| Sl. No. | Item Description |
| 1 | Construction of Emergency ward for T.B. Co-Combined Hospital Thakurganj, District-Lucknow (U.P.) |
| 2 | Earth work in excavation by mechanical means (Hydraulic excavator) manual means in foundation trenches or drains (not exceeding 1.5 m width or 10 sqm on plan), including dressing of sides and ramming of bottoms, for all lift, including getting out the excavated soil and disposal of surplus excavated soil as directed, within a lead of 50 m. |
| 3 | Extra for every additional lift of 1.5 m or part thereof in excavation / banking excavated or stacked materials. |
| 4 | Excavating, supplying, stacking and filling of local earth (including royalty) by mechanical transport upto a lead of 5km also including ramming and watering of the earth in layers not exceeding 20 cm in foundation trenches, plinth, sides of foundation etc. complete for all lift. |
| 5 | Local Sand filling in plinth including supply of neccasary quantity of sand from the site of work 8km and including watering dessing etc. including cost of all materials labour and T&P etc . Required for proper completion of the work. |
| 6 | Providing and injecting chemical emulsion for preconstructional antitermite treatment and creating a chemical barrier under and alround the column pits wall trenches basement excavation top surface if plinth filling junction of wall and floor, along the the external perimeter of binding expansion joints, surrounding of pipes and conduits etc, complete(plinth area of the building at ground floor only shall be measured as per I.S.6313 (PartII 1981) Alderine emulsifiable concentrate or any other approved material such as Heptrachlor or Chlordane will be used. The rate of application of chemical emulsion shall be as follows : (3) Treatment of top surface of plinth filling 5 liters/sqm |
| 7 | With Chlorpriphos EC 20% with 1% concentration |
| 8 | Providing and laying Cement Concret 1:4:8 (1cement :4coarse sand :8 stone aggregate 40mm including supply of all material ,labour and t&p etc.required for completion of work. |
| 9 | Providing and laying in position machine battched and machine mixed design mix M- 25 grade cement concrete for RCC work using cement content as per approved design mix. Including pumping of concrete to site of laying but including the cost of centreing, shuttering, finishing and Excluding reinforcement, including admixtures in recommended proportions as per IS 9103 to accelerate, retard setting of concrete, improve workability without impaaining strenght and durability as per direction of Engineer - In - Charge All works upto plinth level Footing , coloum, plinth beam |
| 10 | All works above plinth level upto floor V level column, beam ,lintel, slab / chazza |
| 11 | Centering and shuttering including strutting, propping etc. and removal of formfor |
| 12 | Foundations, footings, bases of columns, etc. for mass concrete |
| 13 | Columns, Pillars, Piers, Abutments, Posts and Struts |
| 14 | Lintels, beams, plinth beams, girders, bressumers and cantilevers |
| 15 | Suspended floors, roofs, landings, balconies and access platform |
| 16 | Mild steel or iron in plain work such as reinforced concrete or reinforced, brick work (when not included in anover all rates ) wrought to required shape as necessary including bending for proper completion of the work. FE 500 TMT BARS |
| 17 | Class-150 (non- Modular) brick work in foundation and Plinth including supply of all materials, labour and t&p etc. required for proper completion of the work.Cement mortar 1:4 (1 cement : 4 coarse sand) |
| 18 | Providing and laying damp proof course 40 mm thick with cement concrete 1:2:4 (1 cement : 2 Coarse sand : 4 graded stone aggregate 12.5mm nominal size) |
| 19 | Providing and applying a coat of residual petroleum bitumen of grade of VG - 10 of approved quality using 1.7 kg per sqm. On DPC after cleaning the surface with brushes and finally with a piece of cloth lightly soaked in kerosene oil. |
| 20 | Brick work with common burnt clay (non moduler) brick of class -150 in super structure above plith lvl upto floor v lvl. In all shape and size in 1:4 (1: cement 4: coarse and mortar in one brick wall (230mm Thick ) |
| 21 | Half brick masonry with common burnt clay F.P.S. (non modular) bricks of class designation 7.5 in superstructure above plinth level up to floor V level. |
| 22 | Extra for providing and placing in position 5 Nos 10mm dia. M.S. bars at every third course of half brick masonry. |
| 23 | FLOORING |
| 24 | Providing and laying vitrified floor tiles in different sizes (thickness to be specified by the manufacturer) with water absorption less than 0.08% and conforming to IS: 15622, of approved make, in all colours and shades, laid on 20mm thick cement mortar 1:4 (1 cement : 4 coarse sand), jointing with grey cement slurry @ 3.3 kg/ sqm including grouting the joints with white cement and matching pigments etc., complete.Size of Tile 600x600 mm |
| 25 | Providing and laying Vitrified tiles in different sizes (thickness to be specified by the manufacturer), with water absorption less than 0.08% and conforming to IS: 15622, of approved brand & manufacturer, in all colours and shade, in skirting, riser of steps, laid with cement based high polymer modified quick set tile adhesive (water based) conforming to IS: 15477, in average 6 mm thickness, including grouting of joints (Payment for grouting of joints to be made separately).Size of Tile 600x600 mm |
| 26 | Providing and laying Homogeneous VINYL floor (armstrong) simpurity with diamond 10 coating . Thickness 2mm & 2 mtr. Wide thickness of wear layer would be 2mm & single layered. Operation complete as per direction of Engineer - In - Charge. |
| 27 | Providing and fixing 1st quality ceramic glazed floor tiles conforming to IS : 15622 (thickness to be specified by the manufacturer ) of approved make in all colours, shades except burgundy, bottle green, black of any size as approved by Engineer-in-Charge in skirting, risers of steps and dados over 12 mm thick bed of cement Mortar 1:3 (1 cement: 3 coarse sand) and jointing with grey cement slurry @ 3.3kg per sqm including pointing in white cement mixed with pigment of matching shade complete. |
| 28 | Providing and fixing rectified Glazed Ceramic floor tiles of size 300x300mm or more (thickness to be specified by the manufacturer), of 1st quality conforming to IS : 15622, of approved make, in colours White, Ivory, Grey, Fume Red Brown, laid on 20 mm thick cement mortar 1:4 (1 cement : 4 Coarse sand), jointing with grey cement slurry @ 3.3kg/sqm. Including grouting the joints with white cement and matching pigments etc, complete. |
| 29 | Kota stone slab flooring over 20 mm (average) thick base laid over and jointed with grey cement slurry mixed with pigment to match the shade of the including rubbing and polishing complete with base of cement mortar 1 : 4 (1 cement : 4 coarse sand) :25 MM THICK |
| 30 | Providing edge moulding to 18 mm thick marble stone counters, Vanities etc., including machine polishing to edge to give high gloss finish etc. complete as per design approved by Engineer-in-Charge. |
| 31 | Providing and fixing Area of slab upto 0.50 sqm Area of slab over 0.50 sqm 18 mm thick gang saw cut, mirror polished, premoulded and prepolished, machine cut for kitchen platforms, vanity counters, window sills, facias and similar locations of required size, approved shade, colour and texture laid over 20 mm thick base cement mortar 1:4 (1 cement : 4 coarse sand), joints treated with white cement, mixed with matching pigment, epoxy touch ups, including rubbing, curing, moulding and polishing of edges to give high gloss finish etc. complete at all levels.Area of slab over 0.50 sqm |
| 32 | 12 mm thik plaster with 1:6(cement :Coarse sand )2.25 F.M. over brick work minimum thickness not to be less than 1 cm .including supply of all material labour and T&P etc.required for proper completion of the work.Add for extra labour &materials for plaster over rough face of one brick wall .outer wall |
| 33 | 12 mm thik plaster with 1:6(cement :Coarse sand )2.25 F.M. over brick work minimum thickness not to be less than 1 cm .including supply of all material labour and T&P etc.required for proper completion of the work.Add for extra labour &materials for plaster over rough face of one brick wall .Inner wall |
| 34 | Engraving line in the plaster of the outer face wall vertically and horizontally to display the surface as s directed by the engineer -in-charges including labour and T&P etc. required for completion of work in the proportion recommended by the manufacture. |
| 35 | Providing and applying white cement based putty of average thickness 1 mm, of approved brand and manufacturer, over the plastered wall surface to prepare the surface even and smooth complete. |
| 36 | Finishing walls with Acrylic Smooth exterior paint(APEX) of required shade : New work (Two or more coat applied @ 1.25 ltr/10 sqm over and including priming coat of exterior primer applied @.75 LTR/10 sqm) |
| 37 | Wall painting with acrylic emulsion paint of approved brand and manufacture to give an even shade : Two or more coats on new work.Applying one coat of water thinnable cement primer of approved brand and manufacture on wallsurface : |
| 38 | Painting with synthetic enamel paint or approved band and manufacture of required colour to give an even shade.Two or more coats on new work over an under coat of suitable shade with ordinary paint of approved brand and manufacture |
| 39 | Providing and fixing factory made uPVC white colour sliding glazed window upto 1.50 m in heightdimension comprising of uPVC multi-chambered frame with in-built roller track and sash extrudedprofiles duly reinforced with 1.60 ± 0.2 mm thick galvanized mild steel section made from roll formingprocess of required length (shape & size according to uPVC profile), appropriate dimension of uPVCextruded glazing beads and uPVC extruded interlocks, EPDM gasket, wool pile, zinc alloy (white powder coated) touch locks with hook, zinc alloy body with single nylon rollers (weight bearing capacity to be 40 kg), G.I fasteners 100 x 8 mm size for fixing frame to finished wall and necessary stainless steel screws etc. Profile of frame & sash shall be mitred cut and fusion welded at all corners, including drilling of holesfor fixing hardware's and drainage of water etc. After fixing frame the gap between frame and adjacentfinished wall shall be filled with weather proof silicon sealent over backer rod of required size and ofapproved quality, all complete as per approved drawing & direction of Engineer-in-Charge. (Single /double glass panes, wire mesh and silicon sealent shall be paid separately). Variation in profiledimension in higher side shall be accepted but no extra payment on this account shall be made.Three track three panels sliding window with fly proof SS wire mesh (Two nos. glazed & one no. wire mesh panels) made of (small series) frame 92 x 44 mm & sash 32 x 60 mm both having wall thickness of 1.9 ± 0.2 mm and single glazing bead of appropriate dimension (Area of window upto 1.75 sqm). |
| 40 | Providing and fixing factory made uPVC white colour casement/casement cum fixed glazed windows comprising of uPVC multi-chambered frame, sash and mullion (where ever required) extruded profiles duly reinforced with 1.60 ± 0.2 mm thick galvanized mild steel section made from roll forming process of required length (shape & size according to uPVC profile), uPVC extruded glazing beads of appropriate dimension, EPDM gasket, stainless steel (SS 304 grade) friction hinges, zinc alloy (white powder coated) casement handles, G.I fasteners 100 x 8 mm size for fixing frame to finished wall, plastic packers, plastic caps and necessary stainless steel screws etc. Profile of frame & sash shall be mitred cut and fusion welded at all corners, mullion (if required) shall be also fusion welded including drilling of holes for fixing hardware's and drainage of water etc. After fixing frame the gap between frame and adjacent finished wall shall be filled with weather proof silicon sealant over backer rod of required size and of approved quality, all complete as per approved drawing & direction of Engineer-in-Charge. (Single / double glass panes and silicon sealant shall be paid separately). Variation in profile dimension in higher side shall be accepted but no extra payment on this account shall be made.Casement door with 3D hinges made of (big series) frame 67 x 64 mm & sash 67 x 110 mm both having wall thickness of 2.3 ± 0.2 mm and single glazing bead / double glazing bead of appropriate dimension.(Area of door upto 2.00 sqm). |
| 41 | Mild steel or iron work of small sizes and sections such as holding down bolts,hold fast tierods,gratings etc. ( when not included in an over all rates) wrought to required from including supply of steel and its wastage including cost of bolts, nuts if required for and welding, grinding and making holes as required completion of work . |
| 42 | Providing and fixing M.S. Tubular frames for doors, windows, ventilators and cupboard with rectangular/ L-Type sections, made of 1.60 mm thick M.S. Sheet, joints mitred, welded and grinded finish, with profiles of required size, including fixing of necessary butt hinges and screws and applying a priming coat of approved steel primer. |
| 43 | Providing and fixing ISI marked flush door shutters conforming to IS : 2202 (Part I) decorative type, core of block board construction with frame of 1st class hard wood and well matched teak 3 ply veneering with vertical grains or cross bands and face veneers on both faces of shutters.35 mm thick including ISI marked Stainless Steel butt hinges with necessary screws |
| 44 | Providing and fixing glazing in aluminium door, window, ventilator shutters and partitions etc. with EPDM rubber/ neoprene gasket etc. complete as per the architecttural drawings and the directins of engineer-in-charge (Cost of aluminium snap beadingg shall be paid in basic item)With float glass panes of 5.5 mm thicness |
| 45 | Providing and fixing of stainless steel 304 grade handle for door.32mmx 600 mm long sss.(Ozone make) |
| 46 | Providing and fixing ISI marked S.S Sliding door bolts with nuts and screws etc. complete |
| 47 | 300x16 mm |
| 48 | Providing and fixing ISI marked S.S.. Tower bolt black finish, (Barrel type) with necessary screws etc. complete |
| 49 | 300x10 mm |
| 50 | Providing and fixing S.S. handles with screws etc. complete: |
| 51 | 125 mm |
| 52 | Providing and fixing bright finished brass hanging type floor door stopper with necessary screws, etc.complete. |
| 53 | Providing and fixing double action hydraulic floor spring of approved brand and manufacture conforming to IS : 6315, having brand logo embossed on the body / plate with double spring mechanism and door weight upto 125 kg, for doors, including cost of cutting floors, embedding in floors as required andmaking good the same matching to the existing floor finishing and cover plates with brass pivot andsingle piece M.S. sheet outer box with slide plate etc. complete as per the direction of Engineer-incharge.. |
| 54 | With stainless steel cover plate minimum 1.25 mm thickness |
| 55 | Providing and fixing 15 mm thick false ceiling tiles at all heights with integral densified calcium silicate reinforced with fibre and natural filler false ceiling tiles of Size 595x595 mm of approved texture, design and patterns having NRC (Noise Reduction coefficient) of 0.50 (minimum) as per IS 8225:1987, Light reflectance of 85% (minimum). Non combustible as per BS:476 (part-4), fire performance as per BS:476 (part 6 &7), humidity resistance of 100%, thermal conductivity < 0.043 W/m K as per ASTM 518:1991,in true horizontal level on the existing frame work consisting of T-sections and Lsections suitably fixed according to tile size as per direction of Engineer-in-charge. |
| 56 | Providing and fixing to the inlet mouth of rain water pipe cast iron grating 15 cm diameter and weighing not less than 440 grams. Providing and fixing false ceiling at all heights including providing and fixing of frame work made of special sections, power pressed from M.S. sheets and galvanized with zinc coating of 120 gms/sqm (both side inclusive) as per IS : 277 and consisting of angle cleats of size 25 mm wide x 1.6 mm thick with flanges of 27 mm and 37mm, at 1200 mm centre to x centre, one flange fixed to the ceiling with dash fastener 12.5 mm dia 50 mm long with 6 mm dia bolts, other flange of cleat fixed to the angle hangers of 25x10x0.50 mm of required length with nuts & bolts of required size and other end of angle hanger fixed with intermediate G.]. channels 45x15x0.9 mm running at the spacing of 1200 mm centre to centre, to which the ceiling section 0.5 mm thick bottom wedge of 80 mm with tapered flanges of 26 mm each having lips of 10.5 mm, at 450 mm centre to centre, shall be fixed in a direction perpendicular to G.|. intermediate channel with connecting clips made out of 2.64 mm dia x 230 mm long G.I. wire at every junction, including fixing perimeter channels 0.5 mm thick 27 mm high having flanges of 20 mm and 30 mm long, the perimeter of ceiling fixed to wall/partition with the help of rawl plugs at 450 mm centre, with 25 mm long dry wall screws @ 230 mm interval, including fixing of gypsum board to ceiling section and perimeter channel with the help of dry wall screws of size 3.5 x 25 mm at 230 mm c/c, including jointing and also finishing to a flush finish of tapered and square edges of the board with recommended jointing compound , jointing tapes , finishing with jointing compound in 3 layers covering upto 150 mm on both sides of joint and two coats of primer suitable for board, all as per manufacturer’s specification and all in Charge but excluding the cost of painting with : 12.45.1 12.45.2 12.45.3 12.45.4 to IS: 12.5 mm each each each including the cost of making openings for light fittings, grills, diffusers, cutouts made with frame of perimeter channels suitably fixed, complete as per drawings, specification and direction of the Engineer |
| 57 | Fully Perforated Gypsum Plaster Board of size 1200 x 2400x12.5 mm having approx. 15 % perforated area with perforation size and pattern as approved by the Engineer- in-charge and as per manufacturer’s specification, with all 4 sides tapered and backed by acoustical tissue with NRC value not less than 0.60 |
| 58 | GI Metal Ceiling Clip in plain Beveled edge global white color tiles of size 600x600 and 0.5 mm thick with 25 mm height, made of G | sheet having galvanizing of 100 gms/ sqm (both sides inclusive) and 20% perforation area with 1.8 mm dia holes and having NRC of 0.5, electro statically polyester powder coated of thickness 60 microns (minimum), including factory painted after bending and perforation. |
| 59 | Cement concrete flooring 1:2:4 ( 1 Cement : 2 Coarse sand : 4 gradede stone aggregate) finished with a floating coat of neat cement, including cement slurry, but excluding the cost of nosing of steps etc. complete (25 mm thick) |
| 60 | Appron Drain (150x150 ) size with M-150 Class brick work in 1:3 cement and coarse sand mortar F.M.2.5 along appron including supply of all materials labour and t&Petc.required for proper completion of work. |
| 61 | Chequered terrazo tiles 22 mm thick with graded marble chips of size up mm in floors, jointed with neat cement slurry mixed with pigment to match the shade of the tiles, including rubbing and polishing complete, on 20 mm thick bed of cement mortar 1:4 (1 cement :4 coarse sand) : |
| 62 | Providing and laying integral cement based water proofing treatment including preparation of surface as required for treatment of roofs, balconies, terraces etc consisting of following operations: (a) Applying a slurry coat of neat cement using 2.75 kg/sqm of cement admixed with water proofing compound conforming to IS. 2645 and approved by Engineer-in-charge over the RCC slab including adjoining walls upto 300 mm height including cleaning the surface before treatment.(b) Laying brick bats with mortar using broken bricks/brick bats 25 mm to 115 mm size with 50% of cement mortar 1:5 (1 cement : 5 coarse sand) admixed with water proofing compound conforming to IS : 2645 and approved by engineer-in-charge over 20 mm thick layer of cement mortar of mix 1:5 (1 cement :5 coarse sand ) admixed with water proofing compound conforming to IS : 2645 and approved by Engineer-in-charge to required slope and treating similarly the adjoining walls upto 300 mm height including rounding of junctions of walls and slabs.(c) After two days of proper curing applying a second coat of cement slurry using 2.75 kg/ sqm of cement admixed with water proofing compound conforming to IS : 2645 and approved by Engineer-incharge.(d) Finishing the surface with 20 mm thick jointless cement mortar of mix 1:4 (1 cement :4 coarse sand) admixed with water proofing compound conforming to IS : 2645 and approved by Engineer-in-charge including laying glass fibre cloth of approved quality in top layer of plaster and finally finishing the surface with trowel with neat cement slurry and making pattern of 300x300 mm square 3 mm deep.(e) The whole terrace so finished shall be flooded with water for a minimum period of two weeks for curing and for final test.“All above operations to be done in order and as directed and specified by the Engineer-in-Charge : |
| 63 | S/o Hand rail and balustarde modular systom passive ss-304 grade decorative railing system comprising of hand rail 50mm and 1.5 mm thick and 3 no .horizontal steel pipe of 19 mm dia and 1.5 mm thick of equal spacing with balustrade fo ss pipe of 38nn and 1.5mm thick @ 1200mm c/c of passivated ss304 rade and fix duly on the floor with spacially rivet expansion bolt and finish the surface food and covering with steel shoe ,with all visible stainless metal of 304 grade in satin finish hight of railing is 900 mm as per detailed speicification. |
| 64 | SUB HEAD - I - (SANITARY FIXTURES & C.P. BRASS FITTING) |
| 65 | Providing and fixing water closet squatting pan (Indian type W.C. pan) with 100 mm sand cast Iron P or S trap, 10 litre low level white P.V.C. flushing cistern, including flush pipe, with manually controlled device (handle lever) conforming to IS : 7231, with all fittings and fixtures complete, including cutting and making good the walls and floors wherever required:- |
| 66 | White Vitreous china Orissa pattern W.C. pan of size580x440 mm with integral type foot rests |
| 67 | Providing and fixing white vitreous china pedestal type water closet (European type) with seat and lid, 10 litre low level white vitreous china flushing cistern & C.P. flush bend with fittings & C.I. brackets, 40 mm flush bend, overflow arrangement with specials of standard make and mosquito proof coupling of approved municipal design complete, including painting of fittings and brackets, cutting and making good the walls and floors wherever required |
| 68 | W.C. pan with ISI marked white solid plastic seat and lid |
| 69 | Providing and fixing white vitreous china flat back or wall corner type lipped front urinal basin of 430x260x350 mm or 340x410x265 mmsizes respectively. (Manual) |
| 70 | Providing and fixing stone slab with table rubbed, edges rounded and polished, of size 75x50 cm deep and 1.8 cm thick, fixed in urinal partitions by cutting a chase of appropriate width with chase cutter and embedding the stone in the chase with epoxy grout or with cement concrete 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate 6 mm nominal size) as per direction of Engineer-in-charge and finished smooth. |
| 71 | White Agaria Marble Stone |
| 72 | Providing and fixing wash basin with C.I. brackets, 15 mm dia CP Brass single hole basin mixer of approved quality and make, including painting of fittings and brackets, cutting and making good the walls wherever required:- |
| 73 | White Vitreous China Wash basin size 550x400 mm with a 15 mm CP Brass single hole basin mixer |
| 74 | Providing and fixing white vitreous china laboratory sink including making all connections excluding cost of fittings : |
| 75 | Size 450x300x150 mm |
| 76 | Providing and fixing P.V.C. waste pipe for sink or wash basin including P.V.C. waste fittings complete. |
| 77 | Semi rigid pipe |
| 78 | 40 mm dia |
| 79 | Providing and fixing uplasticised PVC connection pipe with brass unions : |
| 80 | 30 cm length |
| 81 | 15 mm nominal bore |
| 82 | 45 cm length |
| 83 | 15 mm nominal bore |
| 84 | Providing and fixing CP Brass 32mm/40mm size Bottle Trap of approved quality & make and as per the direction of Engineer-in-charge. |
| 85 | Providing and fixing 600 x 450mm beveled edge mirror of superior glass (of approved quality) complete with 6 mm thick hard board ground fixed to wooden cleats with C.P. brass screws and washers complete in all respect. |
| 86 | Providing and fixing C.P. brass bib cock of approved quality conforming to IS:8931 : |
| 87 | 15 mm nominal bore |
| 88 | Providing and fixing C.P. brass long body bib cock of approved quality conforming to IS standards and weighing not less than 690 gms. 15 mm nominal bore |
| 89 | 15 mm nominal bore |
| 90 | Providing and fixing C.P. brass stop cock (concealed) of standard design and of approved make conforming to IS: 8931. |
| 91 | 15 mm nominal bore |
| 92 | Providing and fixing C.P. brass angle valve for basin mixer and geyser points of approved quality conforming to IS:8931 |
| 93 | 15 mm nominal bore |
| 94 | Providing & fixing C.P. hand spray with lever control (health faucet) and flexible hose 1 m long connection with C.P. holder for hand spray complete in all respects. (Angle valve to be provide under item no. 18 and measure with that item.) |
| 95 | Providing & Fixing Stainless Steel dustbin. |
| 96 | Providing and fixing twin coat hook complete with brackets fixed to wooden cleats with CP brass screws with concealed fittings arrangement of approved quality and colour. |
| 97 | RO Plant 40 LPH (Liter per hour) PLANT CAPACITY - 40 LPHTreated Water QualityTurbidity : <1NTUpH : 6.5-7.0Chlorides : < 10 ppmSulphates : < 5 ppmTDS : < 150 ppm |
| 98 | Supply installation, testing and commissioning of water cooler Cooling Capacity150Ltrs. / Hrs.,Storage Capacity 40 Ltrs |
| 99 | HANDICAPPED TOILET :- |
| 100 | Providing and fixing of WB 46 x 36 with one pair mounting brackets, EWC & Cistern complete with fittings & seat cover, one no. hinged rail 76 cm & 4 nos. of grab rails 60 cm. |
| 101 | RAIN WATER DRAINAGE WORK |
| 102 | Providing and laying cement concrete 1:5:10(1 cement : 5 coarse sand : 10 graded stone aggregate 20mm nominal size) around P.V.C Soil and waste pipe including bed concrete as per standard design(embedded in the flooring / ground) |
| 103 | 110 mm dia |
| 104 | Providing and fixing on wall face unplasticised-Rigid PVC rain water pipes conforming to IS: 13592 Type A including jointing with seal ring conforming to IS: 5382 leaving 10mm gap for thermal expansion. |
| 105 | 110 mm |
| 106 | Providing and fixing on wall face unplasticised PVC moulded fittings/accessories for unplasticised Rigid PVC rain water pipes conforming to IS:13592 Type A including jointing with seal ring conforming to IS:5382 leaving 10mm gap for thermal expansion. Coupler 110 mm |
| 107 | Single tee with door |
| 108 | 110x110x110 mm |
| 109 | Single tee without door |
| 110 | 110x110x110 mm |
| 111 | Bend 87.5 degree |
| 112 | 110 mm Bend |
| 113 | Shoe (Plain) |
| 114 | 110 mm Shoe |
| 115 | Providing and fixing to the inlet mouth of rain water pipe cast iron grating 15 cm diameter and weighing not less than 440 grams. |
| 116 | Making khurras 45x45 cm with average minimum thickness of 5 cm cement concrete 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate of 20 mm nominal size) over PVC sheet 1m x 1 m x 400 micron, finished with 12 mm cement plaster 1:3 (1 cement : 3 coarse sand) and a coat of neat cement,punning,rounding the edges and making and finishing the outlet complete. |
| 117 | Providing and fixing M.S. holder bat clamps of approved design to C.I. or S.C.I. rain water pipes embedded in and including cement concrete blocks 10x10x10 cm of 1:2:4 mix (1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size) and cost of cutting holes and making good the walls etc. : 110 mm dia |
| 118 | UPVC SWR SOIL, WASTE & VENT PIPES AND FITTINGS |
| 119 | Providing, fixing, jointing and testing, uPVC SWR pipes, - type B conforming to IS : 13592 to wall, ceiling and floor, approved quality, complete, for soil, waste & rain water drain including pushfit jointing with seal ring. (i) Single socketed pipes. |
| 120 | Internal Toilet (Soil, Waste & Rain Water Pipe) |
| 121 | 100 mm dia. |
| 122 | 150 mm dia.(For Storm Water in Court yard) |
| 123 | Cutting holes up to 30x30 cm in walls including making good the same: With With common burnt clay F.P.S. (non modular) bricks |
| 124 | Cutting holes up to 15x15 cm in R.C.C. floors androofs for passing drain pipe etc. and repairing the hole after insertion of drain pipe etc. with cement concrete 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size), including finishing complete so as to make it leak proof |
| 125 | Supply and fixing of UPVC S.W.R. Gully trap confirming to IS-14735 size 150×110mm dia of selt eleaning design inciuding fixed brick Masonry chamber 250×250x250mm.size i/c supply and fixing of CI cever with frame wait not less then 4.50Kg. & CI grating. 150× 150mm complete in all respect. |
| 126 | 250mm x 250mmX250mm |
| 127 | Providing and fixing on wall face unplasticised - PVC moulded fittings/accessories for unplasticised Rigid PVC pipes including jointing with seal ring leaving 10 mm gap for thermal expansion. |
| 128 | Bend without door (45°) |
| 129 | 110mm |
| 130 | Y' Fitting without door |
| 131 | 110mm |
| 132 | Single Tee without door |
| 133 | 110 mm |
| 134 | Coupler |
| 135 | 110mm |
| 136 | 160mm |
| 137 | Clean Out Plug (COP) |
| 138 | 110mm |
| 139 | Vent Cowl |
| 140 | 110mm |
| 141 | Providing, fixing, jointing and testing, unplasticized PVC pipes -10 kg/cm2 confirming to IS : 4985 to wall, ceiling and floor, approved quality, complete,for waste water drain including jointing with rubbering/solvent/solution and airtight joints, etc. |
| 142 | For Wash basin & Urinal |
| 143 | 50mm dia. Pipe |
| 144 | 40mm dia. Pipe (for wash basin & sunken toilet spout) |
| 145 | Elbow (90°) |
| 146 | Elbow (45°) |
| 147 | T fitting |
| 148 | Coupler |
| 149 | Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes, having thermal stability for hot & cold water supply, including all CPVC plain & brass threaded fittings, i/c fixing the pipe with clamps at 1.00 m spacing. This includes jointing of pipes & fittings with one step CPVC solvent cement and the cost of cutting chases and making good the same including testing of joints complete as per direction of Engineer in Charge. |
| 150 | Concealed work, including cutting chases and making good the walls etc. |
| 151 | 15 mm dia nominal bore |
| 152 | 20 mm dia nominal bore |
| 153 | Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes,having thermal stability for hot & cold water supply, including all CPVC plain & brass threaded fittings, including fixing the pipe with clamps at 1.00 m spacing. This includes jointing of pipes & fittings with one step CPVC solvent cement and testing of joints complete as per direction of Engineer in Charge. |
| 154 | 25 mm dia nominal bore |
| 155 | 32 mm dia nominal bore |
| 156 | 40 mm dia nominal bore |
| 157 | Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes, having thermal stability for hot & cold water supply including all CPVC plain & brass threaded fittings This includes jointing of pipes & fittings with one step CPVC solvent cement, trenching, refilling & testing of joints complete as per direction of Engineer in Charge |
| 158 | Internal work - Exposed on wall / Terrace |
| 159 | 20 mm dia nominal bore |
| 160 | 25 mm dia nominal bore |
| 161 | 32 mm dia nominal bore |
| 162 | 40mm dia nominal bore |
| 163 | 50 mm dia nominal bore |
| 164 | 65 mm dia nominal bore |
| 165 | Providing and fixing gun metal gate valve with wheel of approved quality. |
| 166 | 20mm dia nominal bore |
| 167 | 25mm dia nominal bore |
| 168 | 32mm dia nominal bore |
| 169 | 40mm dia nominal bore |
| 170 | 50mm dia nominal bore |
| 171 | 65mm dia nominal bore |
| 172 | Providing and fixing MS pipe puddle flanges of required size with 600mm long with 6mm thick MS plate of size 300mm x 300mm of suitable size properly fixed in RCC walls of water tanks, including necessary welding complete in all respect as per details shown on darwings and directions of Engineeer-in-charge for water tanks. |
| 173 | 25mm dia. |
| 174 | 40mm dia. |
| 175 | 50mm dia. |
| 176 | 65mm dia. |
| 177 | 80mm dia. |
| 178 | 100mm dia. |
| 179 | Constructing brick masonry road gully chamber 50x45x60 cm with bricks of class designation 75 in cement mortar 1:4 (1 cement : 4 coarse sand) including 500x450 mm pre-cast R.C.C. horizontal grating with frame complete as per standard design:- |
| 180 | With common burnt clay F.P.S. (non modular) bricks of class designation 7.5 |
| 181 | FIRE FIGHTING WORKS: |
| 182 | SUB HEAD - I (PUMPING EQUIPMENTS) |
| 183 | Supplying, installation, testing and commissioning of electric driven terrace pump suitable for automatic operation and consisting of following, complete in all respects, as required: (Terrace Pump) |
| 184 | Horizontal type, multistage, centrifugal, split casing pump of cast iron body & bronze impeller with stainless steel shaft, mechanical confirming to IS : 1520. |
| 185 | Suitable HP squirell cage induction motor TEFC type suitable for operation on 415 volts, 3 phase, 50 Hz, AC supply with IP55 class of protection for nclosure, horiziontal foot mounted type with Class-'F' insulation, conforming to IS-325. |
| 186 | M.S.fabricated common base plate, coupling, coupling guard, foundation bolts etc.as required. |
| 187 | Suitable cement concrete foundation duly plastered and with anti vibration pads. |
| 188 | 450 lpm at 35 m Head. |
| 189 | Supplying and fixing air vessel made of 250 mm dia, 8 mm thick MS sheet, 1200 mm in height with air release valve on top and flanged connection to riser, drain arrangement with 25 mm dia gun metal wheel valve with required accessories, pressure gauge and paintingwith synthetic enamel paint of approved shade as required |
| 190 | 1.2 Meter high and 250 mm dia. |
| 191 | Supply, Installation, testing and commissioning of pressure switches for Hydrant / Diesel Engine Driven Pump / Jockey Pumps, diaphragm type, adjustable range from 0-9 bar and a regulation range of 0.1 - 1.5 bar direct mounted SNAP acting type made from die cast aluminium with epoxy powder coated finish and SS316 diaphragm and other wetted parts, including necessary wiring upto control panel & other materials as required as per specifications. |
| 192 | SUB HEAD - II - (PIPING, VALVES AND ACCESSORIES) |
| 193 | SLTC of M.S. pipe on surface |
| 194 | Providing, laying, testing & commissioning of 'C' class heavy duty MS pipe conforming to IS 3589/IS 1239 including Welding, fittings like elbows, tees, flanges, tapers, nuts bolts, gaskets etc. and fixing the pipe on the wall/ceiling with suitable clamp/support frame and painting with two or more coats of synthetic enamel paint of required shade complete as required : |
| 195 | 100 mm dia |
| 196 | 25 mm dia |
| 197 | Providing laying, testing & commissioning of 'C' class heavy duty MS Pipe conforming to IS 1239/3589 i/c fittings like elbows, tees, flanges, tapers, nuts bolts, gaskets etc. in ground including welding, excavation & providing cement concrete blocks as supports, anticorrosive treatment with coaltar/asphalt tape as per IS 10221, refilling the trench etc. of following sizes complete as required. |
| 198 | 100 mm dia |
| 199 | Supplying, fixing, testing and commissioning of butterfly valve of PN 1.6 rating with bronze/gunmetal seat duly ISI marked complete with nuts, bolts, washers, gaskets conforming to IS 13095 of following sizes as required |
| 200 | 100 mm dia |
| 201 | Providing, installation, testing and commissioning of non-return valve of following sizes confirming to IS: 5312 complete with rubber gasket, GI bolts, nuts, washers etc.as required |
| 202 | 100 mm dia |
| 203 | Supply, Installation, Testing and Commissioning of 100 mm dia Bourden type, Stainless Steel dial type Pressure Gauge including brass isolation valve and siphon pipe having calibration of 0 - 16 Kg / cm2 . |
| 204 | Providing, installation, testing and commissioning of stainless steel Y-strainer fabricated out of 1.6 mm thick stainless steel, Grade 304, sheet with 3 mm dia holes with stainless steel flange |
| 205 | 100 mm dia |
| 206 | Supplying and Fixing of Fire Man's axe with heavy insulated rubber as per standard conforming to IS 926. |
| 207 | Providing & fixing double flanged Metallic expansion with M.S. fixed flanges (PN-1.6) joint (suitable for system test pressure) of standard length as per manufacturers specs including rubber gaskets, flanges, nuts, bolts and washers complete as required as per specifications. |
| 208 | 100 mm dia |
| 209 | SUB HEAD - III - (HYDRANTS SYSTEM) |
| 210 | Supplying and fixing first-aid Hose Reel with MS construction spray painted in post office red, conforming to IS 884 complete with the following as required. 20 mm nominal internal dia water hose thermoplastic (Textile reinforced) type -2 as per IS: 12585. 20 mm nominal internal dia gun metal globe valve & nozzle. Drum and brackets for fixing the equipmets on wall. Connections from riser with 25 mm dia stop gun metal valve & M.S. Pipe and socket |
| 211 | SITC weather proof M.S Door and glass fire door size 2100 mm x 900 mm or as per arch. |
| 212 | Supplying, installation, testing and commissioning of weather proof M.S door and glass fire door size 2100 mm x 900mm fabricated from 1.6mm thick M.S. sheets and M.S angle 40mmx40mmx6mm complete with glass, locking arrangements to accommodate the following: - |
| 213 | Supplying and fixing of fire brigade connection of cast iron body with gun metal male instantaneous inlet couplings complete with cap and chain as reqd. for suitable dia MS pipe connection conforming to IS 904 as required : |
| 214 | 2 way-100 mm dia M.S. Pipe |
| 215 | SUB HEAD - IV - (FIRE EXTINGUISHERS) |
| 216 | Supply and fixing of C02 type fire extinguisher 4.5 kg. capacity (ISI Marked IS : 2878 & TAC approved) complete with initial charge and wall bracket, along with supply of all materials and labour for proper completion of work. |
| 217 | Supply and fixing of fire extinguisher, ABC Type 6.00 kg. capacity (ISI Marked IS : 15683 & TAC approved) complete with initial charge and wall bracket, along with supply of all materials and labour for proper completion of work |
| 218 | Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable etc. as required. |
| 219 | Group - C |
| 220 | Wiring for group controled (looped) light point/ fan point/ exhaust fan point/ call bell point (without independent switch etc) with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable etc. as required. |
| 221 | Group - C |
| 222 | Wiring for twin control light point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit, 2 way modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable etc. as required. |
| 223 | Wiring for light/power plug with 2x4 sqmm FRLS PVC insulated copper conductor single core cable in suface / recessd medium class PVC conduit along with 1 no 4 sqmm FRLS insulated copper condutor alongwith 2 nos 4sqmm FRLS PVC insulated copper conductor single core cable for loop earthing as required . |
| 224 | Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required. |
| 225 | 2 X 1.5 sq. mm + 1 X 1.5 sq. mm earth wire |
| 226 | 2 X 2.5 sq. mm + 1 X 2.5 sq. mm earth wire |
| 227 | 2 X 6 sq. mm + 1 X 4 sq. mm earth wire |
| 228 | 4x10 sq. mm + 2x6 sq. mm earth wire |
| 229 | 4x16 sq. mm + 2x6 sq. mm earth wire |
| 230 | Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 3 pin 5/6 A modular socket outlet and 5/6 amps modular switch, connection etc. as required. |
| 231 | Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 6 pin 5/6 & 15/16 amps modular socket outlet and 15/16 amps modular switch, connection etc. as required. |
| 232 | Supply and fixing suitable size GI box with moduler plate and cover in front on surface or in recess including providing and fixing 2 nos 3 pin /6 amp moduler socket out let and 2 nos 5/6 a moduler switch all as directed in non residencial building |
| 233 | Supply and fixing suitable size GI box with moduler plate and cover in front on surface or in recess including providing and fixing 25 A moduler socket out let and 25 A moduler SP MCB including connection etc |
| 234 | Supplying and drying co-axial TV cable RG 6 grade 0.7 mm solid copper conductor PE insulated shielded with fine tinned copper braid and protected in existing conduit |
| 235 | Supply and lay PVC Conduit medium size of following sizes 25 mm dia |
| 236 | Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excludingmodular plate etc. as required. |
| 237 | TV antenna socket outlet |
| 238 | Supply, Fixing and testing complete Call Bell dind dong type 230 volt single phase . |
| 239 | Supplying and fixing two module stepped type electronic fan regulator on the existing modular plate switch box including connections but excluding modular plate etc. as required |
| 240 | Supply, Fixing and testing complete Call Bell dind dong type 230 volt single phase . |
| 241 | Supplying and fixing following module GI box with moduler base and pleate with plate cover |
| 242 | 1 or 2 modules |
| 243 | Installation , Testing and commissioning of wall /celing fitting of all sizes and shape containing up two GLS/ CFL/ LED lamp per fitting etc as required |
| 244 | Supplying and fixing modular blanking plate on the existing modular plate & switch box excluding modular plate as required |
| 245 | Supplying and drying of UTP 4 Pair Cat 6 Lan Cable |
| 246 | 1 run of cable |
| 247 | Supplying and fixing following way, horizontal type three pole and neutral, sheet steel, MCB distribution board, 415 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator) |
| 248 | 4 Way (4+12) Double door |
| 249 | 8 Way (4+24) Double door |
| 250 | Supplying and fixing following way, Surface / recceced mounting vertical type 415 Volt three pole and neutral, sheet steel, MCB distribution board, 415 V, on surface/ recess, duly powder painted, inclusive of 200 A tinned copper bus bar, neutral link, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator) |
| 251 | Supplying and fixing 5 amps to 32 amps rating, 240/415 volts, \\"C\\" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. |
| 252 | Single pole |
| 253 | Triple pole and neutral |
| 254 | Supply and fixing 63 Amp four pole (three Phase) |
| 255 | SUB-HEAD II - FANS & LIGHT FIXTURES: |
| 256 | Supplying, installation, Testing & Commissioning of LED surface mounted Batten light of following body material and construction as per IS : 10322 with driver (Replaceable) as per the requirement with Driver efficiency>85% ,Operating voltage AC 140-270 Volt, freq 50/60 hz, Operating temp range -15 deg to 40 deg centigrade, internal surge protection of 2.5 KV with Short & Open circuit protection ,THD < 10% , P. F.≥0.95, IP20, CRI >80, Flicker free, (flicker should be below 5 %), life time (LED,Driver & electrical circuitary), of minimum 50000 Burning Hours with , 70% of initial Lumen maintained till life ends, CCT 3000°K / 4000°K / 5700°K /6000°K/6500°K (As per ANSI Bin), SDCM(Standard Deviation Color Matching) <3, Maximum power consumption should not more than the specified rating and Fixture shall be of relevant BIS standard and trade mark certificate ( T.C.). Manufactures Word Mark/ Name Engraved/ Embossing/ Screen printing on housing. complete in all respect i/c connections with 1.5 sq mm FRLS, PVC insulated copper conductor single core cable and earthing etc. as required with Minimum 5 year OEM warranty. System lumen efficacy ≥105 <120 lm/Watt output . LM79 & LM80 Test report from NABL lab for all testing required for LED fixtures asper BIS shall be submitted. Shape size and CCT shall be as approved by Engineer-in-Charge as per requirement. (Thermal management: heat sink of aluminum housing such that LED junction temperature shall not rise above 90°C). Powder coated die cast / Extruded aluminium Body (Thickness ≥ 1.20 mm) |
| 257 | 20- 22 watt |
| 258 | Supplying, installation, Testing & Commissioning of LED Recessed/ surface Down lighter (Round/ square/ Rectangular) SMD type of following body material with PMMA and prismatic diffuser and construction as per IS :10322 with driver as per the requirement with Driver efficiency >85%, Operating voltage AC 140-270 Volt, frequency 50/60 hz, Operating temp range -15 deg to 40 deg centigrade, internal surge protection of 2.5 KV with Short & Open circuit protection ,THD < 10% , P. F.≥0.95, IP20, CRI >80 , UGR (Unified Glare Rating) < 19, Flicker free (flicker should be below 5%), life time (LED,Driver & electrical circuitary), of minimum 50000 Burning Hours with 70% of initial Lumen maintained till life ends , CCT 3000°K / 4000°K / 5700°K / 6000°K / 6500°K (As per ANSI Bin), SDCM (Standard Deviation Color Matching) <3, Maximum power consumption should not more than the specified rating and Fixture shall be confirming to relevant BIS standards and trade mark certificate (T.C.). Manufactures Word Mark/ Name Engraved/ Embossing/ Screen printing on housing Complete in all respect i/c connections with 1.5 sq mm FRLS, PVC insulated copper conductor single core cable and earthing etc. as required with Minimum 5 year OEM warranty. System lumen efficacy ≥105 and <120 lm/Watt output . LM79 & LM80 Test report from NABL lab for all testing required for LED fixtures as per BIS shall be submitted. Shape size and CCT shall be as approved by Engineer-in-Charge as per requirement. (Thermal management: heat sink of aluminum housing such that LED junction temperature shall not rise above 90°C) Powder coated die cast /Extruded aluminum Body including trim |
| 259 | 10 - 12 watt |
| 260 | Supplying of LED mirror light luminaire with 10W watt complete with electronic ballast, lamp including connection etc. complete as required |
| 261 | Supply, Installation, Testing and Commissioning of 1200 mm sweep, BEE 5 star rated, ceiling fan with Brush Less Direct Current (BLDC) Motor, class of insulation: B, 3 nos. blades, 30 cm long down rod, 2 nos. canopies, shackle kit, safety rope, copper winding, Power Factor not less than 0.9, Service Value (CMM/W) minimum 6.85, Air delivery minimum 215 CMM, 350 RPM (tolerance as per IS : 374- 2019), THD less than 10%, remote or electronic regulator unit for speed control and all remaining accessories including safety pin, nut bolts, washers, temperature rise=75 degree C (max.), insulation resistance more than 2 mega ohm, suitable for 230 V, 50 Hz, single phase AC Supply, earthing etc. complete as required. 1200 mm sweep ceiling fan |
| 262 | Supplying of following size exhaust fan complete with gravity louver and connection with 3 core flexible wire as required. |
| 263 | 300mm EXHAUST FAN with louvers |
| 264 | Supplying and fixing 20 A , 240V, SPN Industrial type socket out let with 2 Pole and earth , metal enclosed plug top along with 20 amp \\"C\\" curve SP MCB in sheet steel enclouser , on surface or in recess , with chained metal cover for the socket outlet and complete with connection testing and commissioning etc as required. |
| 265 | Supplying and installing following size of perforated Hot Dipped Galvanised Iron cable tray (Galvanisation thickness not less than 50 microns) with perforation not more than 17.5%, inconvenient sections, joined with connectors, suspended from the ceiling with G.I. suspenders including G.I. bolts & nuts, etc. as required. |
| 266 | 200 mm width X 50 mm depth X 1.6 mm thickness |
| 267 | Control Panel |
| 268 | Main Bldg LT Panel |
| 269 | Supply & Erection of factory fabricated & wired metal clad dust and vermin proof mounting, M.S Channel Base with botom and top cable entreis Electrical control panel with TPN MCCB's (four Pole 36 KA with thermal magnatic release) switches and instrument chamber etc. complete in all respect. The instrument chamber shall be separate and shall comprise of flush type/digital ammeter Voltmeter, Selector switches for ammeter and Voltmeter, instrument fuses current transformer etc. The Board shall have suitable capacity electrolytic aluminium busbars as per IS8623 insulated with heat shrink sleeving and mounted on non hygroscopic supports such as CMC/DMC support with deteachable side covers and shall be suitable for extension on the sides. The switches enty boxes shall be complete with suitable cable end boxes reverse. The job includes the grounting of the board as per directions of Engineer-in-charge. All out goings of 100 Amp. and above will be provided with Amp. Metre, curent transformer and selector switches etc. and insurment fuse The switch board shall be fabicated with CRCA sheet with a minimum thickness of 1.6mm/2mm. Cubical type switch board shall be of cat A & B only. |
| 270 | Incoming:- |
| 271 | 1 nos 400 amp MCCB 36 Ka having s/c. E/F and O/l relays |
| 272 | BUSBAR:- |
| 273 | Aluminium Bus Bar for suitable Capacity |
| 274 | OUT GOING :- |
| 275 | 3 nos 100 amp FP MCCB 25 ka including all type of protection relays |
| 276 | 4 Nos 125 Amp FP MCCB 25 Ka including all type of protection relays |
| 277 | Floor Panel for Ground, First Floor |
| 278 | Panel described as above |
| 279 | Incoming:- |
| 280 | 1 nos 125 amp FP MCCB 25 Ka havin s/c. E/F and O/l relays |
| 281 | BUSBAR:- |
| 282 | 1 set of suitable size BUS BAR of alluminim .alies |
| 283 | OUT GOING :- |
| 284 | 4 nos 63 amp FP MCCB |
| 285 | Panel described as above |
| 286 | Supply of Power Cable Solid Aluminium conductor up to 300 sqmm |
| 287 | 70 sqmm 3.5 core |
| 288 | 95 sqmm 3.5 core |
| 289 | 300 sqmm 3.5 core |
| 290 | Supply and making end termination with with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1100 volt grade |
| 291 | 6 sqmm 2 core |
| 292 | 16 sqmm 4 core |
| 293 | 95 sqmm 3.5 core |
| 294 | 300 sqmm 3.5 core |
| 295 | Laying of 1 no PVC insulated and PVC shethed / XLPE Power cable of 1.1 KV grade of following size in existing RCC/ HUME / Metal / Cable Tray as required and directed at site. |
| 296 | Up to 35 Sqmm |
| 297 | Above 35 Sqmm up to 95 Sqmm |
| 298 | Supply layin of DWC HDPE Pipe 200 mm dia |
| 299 | SUBHEAD: - V : EARTHING |
| 300 | Earthing with G.I. earth plate 600 mm x 600 mm x 6 mm thick including accessories , and providing masonry enclosure with cover plate having locking arrangement and watering pipe etc. (but with charcoal or coke and salt) as required. |
| 301 | Supplying and laying 25 mm X 5 mm G.I strip at 0.50 metre below ground as strip earth electrode, including connection/ terminating with G.I. nut, bolt, spring, washer etc. as required. (Jointing shall be done by overlapping and with 2 sets of G.I. nut bolt & spring washer spaced at 50mm) |
| 302 | Supplying and laying 25 mm X 5 mm GI strip in 40 mm gi pipe from earth electrode including connection with brass nut, bolt spring washer excavation and refilling etc . |
| 303 | Supplying and laying 25 mm X 5 mm GI strip on surface for connection etc. |
| 304 | Supplying and laying 6 SWG GI wire for loop earthing . |
| 305 | Supply and instalation properlyCable Trunking PVC 100 mm x 100 mm narrow sloted Tensile Strength:390 Kg/cm Tensile Strength:390 Kg/cm PVC FRLS Cable Ducts efficiently carries and protects wires and cables, which are manufactured from specially compounded, low smoke, flame retarded and high impact rigid polyvinyl chloride (RPVC) resin for DATA And Telephone cable arrengement fixed on wall verically / horizontly as required at site and directed by EIC including all neccesory fittings etc |
| 306 | Supplying, installation, testing and commissioning of solar water heating system with heat exchanger type including electric heater backup, make up water tank but without piping (@Rs 23920/100 Lit) Note:- 30 Lit for Each and hostal Cap is 50 Person |
| 307 | SUB HEAD - I - (SEWERAGE AND DRAINAGE) |
| 308 | Excavating trenches of required width for pipes, cables, etc including excavation for sockets, and dressing of sides, ramming of bottoms, depth upto 1.5 m, including getting out the excavated soil, and then returning the soil as required, in layers not exceeding 20 cm in depth, including consolidating each deposited layer by ramming, watering, etc. and disposing of surplus excavated soil as directed, within a lead of 50 m : |
| 309 | All kinds of soil |
| 310 | Pipes, cables etc. exceeding 80mm dia but not exceeding 300mm. |
| 311 | Open timbering in trenches including shuttering and shoring complete. (Measurement to be taken of the face area timbered) |
| 312 | Depth not exceeding 1.5 meter |
| 313 | Providing and laying cement concrete 1:5:10 (1 cement: 5 coarse sand : 10 graded stone aggregate 40mm nominal size) upto the haunches of pipes including bed concrete as per standard design |
| 314 | 150 mm. dia. RCC Pipes |
| 315 | 300 mm. dia. RCC Pipes |
| 316 | Providing and laying Non pressure NP 2 class (light duty) RCC pipe with collars jointed with stiff mixture of cement mortar in the proportion of 1:2 (1cement : 2 fine sand ) including testing of joints etc. complete. |
| 317 | 150 mm. dia. RCC Pipes |
| 318 | 300 mm. dia. RCC Pipes |
| 319 | Providing and fixing square-mouth S.W. gully trap SP-1 complete with C.I. grating, brick masonry chamber with water tight C.I. cover with frame of 300 x300 mm size (inside) the weight of cover to be not less than 4.50 kg and frame to be not less than 2.70 kg as per standard design |
| 320 | 150 x 100 mm size P type |
| 321 | With common burnt clay FPS (non modular) bricks of class designation 75 |
| 322 | Providing, laying and jointing glazed stoneware pipes class SP-1 with stiff mixture of cement mortar in the proportion of 1:1 (1 cement : 1 fine sand) including testing of joints etc. complete: |
| 323 | 100 mm diameter |
| 324 | Constructing brick masonry manhole in cement mortar 1:4 (1 cement :4 coarse sand) RCC top slab with 1:2:4 mix (1 cement :2 coarse sand :4 graded stone aggregate 20mm nominal size), foundation concrete 1:4:8 mix (1 cement :4 coarse sand :8 graded stone aggregate 40mm nominal size) inside plastering 12mm thick with cement mortar 1:3 (1 cement :3 coarse sand) finished with floating coat fo neat cement and making channels in cement concrete 1:2:4 (1 cement :2 coarse sand :4 graded stone aggregate 20mm nminal size) finished with a floating coat of neat cement complete as per standard design. |
| 325 | Inside size 90x80cms and 45cms deep including CI cover with frame (light duty) 455x610mm internal diamensions total weight of cover and frame to be not less than 38 kg (weight of cover 23 kg and weight of frame 15kg). |
| 326 | With common burnt clay FPS (non modular) bricks of class designation 7.5 |
| 327 | Inside size 120x90 cm and 90 cm deep including C.I. cover with frame (medium duty) 500 mm internal diameter, total weight of cover and frame to be not less than 116 kg (weight of cover 58 kg and weight of frame 58 kg) :- |
| 328 | With common burnt clay F.P.S. (non modular) bricks of class designation 7.5 |
| 329 | Extra for depth for manholes: |
| 330 | Size 90x80cm |
| 331 | With common burnt clay FPS (non modular) bricks of class designation 7.5 |
| 332 | Providing orange colour safety foot rests of minimum 6 mm thick plastic encapsulated as per IS:10910 on 12 mm dia steel bar conforming to IS:1786 having minimum cross section as 23 mm x 25 mm and over all minimum length 263 mm and width as 165 mm with minimum 112 mm space between protruded legs having 2 mm thread on top surface by ribbing or chequering besides necessary and adequate anchoring projections on tail length on 138 mm as per standard drawing and suitable to with stand the bend test and chemical resistance test as per specifications and having manufacture's permanent identification mark to be visible even after fixing, including fixing in manholes with 30x20x15 cm cement concrete block 1:3:6 (1 cement : 3 coarse sand : 6 graded stone aggregate 20 mm nominal size) complete as per design. |
| 333 | SUB HEAD - II - EXTERNAL WATER SUPPLY |
| 334 | Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes, having thermal stability for hot & cold water supply including all CPVC plain & brass threaded fittings This includes jointing of pipes & fittings with one step CPVC solvent cement, trenching, refilling & testing of joints complete as per direction of Engineer in Charge. |
| 335 | 80 mm dia nominal bore |
| 336 | Supplying, fixing, testing and commissioning of butterfly valve of PN 1.6 rating with bronze/gunmetal seat duly ISI marked complete with nuts, bolts, washers, gaskets conforming to IS 13095 of following sizes as required:- |
| 337 | 50 mm dia |
| 338 | 80 mm dia |
| 339 | Making connection of G.I. distribution branch with G.I. main of following sizes by providing and fixing tee, including cutting and threading the pipe etc. complete : |
| 340 | 25 to 40 mm nominal bore |
| 341 | 50 to 80 mm nominal bore |
| 342 | Constructing masonry Chamber 60 x 60 x 75 cm, inside with 75 class designation brick work in cement mortar 1:4 (1 cement : 4 fine sand) for sluice valve, with C.I. surface box 100mm top diameter, 160 mm bottom diameter and180 mm deep (inside) with chain lid and RCC top slab 1:2:4 mix (1 cement : 2 coarse sand : 4 graded stone aggregate 20mm nominal size) necessary excavation foundation concrete 1:5:10 (1 cement : 5 fine sand : 10 graded stone aggregate 40 mm nominal size) and inside plastering with cement mortar 1:3 (1 cement :3 coarse sand) 12 mm thick finished with a floating coat of neat cement complete as per standard design. |
| 343 | With F.P.S. bricks |
| 344 | RAIN WATER HARVESTING WITH |
| 345 | RECHARGE PITS |
| 346 | Earth work in exacavation in trenches for foundations and for pipes cables etc. in ordinary soil(loam clay or sand) including lift upto 1.5 m and dressing of sides and ramming of bottom sand disposal of surplus excavated earth as directed by the Engineer i/c with in a lead of 50m. |
| 347 | In all kind of soil upto 1.5m depth |
| 348 | In all kind of soil upto 1.5m to 3.0m. depth |
| 349 | In all kind of soil upto 3.0m to 4.5m. depth |
| 350 | R.C.C. work in Slab |
| 351 | 15 mm cement plaster on rough side of single or half brick wall of mix : 1:4 (1 cement: 4 coarse sand) |
| 352 | With 20x20mm square bar |
| 353 | M.D. -10- Circular shape 500mm internal diameter |
| 354 | Drilling of 300mm dia bore hole manually. |
| 355 | 150 mm nominal size dia |
| 356 | Supplying, filling, spreading & leveling gravels of size range 5 mm to 10 mm, in the recharge pit, over the existing layer of boulders, inrequired thickness, for all leads & lifts, all complete as per directionof Engineer-in-charge. |
| 357 | Gravel packing in tubewell construction in accordance with IS: 4097, including providing gravel fine/ medium/ coarse, in required grading & sizes as per actual requirement, all complete as per direction of Engineer-in-charge. |
| 358 | 15 mm cement plaster on rough side of single or half brick wall of mix : 1:4 (1 cement: 4 coarse sand) |
| 359 | 150 mm. dia. |
| 360 | Constructing masonry Chamber 60x60x75 cm inside, in brick work in cement mortar 1:4 (1 cement : 4 coarse sand) for sluice valve, with C.I. surface box 100mm top diameter, 160 mm bottom diameter and 180 mm deep ( inside) with chained lid and RCC top slab 1:2:4 mix (1 cement : 2 coarse sand : 4 graded stone aggregate 20mm nominal size ) , i/c necessary excavation, foundation concrete 1:5:10 (1 cement : 5 fine sand : 10 graded stone aggregate 40 mm nominal size) and inside plastering with cement mortar 1:3 (1 cement : 3 coarse sand) 12 mm thick, finished with a floating coat of neat cementcomplete as per standard design :With common burnt clay F.P.S.(non modular) bricks of .class designation 7.5 |
| 361 | Suspended floors, roofs, landings, balconies and access platform |
| 362 | Excavation of foundation in ordinary soil (loam clay or sand) including lift upto 1.50 meter and lead upto 30 meter and including filling, watering and ramming of excavated earth into the trenches or into the space between the building and sides of foundation trenches or into the plinth and removal and disposal of sur-plus earth as directed by the Engineer incharge up to a distance of 30 meters from the foundation trenches. |
| 363 | Providing and laying in position ready mixed or site batched design mix cementconcrete for plain cement concrete work; using coarse aggregate and fine aggregate derived from natural sources, Portland Pozzolana/ Ordinary Portland /Portland Slag cement, admixtures in recommended proportions as per IS: 9103 to accelerate / retard setting of concrete, to improve durability and workability without impairing strength; including pumping of concrete to site of laying, curing, carriage for all leads; but excluding the cost of centering, shuttering and finishing as per direction of the engineer-in-charge; for the following grades of concrete. Note: Extra cement up to 10% of the minimum specified cement content in design mix shall be payable separately. In case the cement content in design mix is more than 110% of the minimum specified cementcontent, the contractor shall have discretion to either re-design the All works upto plinth level :mix or bear the cost of extra cement. Concrete of M10 grade with minimum cement content of 220 kg /cum |
| 364 | 40mm thick 1:2:4 plain cement concrete floor (1 cement :2 coarse sand :4 graded stone aggregate 12-20mm nominal size laid in one layer neat cement. |
| 365 | INTERLOCKING |
| 366 | Providing and laying in position ready mixed or site batched design mix cementconcrete for plain cement concrete work; using coarse aggregate and fine aggregate derived from natural sources, Portland Pozzolana/Ordinary Portland /Portland Slag cement, admixtures in recommended proportions as per IS: 9103 to accelerate / retard setting of concrete, to improve durability and workability without impairing strength; including pumping of concrete to site of laying, curing, carriage for all leads; but excluding the cost of centering, shuttering and finishing as per direction of the engineer-in-charge; for the following grades of concrete.Concrete of M10 grade with minimum cementcontent of 220 kg /cum |
| 367 | Providing and laying factory made chamfered edge Cement Concrete paver blocks in footpath, parks, lawns, drive ways or light traffic parking etc, of required strength, thickness & size/ shape, made by table vibratory method using PU mould, laid in required colour & pattern over 50 mm thick compacted bed of sand, compacting and proper embedding/laying of inter locking paver blocks into the sand bedding layer through vibratory compaction by using plate vibrator, filling the joints with sand and cutting of paver blocks as per required size and pattern, finishing and sweeping extra sand. complete all as per direction of Engineer-in-Charge. 80 mm thick C.C. paver block of M-35 grade with approved colour design and pattern. |
| 368 | SEPTIC TANK & SOAK PIT |
| 369 | Providing and laying of cement concrete in base excluding the cost of centring and shuttering by 1:2:4 (1 cement : 2 coarse sand : 4 gradded stone aggregae 40mm nominal size) |
| 370 | Reinforcement cement concrete work in RCC culvert slab with 1:1.5:3 (1 cement : 1.5 coarse sand and 3 gradded stone aggregate of 20 mm nominal size) excluding centering and shuttering and reinforcement. |
| 371 | P/F Mild steel or iron in plain work such as reinforced concrete or reinforced, brick work (when not included in over all rates ) wrought to required shape as necessary including bending for proper completion of the work and including supply of steel its wastage bend hooks and authorised over lapping shall be measured upto floor two level. |
| 372 | 12mm cement plaster on rough side of mix 1:3 (1 cement : 3 coarse sand) |
| 373 | Providing M.S. foot rest including fixing with 20x20x10 cm. cement concrete block 1:3:6 (1 cement : 3 coarse sand : 6 gradded aggregate of nominal size 20mm ) as per standard design with 20x20mm sq bars. |
| 374 | Providing and fixing C.I. tee at the inlet and outlet of septic tank. |
| 375 | Providing & fixing 75mm dia vent pipes. |
| 376 | Providing & fixing of 75mm dia cast iron terminal guard. |
| 377 | Providing and fixing in position precast RCC manhole cover and frame of required shape and approved quality. |
| 378 | M.D. -10- Circular shape 500mm internal diameter |
| 379 | M.D. -2.5- Circular shape 450mm internal diameter |
| 380 | SOAKPIT |
| 381 | Excavation in Foundation in ordinary soil (Loam clay, or sand) including lift upto 1.5 metre (5 fts.) and lead upto 30m (100 fts) & including filling, watering and ramming of excavated earth into the trenches or into the space between the building and the sides of foundation trenches or into the plinth and removal and disposal of surplus earth as directed by the Engineer-in-charge upto a distance of 30 m. (100 fts) from the foundation trenches. (Rate is including Royality). |
| 382 | 1:1.5:3 (1 cement : 1.5 coarse sand (zone-III) derived from natural sources : 3 graded stone aggregate 20 mm nominal size derived from natural sources) |
| 383 | Providing & fixing 100mm dia Drain pipes. |
| 384 | Providing & fixing of 75mm dia cast iron terminal guard. |
| 385 | Supplying and stacking at site. |
| 386 | GST Extra as applicable Please Enable Macros to View BoQ information |
| SR No | FileName | File Description |
| 1 | Click here to download tender document | Tender Documents |
| 2 | Click here to download tender document | Tender Documents |
| 3 | Click here to download tender document | Tender Documents |
| 4 | Click here to download tender document | Tender Documents |
Copyright © 2026 · All Rights Reserved. Terms of Usage | Privacy Policy
For Tender Information Services Visit : TenderDetail