| 1 | Sub Station Works |
| 2 | Installation, Testing and Commissioning of 100 kVA, 33/0.433 kV, 3-Phase Distribution Transformer with LV Box having detachable Aluminium Gland Plate and all other accessories (Transformer to be provided by MES) |
| 3 | Supply, Carriage upto site (including Loading/Unloading),Testing and Erection of Steel Tubular Pole, 11 Mtr. Long Pole (ST-410 SP-56) with planting depth of 1/6 th of the height of the pole, (11 mtr. Long ) as per approved drawings/standards |
| 4 | Supply, Carriage upto site (including Loading/Unloading), Laying ,Stringing, Tensioning & Binding of ACSR Conductor, (100 Sqmm ACSR Conductor-Dog) as per approved drawings/standards |
| 5 | Supply, Carriage upto site (including Loading/Unloading),Testing & Fixing of GI Channel/ GI V X Arms/Extension Top/Angle Iron/Flat/Belting Angle/Anti Skidding Clamps/Fuse plates of various sizes including clamps as per approved drawings/standards |
| 6 | Supply, Carriage upto site (including Loading/Unloading),Testing & Fixing of 33 kV Isolator with Earthing Blade (36kV,800A, Outdoor,3 poles, 25 kA) as per approved drawings/standards (1 Set=03 Poles) |
| 7 | Supply, Carriage upto site (including Loading/Unloading),Testing & Fixing of 33 kV Isolator without Earthing Blade (36kV,800A, Outdoor,3 poles, 25 kA) as per approved drawings/standards (1 Set=03 Poles) |
| 8 | Supply, Carriage upto site (including Loading/Unloading),Testing & Fixing of PG Clamps suitable for 100 Sqmm ACSR as per approved drawings/standards |
| 9 | Supply, Carriage upto site (including Loading/Unloading),Testing & Fixing of HDPE Pipe Outer Dia 180 mm inner dia 152 mm for laying of 11/33 kV XLPE Cable including excavation, back filling and laying complete with all necessary accessories as per approved drawings/standards |
| 10 | Supply, Carriage upto site (including Loading/Unloading),Testing & Fixing of 33kV Polymeric composite Pin Insulator 36kV, 10kN, Lighting Impulse 170kV Positive and 180kV Negative, creepage distance 900mm (reputed make)as per approved drawings/standards |
| 11 | Supply, Carriage upto site (including Loading/Unloading),Testing & Fixing of 33kV Polymeric composite Disc Insulator 36kV,min failing load 70kN, Lighting Impulse 170kV Positive and 180kV Negative, creepage distance 900mm with disc fitting (reputed make) as per approved drawings/standards |
| 12 | Supply, Carriage upto site (including Loading/Unloading),Testing & Fixing of 33kV Horn Gap Fuse Set including all accessories as per approved drawings/standards |
| 13 | Supply, Carriage upto site (including Loading/Unloading),Testing & Fixing of 33 kV Lightening Arrestor,(33 kV ,10 kA ,Station class,ZnO, Polymer) gapless including all accessories as per approved drawings/standards |
| 14 | Supply, carriage up to site (including loading/unloading), testing and commissioning of outdoor combined CT & PT unit suitable for 33 kV, 50 Hz system voltage, having metering core CT accuracy class 0.5S, ratio 10/5 A, burden 10 VA minimum, and PT accuracy class 0.5, ratio 33 kV/110 V, complete with mounting structure, sealing arrangement and all accessories, conforming to relevant IS/IEC standards; along with 3-phase, 4-wire, CT/PT operated, fully static, AMR compatible, DLMS compliant tri-vector energy meter of accuracy class 0.5S, suitable for CT ratio 10/5 A and PT ratio 33 kV/110 V, provided with optical communication port and RS-485/RS-232 communication interface, 33kV/√3 /110V/√3, Ph-N (3P, 4W) meters for measurement of different electrical parameters including Active Energy (kWh/ MWh), Reactive Energy (kVArh/MVArh), Apparent Energy (kVAh/ MVAh) etc. complete in all respects |
| 15 | Earthing of SubStation--Excavation of earth pit of dia 650 mm & depth 3000 mm, installation of Earthing pipe of 40 mm Nominal bore & 4mm wall thickness & length 2.5 mtr long as Per IS 1239.GI Strip for neutral earthing of size 75 mm x10 mm & 50 mm x 6 mm for connection of transformer body,G.O Set & lightening arrestor as per IS 2629/85, GI nuts & bolts,refilled with earth enhancement materials and earth Chamber made of brick masonary with RCC slab cover. |
| 16 | Supply, Carriage upto site (including Loading/Unloading), Testing & Fixing of LT Distribution Box with 160 Amp MCCB 3P 16 kA for incomer & 100 Amp MCCB 3P 16 kA 02 No.s for Outgoing Circuits complete with all accessories as per approved drawings/standards |
| 17 | Supply, Carriage upto site (including Loading/Unloading), Testing & Fixing of 120 mm2 XLPE LT Cable Single Core, as per approved drawings/standards |
| 18 | Supply, Carriage upto site (including Loading/Unloading), Testing & Fixing of 120 mm2 3 1/2 Core Cable, 1.1 kV Grade, Armoured, XLPE Insulated Stranded Conductor FRLS as per approved drawings/standards |
| 19 | Supply, Carriage upto site (including Loading/Unloading), Testing & Fixing of End Termination Cable Kit Suitable for 3 1/2 Core Cable, as per approved drawings/standards |
| 20 | Supply, Carriage upto site (including Loading/Unloading),Testing & Fixing of Galvinized Nuts and Bolts as per approved drawings/standards |
| 21 | Supply, Carriage upto site (including Loading/Unloading),Testing & Fixing of Earthing Complete by GI Pipe 40 mm 3 mtr long through GI Strip 25x3mm as per approved drawings/standards |
| 22 | Supply & Laying of Cement bottoming for 11 Mtr ST Pole in 1:2:4 mix as per Standards 0.66 cum / pole including the Loading/Carriage/Unloading of required material. |
| 23 | Supply, Carriage upto site (including Loading/Unloading),Testing & Fixing of Galvanised Stay Set with 50x8mm stay clamp, guy insulator(2No.), anchor plate (300x 300 x 8 mm), nut-bolts, 2No.turnbuckles, 1.8m long,20 mm diameter solid GS stay rod & 7/4 mm dia GI stranded wire complete as per approved drawings/standards |
| 24 | Supply, Carriage upto site (including Loading/Unloading),Testing & Fixing of Guard netting as per approved drawings/standards |
| 25 | Supply,Testing,Loading,Carriage,Unloading and fixing of Danger Plates with Clamps as per approved drawings/standards |
| 26 | Supply,Testing,Loading,Carriage,Unloading and fixing of Anti-Climbing Device with Clamps as per approved drawings/standards |
| 27 | Providing & Painting of Poles 11Mtr Long with one coat of Red Oxide and two coats of aluminium paint and as per approved drawings/standards |
| 28 | Providing & Fixing of sundry items like aluminium lugs, jumpers, binding Tape etc. as per approved standards |
| 29 | Contingencies/ T&P |
| 30 | Hiring of Vehicle (Scorpio/Bolero/Innova/Tavera or equivalent) to be used by the Engineer Incharge for supervision of the project including Fuel/Toll Tax/ Driver/ any other maintenace charges of the vehicle. The max. Kms to be driven per day is 120 Km. In case the vehicle is utilized less than 120 km on any given day, the payment shall be subject to deduction on account of actual fuel savings. Such deduction shall be worked out proportionately based on the approved mileage (km per litre) of the vehicle and the prevailing fuel rate. |
| 31 | Supply of ISI-marked Safety Helmet made of high-quality, impact-resistant HDPE/ABS material, equipped with adjustable headband, chin strap, ventilation system, and sweat-absorbent inner lining, conforming to IS:2925 standards, of approved make and colour, as per directions of the Engineer-in-Charge |
| 32 | Supply of ISI-marked Safety Belt / Full Body Harness made of high-strength polyester webbing with adjustable shoulder and thigh straps, equipped with double lanyard, shock absorber, and forged steel snap hooks, conforming to IS:3521 standards, of approved make and quality, as per directions of the Engineer-in-Charge |
| 33 | Supply of ISI-marked industrial Safety Shoes made of genuine leather with steel toe cap, oil/acid/slip resistant PU sole, shock-absorbing heel, and padded ankle support, conforming to IS:15298 (Part 2) standards, of approved make, size, and quality, as per directions of the Engineer-in-Charge |
| 34 | Supply of Electrical Rubber Insulating Gloves suitable for working up to 33 kV, made of high-dielectric natural rubber, seamless, ergonomically designed, conforming to IS:4770 / IEC 60903 standards, duly tested and certified, complete with manufacturer’s test certificate, of approved make and quality, as per directions of the Engineer-in-Charge. |
| 35 | Supply of High Voltage Detector suitable for outdoor/indoor use, capable of detecting multiple voltage levels ranging from 3.3 kV to 33 kV (or higher as specified), provided with clear audible and visual indication, telescopic epoxy/fiberglass insulating rod, battery-operated electronic circuit, and complete with carrying case, conforming to relevant IS/IEC standards, of approved make and quality, as per directions of the Engineer-in-Charge Please Enable Macros to View BoQ information |