all respects. (800 x 800 mm) |
| 30 | RAW WATER PUMP: Supplying, erection, testing and commissioning of Horizontal motor pumping set for Raw water having head as per the indicated requirements of discharge in LPM and power capacity in BHP as per IS marked ` 4100 LPM X 15.00 M Head 2 5 BHP( For S and S Tank At 1st W/W) ) |
| 31 | `RAW WATER PUMP: Supplying, erection, testing and commissioning of Horizontal motor pumping set for Raw water having head as per the indicated requirements of discharge in LPM and power capacity in BHP as per IS marked ` 3200 LPM X 25.00 M Head 30 BHP( For 2nd W/W ) |
| 32 | `CLEAR WATER PUMP: Supplying, erection, testing and commissioning of Horizontal motor pumping set forClear water having head as per the indicated requirements of discharge in LPM and power capacity in BHP as per IS marked ` 3700 LPM x 35.00 M Head 50 bhp |
| 33 | PROVIDING AND FIXING DISPLAY BOARD OF SIZE 1200 MM X 900 MM AS PER LETTER ISSUED BY HEAD OFFICE MEMO NO 3449-60 IEC and HRD /WSSO - 28 DATED 07.08.2023 |
| 34 | Providing and fixing of 15 mm nominal diameter water meter as per IS 779:1994 Inferential type dry dial, mechanical driven, non megnatic drive, straight reading cyclometer type, 7-inline consequent digits with one center point for easy reading complete in all respect. |
| 35 | Electromagnetic Flow meter: Supply, Installation, testing, Commissioning five year maintenance, Electromagnetic Flow meter along with its installation complete in all respect as per specifications. Size as per site requirement.(IP-68), RS-485 Mod Bus and 4-20mA output. Line size 150 mm, installed at pump End / Source.4 NOS PROPOSED BOOSTING STATION AND 2 NOS WATER WORKS |
| 36 | ANNEXE BUILDING: Construction of HT / LT Panel room, PLC room, Blower room and Lab cum Office building, Toilet block including doors, windows,finishing, electric, and sanitary fittings complete in all respect as per drawings approved by SE. The building will be built up with RCC frame structure and brick work as per specifications mentioned in attached additional documents..1 |
| 37 | Operation and maintenance complete scope of work i.e 2 Nos water works WTPs capacity 2.0 MLD,1.00 MLD 2 Nos Boosting Stations ,Rising main, Distribution System, STP 2.0 MLD ,5 Nos IPS Sewerage System during defect lability period for 6 Year after 3 months Trial Run Period |
| 38 | Item Description HSR Item |
| 39 | Name of work DNIT Name :(PART-A: KAIMRI W/S SCHEME):- `Construction of 1 new W/W, R/W P/Stn., Boosting Stations, up-gradation of Exist. W/W comprising 2 WTP having capacity 2.00 and 1.50 MLD, RCC S/S tanks, R/W sump well, Inlet channel, clear water tanks, pump chamber, Boundary wall, pumping machinery, D.G set, electric transformer, R/W and C/W Rising main lines, distribution pipe lines and house connections.”(PART-B: KAIMRI SEWAGE SCHEME):- “Construction of 2.00 MLD STP (SBR technology based), SCADA / PLC controlled including MPS and 5 IPS comprising wet well sump, boundary wall, pump chamber, R/M lines, staff quarters, P/M, DG set, electric transformer and Laying the sewerage network in village. O and M of the schemes during 6 years defect liability cum maintenance period after successful trial run of 3 months and all other contingent thereto as per specifications mentioned in the DNIT Please Enable Macros to View BoQ information |