| 1 | Part 1 Main line cable from substation to Ramanujan,Tagore,Annexe,New Hostel SECTION 1 : Supply & Installation A. From 33KV main panel to Ramanujan & Annex, Tagore and New hostel Panel. |
| 2 | Supply and Laying of PVC insulated 3.5C x 300 sq.mm (XLPE) armoured, Cable.1.1Kv grade Laying of the cable will be minimum 600 mm below from the G.L and protection of the cable with sand and bricks etc.( work includes necessary road cutting and back filling as per site requirement). Makes : KEI/ POLYCAB/ FINOLEX ( only 1 No. cable laying in one route) |
| 3 | Supply and Laying of PVC insulated 3.5C x 300 sq.mm (XLPE) armoured, Cable.1.1Kv grade Laying of the cable will be minimum 600 mm below from the G.L and protection of the cable with sand and bricks etc.( work includes necessary road cutting and back filling as per site requirement). Makes : KEI/ POLYCAB/ FINOLEX ( 3/4 Nos. cable laying in one route) |
| 4 | Supply and Laying of PVC insulated 3.5C x 300 sq.mm (XLPE) armoured, Cable.1.1Kv grade Laying of the cable will be minimum 600 mm below from the G.L and protection of the cable with sand and bricks etc.( work includes necessary road cutting and back filling as per site requirement). Makes : KEI/ POLYCAB/ FINOLEX ( 2/3 Nos. cable laying in one route) |
| 5 | Supply and Laying of PVC insulated 3.5C x 300 sq.mm (XLPE) armoured, Cable.1.1Kv grade . Cable laying in the existing cable trench or Hume pipe etc.Makes : KEI/ POLYCAB/ FINOLEX |
| 6 | Supply & installation State through joint of 3.5C X 400/300 sq mm (XLPE) cable including Jointing Kit ( Compound) make-3M and AL lugs, socket etc. |
| 7 | End Termination of 3.5C X 400/300 sq mm (XLPE) cable including Gland ( Double) make-comet and AL lugs, socket etc. |
| 8 | Supply , Installation , Testing & Commissioning of weather proof outdoor type Feeder pillar Aluminium painted made of 12 SWG MS powder coated with 2 nos. hinge type biparting door (at front and back side of feeder) The feeder pillar with dimension (Height – 1500 mm x W – 1250 mm x D – 800 mm) should consist of the following :- Fuse make- L&T/Havels/Siemens/Legrand. a) Bakelite sheet,20-25 mm thickness in adequate size = 1 set b) 50 mm x 6 mm, 500 A copper bus bar = 06 nos. c) 40 mm x 3 mm, 300 A copper bus bar = 02 nos. d) Porcelain fuse 200A ( KKRT) = 12 nos & Porcelant fuse 100A =6 nos e) Porcelain fuse 320A ( KKRT) = 06 nos f) Iron angle frame with 6 nos. leg = 1 set. g) 40 mm x 6 mm copper busbar link for porcelain fuse h) Fabrication & painting of the feeder Pillar. i) Danger plate & name plate & suitable base plate. j) Phase Indicating lamp LED both In side . Installation of above feeder box with proper brick foundation & brick soiling from front side as well as back side of the feeder box and completely plastering. Job also includes making 2 nos. platform of PCC with brick flat soling each of area 450 mm x 1300 mm on both sides of the feeder piller (front & back side) |
| 9 | Earthing with GI earth pipe 4.5 Mtr. Long 40 mm dia including accessories, and providing masonry enclosure with cover plate having locking arrangement and etc. with charcol/coke and salt as required. Including Earthing Strip 50X6 as required. |
| 10 | Any miscellaneous work not covered in present schedule but is required to be done on a as and when basis will be executed by the contractor. Work value will be ascertained based on rate analysis / original bill submission. 10% profit will be paid on original bil value submitted. The work will be done as per direction of Engineer- In- Charge. |
| 11 | Part 2 Main line cable from LVH backside to MDC & LVH panel room SECTION 1 : Supply & Installation A. From LVH dining back side panel to MDC & LVH Panel room. |
| 12 | Supply and Laying of PVC insulated 3.5C x 400 sq.mm (XLPE) armoured, Cable.1.1Kv grade Laying of the cable will be minimum 600 mm below from the G.L and protection of the cable with sand and bricks etc.( work includes necessary road cutting and back filling as per site requirement). Makes : KEI/ POLYCAB/ FINOLEX ( only 1 No. cable laying in one route) |
| 13 | Supply and Laying of PVC insulated 3.5C x 400 sq.mm (XLPE) armoured, Cable.1.1Kv grade Laying of the cable will be minimum 600 mm below from the G.L and protection of the cable with sand and bricks etc.( work includes necessary road cutting and back filling as per site requirement). Makes : KEI/ POLYCAB/ FINOLEX ( 3/4 Nos. cable laying in one route) |
| 14 | Supply and Laying of PVC insulated 3.5C x 400 sq.mm (XLPE) armoured, Cable.1.1Kv grade Laying of the cable will be minimum 600 mm below from the G.L and protection of the cable with sand and bricks etc.( work includes necessary road cutting and back filling as per site requirement). Makes : KEI/ POLYCAB/ FINOLEX ( 2/3 Nos. cable laying in one route) |
| 15 | Supply and Laying of PVC insulated 3.5C x 400 sq.mm (XLPE) armoured, Cable.1.1Kv grade . Cable laying in the existing cable trench or Hume pipe etc.Makes : KEI/ POLYCAB/ FINOLEX |
| 16 | Supply and Laying of PVC insulated 3.5C x 300 sq.mm (XLPE) armoured, Cable.1.1Kv grade Laying of the cable will be minimum 600 mm below from the G.L and protection of the cable with sand and bricks etc.( work includes necessary road cutting and back filling as per site requirement). Makes : KEI/ POLYCAB/ FINOLEX ( only 1 No. cable laying in one route) |
| 17 | Supply and Laying of PVC insulated 3.5C x 300 sq.mm (XLPE) armoured, Cable.1.1Kv grade Laying of the cable will be minimum 600 mm below from the G.L and protection of the cable with sand and bricks etc.( work includes necessary road cutting and back filling as per site requirement). Makes : KEI/ POLYCAB/ FINOLEX ( 3/4 Nos. cable laying in one route) |
| 18 | Supply and Laying of PVC insulated 3.5C x 300 sq.mm (XLPE) armoured, Cable.1.1Kv grade Laying of the cable will be minimum 600 mm below from the G.L and protection of the cable with sand and bricks etc.( work includes necessary road cutting and back filling as per site requirement). Makes : KEI/ POLYCAB/ FINOLEX ( 2/3 Nos. cable laying in one route) |
| 19 | Supply and Laying of PVC insulated 3.5C x 300 sq.mm (XLPE) armoured, Cable.1.1Kv grade . Cable laying in the existing cable trench or Hume pipe etc.Makes : KEI/ POLYCAB/ FINOLEX |
| 20 | Supply & installation State through joint of 3.5C X 400/300 sq mm (XLPE) cable including Jointing Kit ( Compound) make-3M and AL lugs, socket etc. |
| 21 | End Termination of 3.5C X 400/300 sq mm (XLPE) cable including Gland ( Double) make-comet and AL lugs, socket etc. |
| 22 | (For LVH Dining back panel ) Supply , Installation , Testing & Commissioning of weather proof outdoor type, Dauble door type Panel Aluminium painted made of 12 SWG MS powder coated . The feeder pillar with dimension (Height – 1500 mm x W – 1250 mm x D – 800 mm) should consist of the following :- 1) 1250 Amp. MCCB--1 no, 2) 6300 Amp. MCCB--1 no,3) 400 Amp. MCCB--4 no,4) 250 Amp. MCCB--1 no, L&T/Schnider/Siemens/Legrand. b) 1500 Amp Al bus bar = 03 nos. c) 1000 A Al bus bar = 01 nos.for Nutral d) 50mmX6mm GI Earthing Bus bar =2 nos f) Iron angle frame with 6 nos. leg = 1 set. i) Danger plate & name plate & suitable base plate. j) Phase Indicating lamp LED both In side . Installation of above Panel with proper brick foundation & brick soiling from front side as well as back side of the feeder box and completely plastering. Job also includes making 2 nos. platform of PCC with brick flat soling each of area 1000 mm x 2000 mm on both sides of the Panel (front & back side) L1 Vender should be take approval of the panel drawing from the Engineering -Electrical. |
| 23 | (For MDC- A2 power cable ) Supply , Installation , Testing & Commissioning of weather proof outdoor type Feeder pillar Aluminium painted made of 12 SWG MS powder coated with 2 nos. hinge type biparting door (at front and back side of feeder) The feeder pillar with dimension (Height – 1500 mm x W – 1250 mm x D – 800 mm) should consist of the following :- Fuse make- L&T/Havels/Siemens/Legrand. a) Bakelite sheet,20-25 mm thickness in adequate size = 1 set b) 50 mm x 6 mm, 600 A copper bus bar = 06 nos. c) 40 mm x 3 mm, 300 A copper bus bar = 02 nos. d) Porcelain fuse 200A ( KKRT) = 18 nos e) Porcelain fuse 400A ( KKRT) = 06 nos f) Iron angle frame with 6 nos. leg = 1 set. g) 40 mm x 6 mm copper busbar link for porcelain fuse h) Fabrication & painting of the feeder Pillar. i) Danger plate & name plate & suitable base plate. j) Phase Indicating lamp LED both In side . Installation of above feeder box with proper brick foundation & brick soiling from front side as well as back side of the feeder box and completely plastering. Job also includes making 2 nos. platform of PCC with brick flat soling each of area 450 mm x 1300 mm on both sides of the feeder piller (front & back side) |
| 24 | ( For MDC A1 &A3 Power Cable) Supply, Installation, Testing & Commissioning of weather proof out door type Feeder Pillar Aluminum painted made of 12 SWG MS Sheet double hinged biparting door at front and back side feeder box. The feeder pillar with dimension (Height-1250mm x W-950 mm x D-600mm) should consist of the following:- a)Porcelain fuse 400A, Havells make - 3nos b)Porcelain fuse 200A, Havells make - 12 Nos. c)Porcelain fuse 100A, Havells make - 3 Nos. d)50 x 6mm 400A copper Bus Bar - 4 Nos. e)20mm thick adequate size Bakelite Plate -1 No f) Fabrication & Painting of the feeder box -1 No. g) Iron angle frame frame with 4-Nos. legs-1Set. h) Danger plate & suitable size base plate-1 Set. Job include:- Installation the said feeder piller on concreat /brick foundation. The foundation should be plastering and painted with black paint. |
| 25 | Earthing with GI earth pipe 4.5 Mtr. Long 40 mm dia including accessories, and providing masonry enclosure with cover plate having locking arrangement and etc. with charcol/coke and salt as required. Including Earthing Strip 50X6 as required. |
| 26 | Any miscellaneous work not covered in present schedule but is required to be done on a as and when basis will be executed by the contractor. Work value will be ascertained based on rate analysis / original bill submission. 10% profit will be paid on original bil value submitted. The work will be done as per direction of Engineer- In- Charge. |
| 27 | Part 3 Internal wiring from feeder to individual rooms of Ramanujan,Tagore,Annexe,NHRamanujan Hostel |
| 28 | Supply of 3.5 c x 120 sq.mm PVCA AL Armored cablle from Power feeder box to Distribution Panel . Make.-Gloster/Polycab/Havells. |
| 29 | Laying of the above cable as a direct burial with brick protection as per electrical rules. |
| 30 | Laying of the above cable on the wall with proper saddling |
| 31 | Providing distribution poder coated power panel in 16 swg smoke grey colour size in adequate(1000Wx1100Hx300 D mm) with necessary materials are.-1) 250 A TPN SFU-1 no. Havells/L&T 2) 250 A Copper Bus bar-4 nos. 3) 125 A 4-pole MCCB-4nos. L&T 4) Voltmeter -1 no. 5)volt meter selector sw.-1 no and internal connectivity by 1.5/10 sq. mm copper wire. and cable end box. |
| 32 | Supply and fixing of 3-ph 150 A copper Bus bar chember with enclosure and necessary connection complete. |
| 33 | Supply of 3.5 core 35 sq. mm PVC AL Armored cable from distribution panl to BUS Bar chamber. |
| 34 | Lay of the above cable on the wall with proper saddling. |
| 35 | Distribution wiring by 2 x 6 sq. mm + 1 x 1.5 sq.mm copper wire with PVC pipe and necessary connection complete. Make Poly cab/ Finolex. |
| 36 | Supply and fixing of 20 A DP MCB with pvc enclosure and necessary connection complete. Make.-Havells /L&t |
| 37 | Individual AC power point wiring by 2 x 4 + 1 x 1.0 sq. mm copper wire with pvc pipe and necessary connection complete.Make.-Polycab/Finolex. |
| 38 | Supply and fixing of PVC Connector box for the wire termination. |
| 39 | Supply and fixing of PVC/wooden box with bakelite cover in 16 A SP MCB-1no ,16 A socket -1no and necessary connection complete. Make.-Presto/Anchor/Havells/L&T. |
| 40 | Preparation of earthing with GI Pipe sal charcoal GI Strip as per electrical rule. |
| 41 | Earthing attachment by nacked copper wire by 14 swg in guage |
| 42 | Preparation of copper Gland, end termination , socketing for different sizes of cable /wire. |
| 43 | Road cutting for the GI Pipe for cable protection outside of the hostel. |
| 44 | 2.5 inches dia GI Pipe for cable protection Make.-Tata/Jindal. |
| 45 | Miscelllaneous works that is not included in schedule but is required to be done will be ascertained on basis of Original bill / Rate analaysis / market rate. 10% profit will be given on original bill |
| 46 | Annexe Hostel |
| 47 | Supplly of 3.5 c x 120 sq.mm PVCA AL Armored cablle from Power feeder box to Distribution Panel . Make.-Gloster/Polycab/Havells. |
| 48 | Laying of the above cable as a direct burial with brick protection as per electrical rules. |
| 49 | Laying of the above cable on the wall with proper saddling |
| 50 | Providing distribution poder coated power panel in 16 swg smoke grey colour size in adequate((1000Wx1100Hx300 D mm) with necessary materials are.-1) 250 A TPN SFU-1 no. Havells/L&T 2) 250 A Copper Bus bar-4 nos. 3) 125 A 4-pole MCCB-4nos. L&T 4) Voltmeter -1 no. 5)volt meter selector sw.-1 no and internal connectivity by 1.5/10 sq. mm copper wire. and cable end box. |
| 51 | Supply & Fixning feeder piller. |
| 52 | Supply & Fixning feeder piller for NTB. |
| 53 | Supply and fixing of 3-ph 150 A copper Bus bar chember with enclosure and necessary connection complete. |
| 54 | Supply of 3.5 c x 35 sq. mm PVC AL Armored cable from distribution panl to BUS Bar chamber. |
| 55 | Lay of the above cable on the wall with proper saddling. |
| 56 | Distribution wiring by 2 x 6 sq. mm + 1 x 1.5 sq.mm copper wire with PVC pipe and necessary connection complete. Make Poly cab/ Finolex. |
| 57 | Supply and fixing of 20 A DP MCB with pvc enclosure and necessary connection complete. Make.-Havells /L&T |
| 58 | Individual AC power point wiring by 2 x 4 + 1 x 1.0 sq. mm copper wire with pvc pipe and necessary connection complete. Make.-Polycab/Finolex. |
| 59 | Supply and fixing of PVC Connector box for the wire termination. |
| 60 | Supply and fixing of PVC/wooden box with bakelite cover in 16 A SP MCB-1no ,16 A socket -1no and necessary connection complete. Make.-Presto/Anchor/Havells/L&T. |
| 61 | Preparation of earthing with GI Pipe sal charcoal GI Strip as per electrical rule. |
| 62 | Earthing attachment by nacked copper wire by 14 swg in guage |
| 63 | Preparation of copper Gland, end termination , socketing for different sizes of cable /wire. |
| 64 | Supply and laying 2.5 inches dia GI Pipe for cable protection Make.-Tata/Jindal. |
| 65 | Miscelllaneous works that is not included in schedule but is required to be done will be ascertained on basis of Original bill / Rtae nalaysis / market rate. 10% profit will be given on original bill |
| 66 | Tagore Hostel |
| 67 | Supplly of 3.5 c x 120 sq.mm PVCA AL Armored cablle from Power feeder box to Distribution Panel . Make.-Gloster/Polycab/Havells. |
| 68 | Laying of the above cable as a direct burial with brick protection as per electrical rules. |
| 69 | Laying of the above cable on the wall with proper saddling |
| 70 | Supply & Fixning feeder piller for cable connection. |
| 71 | Providing distribution poder coated power panel in 16 swg smoke grey colour size in adequate (1200WX1100HX300D mm) with necessary materials are.-1) 250 A TPN SFU-1 no. Havells/L&T 2) 250 A Copper Bus bar-4 nos. 3) 125 A 4-pole MCCB-7nos. L&T 4) Voltmeter -1 no. 5)volt meter selector sw.-1 no and internal connectivity by 1.5/10 sq. mm copper wire. and cable end box. |
| 72 | Supply and fixing of 3-ph 150 A copper Bus bar chember with enclosure and necessary connection complete. |
| 73 | Supply of 3.5 c x 35 sq. mm PVC AL Armored cable from distribution panl to BUS Bar chamber. |
| 74 | Lay of the above cable on the wall with proper saddling. |
| 75 | Distribution wiring by 2x6 sq. mm + 1x1.5 sq.mm copper wire with PVC pipe and necessary connection complete. Make Poly cab/ Finolex. |
| 76 | Supply and fixing of 20 A DP MCB with pvc enclosure and necessary connection complete. Make.-Havells /L&t |
| 77 | Individual AC power point wiring by 2 x 4 +1 x 1.0 sq. mm copper wire with pvc pipe and necessary connection complete. Make.-Polycab/Finolex. |
| 78 | Supply and fixing of PVC Connector box for the wire termination. |
| 79 | Supply and fixing of PVC/wooden box with bakelite cover in 16 A SP MCB-1no ,16 A socket -1no and necessary connection complete. Make.-Presto/Anchor/Havells/L&T. |
| 80 | Preparation of earthing with GI Pipe sal charcoal GI Strip as per electrical rule. |
| 81 | Earthing attachment by nacked copper wire by 14 swg in guage |
| 82 | Preparation of copper Gland, end termination , socketing for different sizes of cable /wire. |
| 83 | Supply and laying 2.5 inches dia GI Pipe for cable protection Make.-Tata/Jindal. |
| 84 | Miscelllaneous works that is not included in schedule but is required to be done will be ascertained on basis of Original bill / Rtae nalaysis / market rate. 10% profit will be given on original bill |
| 85 | New Hostel |
| 86 | Supplly of 3.5 c x 120 sq.mm PVCA AL Armored cablle from Power feeder box to Distribution Panel . Make.-KEI/Polycab/Havells. |
| 87 | Laying of the above cable as a direct burial with brick protection as per electrical rules. |
| 88 | Laying of the above cable on the wall with proper saddling |
| 89 | Providing distribution poder coated power panel in 16 swg smoke grey colour size in adequate(1200WX1500HX300D mm) with necessary materials are.-1) 400 A TPN SFU-1 no. Havells/L&T 2) 3000 A Copper Bus bar-4 nos. 3) 125 A 4-pole MCCB-6nos. L&T 4) Voltmeter -1 no. 5)volt meter selector sw.-1 no and internal connectivity by 1.5/10 sq. mm copper wire. and cable end box. |
| 90 | Shed preparation for the above panel outside of the building with AL Coated tin and MS pipe. |
| 91 | Supply and fixing of 3-ph 150 A copper Bus bar chember with enclosure and necessary connection complete. |
| 92 | Supply of 3.5 c x50 sq. mm PVC AL Armored cable from distribution panl to BUS Bar chamber. |
| 93 | Supply of 3.5 c x 35 sq. mm PVC AL Armored cable from distribution panl to BUS Bar chamber. |
| 94 | Lay of the above cable on the wall with proper saddling. |
| 95 | Distribution wiring by 2 x 6 sq. mm + 1 x 1.5 sq.mm copper wire with PVC pipe and necessary connection complete. Make Poly cab/ Finolex. |
| 96 | Supply and fixing of 20 A DP MCB with pvc enclosure and necessary connection complete. Make.-Havells /L&T |
| 97 | Individual AC power point wiring by 2x4 +1x1.0 sq. mm copper wire with pvc pipe and necessary connection complete. Make.-Polycab/Finolex. |
| 98 | Supply and fixing of PVC Connector box for the wire termination. |
| 99 | Supply and fixing of PVC/wooden box with bakelite cover in 16 A SP MCB-1no ,16 A socket -1no and necessary connection complete. Make.-Presto/Anchor/Havells/L&T. |
| 100 | Preparation of earthing with GI Pipe sal charcoal GI Strip as per electrical rule. |
| 101 | Earthing attachment by nacked copper wire by 14 swg in guage |
| 102 | Preparation of copper Gland, end termination , socketing for different sizes of cable /wire. |
| 103 | Supply and laying 2.5 inches dia GI Pipe for cable protection Make.-Tata/Jindal. |
| 104 | Miscelllaneous works that is not included in schedule but is required to be done will be ascertained on basis of Original bill / Rtae nalaysis / market rate. 10% profit will be given on original bill |
| 105 | Part 4 Internal wiring from feeder to individual rooms of LVHLAKE VIEW HOSTEL |
| 106 | Supply of 3.5C x 35 sq.mm (XLPE)Armored cablle Make- Finolex/ Polycab/ KEI |
| 107 | Laying of the above cable on the wall with proper saddling. |
| 108 | Supplly of 3.5 core 120 sq.mm PVC AL Armored cablle from Power feeder box to Distribution Panel . Make.-Finolex/ Polycab/ KEI |
| 109 | Laying of the above cable on the wall with proper saddling |
| 110 | Providing distribution poder coated power panel in 16 swg smoke grey colour size in adequate(1450Wx1250Hx600 D mm) with necessary materials are.-1) 630 A Main Switch-1. 2) 740 A Copper Bus bar ( 60X3 mm)-4 nos. 3) 150 A 4-pole MCCB-5nos. 4) 100A 4 pole MCCB - 2nos. 5)Voltmeter -1 no. 6)volt meter selector sw.-1 no 7) Amp. Meter-1 no and internal connectivity by 6/10 sq. mm copper wire. and cable end box. Make of MCCB & MCB-Schnider/L&T/ABB. |
| 111 | Supply and fixing of 3-ph 150 A copper Bus bar chember with enclosure and necessary connection complete. |
| 112 | Distribution wiring by 2x2.5 sq. mm + 1x1.0 sq.mm copper wire with PVC Casing (M-Pesto plus)and necessary connection complete. Make of wire Poly cab/ Finolex/ KEI. |
| 113 | 6 Way TPN DB Double door, including 63A TPN MCB-1 no and 18 nos 20A SP MCB. and necessary connection complete. Make.-ABB/Schnider /L&t/Legrand |
| 114 | Individual AC power point wiring by 2x4 +1x1.0 sq. mm copper wire with pvc pipe and necessary connection complete.Make.-Polycab/Finolex/KEI. |
| 115 | Supply and fixing of MCB protected (16 A SP MCB-1no ,16 A socket -1no & 16 A Top)Combo power Box and necessary connection complete. Make.-Legrand/Anchor/Havells/L&T/ Schneider. |
| 116 | Preparation of earthing with GI Pipe salt charcoal GI Strip as per electrical rule. |
| 117 | Preparation of copper Gland, end termination , socketing for different sizes of cable /wire. |
| 118 | Road cutting for the GI Pipe for cable protection outside of the hostel. |
| 119 | 2.5 inches dia GI Pipe for cable protection Make.-Tata/Jindal. |
| 120 | Any miscellaneous work not covered in present schedule but is required to be done on a as and when basis will be executed by the contractor. Work value will be ascertained based on rate analysis / original bill submission. 10% profit will be paid on original bil value submitted. The work will be done as per direction of Engineer- In- Charge. Please Enable Macros to View BoQ information |