| 1 | Excavation in trenches not exceeding 1.5m wide and not exceeding 1.5m in depth for foundation, laying of cable/pipe/pole etc or soil for shaft, walls, cesspts, manholes, pier holes etc not exceeding 10 sqm on plan and getting out in soft/loose soil complete all as specified & directed by Engr-in-Charge. |
| 2 | Excavation in trenches not exceeding 1.5m wide and not exceeding 1.5m in depth for foundation, laying of cable/pipe/pole etc or soil for shaft, walls, cesspts, manholes, pier holes etc not exceeding 10 sqm on plan and getting out in hard/dense soil complete all as specified & directed by Engr-in-Charge. |
| 3 | Excavation in trenches not exceeding 1.5m wide and not exceeding 1.5m in depth for foundation, laying of cable/pipe/pole etc or soil for shaft, walls, cesspts, manholes, pier holes etc not exceeding 10 sqm on plan and getting out in soft/disintegrated rock complete all as specified & directed by Engr-in-Charge. |
| 4 | Returning, filling in, including, spreading, levelling, watering and well ramming in layers not exceeding 25 cm thick soil/disintegrated rock all as specified & directed by Engr-in-Charge. |
| 5 | Removing excavated material soil/disintegrated rock to a distance not exceeding 50 m and depositing where directed at a level not exceeding 1.5 m above the starting point all as directed by Engr-in-Charge. |
| 6 | Supplying, laying, testing and commissioning of LT UG, XLPE insulated, heavy duty, 1100V grade of size 120 Sqmm 3½ core electric cable with aluminum conductor, served with an inner sheathing of PVC tape armored with galvanized steel wire or tape and overall PVC sheathed, laid in trenches or passing through pipe, making all connections with and including provision of necessary glands, lugs, bushing etc as required including taking down old existing unserviceable cable complete all as specified and as directed by Engineer-in-Charge of following sizes:-Note : - Earthwork excavation, protection pipe shall be measured and paid separately in their respective items |
| 7 | All as per item No 6 above but of size 95 sq mm. 3½ core |
| 8 | All as per item No 6 above but of size 70 sq mm. 3½ core |
| 9 | All as per item No 6 above but of size 50 sq mm. 3½ core |
| 10 | All as per item No 6 above but of size 35 sq mm. 3½ core |
| 11 | All as per item No 6 above but of size 25 sq mm. 4core |
| 12 | All as per item No 6 above but of size 16 sq mm. 4 core |
| 13 | All as per item No 6 above but of size 10 sq mm 4 core |
| 14 | Re-laying /fixing only existing , XLPE insulated , Armoured , Electric Power UG Cable (Heavy Duty) , 1100 Volt Grade of any Cross sectional areacomplete all as specified and directed by Engr -in- Charge.Note : Excavation, earth work, Pipe etc measured and paid separately. |
| 15 | Supply and laying DOUBLE WALLED CORRUGATED (DWC) pipe 90 mm bore as per IS-16205 part-24 for cable protection including all fittings as required complete all as specified and directed by Engr -in- Charge. |
| 16 | Supply and laying DOUBLE WALLED CORRUGATED (DWC) pipe 75 mm bore as per IS-16205 part-24 for cable protection including all fittings as required complete all as specified and directed by Engr -in- Charge. |
| 17 | Supply and laying DOUBLE WALLED CORRUGATED DWC , HDPE pipe 63 mm bore as per IS-16205 part-24 for cable protection including all fittings as required complete all as specified and directed by Engr -in- Charge. |
| 18 | Supply and laying DOUBLE WALLED CORRUGATED (DWC) pipe 50 mm bore as per IS-16205 part-24 for cable protection including all fittings as required complete all as specified and directed by Engr -in- Charge. |
| 19 | Supply and fixing in replacement of MCCB 4 Pole 400 Amps, breaking capacity 36 KA, thermal & magnetic adjustable type, 415 volts with extended copper terminals complete and connecting links on LT panel/feeder pillar including dismantling/taking down existing unserviceable MCCB complete all as specified and directed and directed by Engr-in Charge. |
| 20 | Supply and fixing in replacement of MCCB 4 Pole 250 Amps, breaking capacity 36 KA, thermal & magnetic adjustable type, 415 volts with extended copper terminals complete and connecting links on LT panel/feeder pillar including dismantling/taking down existing unserviceable MCCB complete all as specified and directed and directed by Engr-in Charge. |
| 21 | Supply and fixing in replacement of MCCB 4 Pole 200 Amps, breaking capacity 25 KA, thermal & magnetic adjustable type, 415 volts with extended copper terminals complete and connecting links on LT panel/feeder pillar including dismantling/taking down existing unserviceable MCCB complete all as specified and directed and directed by Engr-in Charge. |
| 22 | Supply and fixing in replacement of MCCB 4 Pole 160 Amps, breaking capacity 25 KA, thermal & magnetic adjustable type, 415 volts with extended copper terminals complete and connecting links on LT panel/feeder pillar including dismantling/taking down existing unserviceable MCCB complete all as specified and directed and directed by Engr-in Charge. |
| 23 | Supply and fixing in replacement of MCCB 4 Pole 100 Amps, breaking capacity 16 KA, thermal & magnetic adjustable type, 415 volts with extended copper terminals including taking out existing UNSV / burnt MCCB complete all as specified and directed by Engineer-in-charge. Note for Ser No 19 to 23 :All MCCB will be ICS = ICU 100%). |
| 24 | Supply and fixing in replacement of MCCB 4 pole 63 Amps rupturing capacity 16 KA with connecting links on LT panel/feeder pillar including dismantling/taking down existing unserviceable MCCB complete all as specified and directed. |
| 25 | Supply and fixing in replacement of MCB TPN 100 Amps rupturing capacity 10 KA with connecting links on LT panel/feeder pillar including dismantling/taking down existing unserviceable MCB complete all as specified and directed. |
| 26 | Supply and fixing in replacement of MCB TPN 63 Amps rupturing capacity 10 KA with connecting links on LT panel/feeder pillar including dismantling/taking down existing unserviceable MCB complete all as specified and directed. |
| 27 | S&F in repair, MCB Triple pole and netural rated capacity 32 Amps, 415 volts breaking capacity 10 KA complete all as specified & directed by Engineer-in-Charge. |
| 28 | S&F in repair, MCB Single pole and netural rated capacity 40 Amps, 240 volts breaking capacity 10 KA complete all as specified & directed by Engineer-in-Charge. |
| 29 | Material and labour for cutting the existing bituminous road / hard standing to size not exceeding 45cm wide and depth not less than 45cm for passing of UG cable through GI pipe and making good the disturbed surface filled with excavated material and top 200mm depth with plain cement concrete 1:3:6, type C1 using 20mm graded aggregate complete all as specified and directed by Engineer-in-Charge. |
| 30 | S&F in repair GI pipe light grade of dia 50 mm laying in road and along with poles for cable protection complete all as directed by Engr-in-Charge. |
| 31 | All as per item No. 30 above but size 80mm dia. |
| 32 | Supply,installing, testing and commissioning in repair out door type LT feeder piller box, padestal mounted, CPRI type tested factory made totally enclosed, dust and vermin proof, double leaf shutter in front and single leaf shutter in rear side made of 3.15 mm thick CRCA sheet, framing with 50 x 50 x 6 mm thick MS angle iron and legs of size 0.5m long . duly fabricated and having proper locking arrangement in both front and rear door with 4 side slanting roof duly projected and painted to both internal and External surfaces with powder coating paint in heat process of sheet and suitable for 415 volts, 50 Hz, 3 phase 4 wire system and comprising with and the panel shall be mounted on 50x50x6mm angle iron stand of height 45cm above ground and 45 cm embeded in ground on suitable PCC foundations. Computer cut shelf adhesive vinyl danger notice plate having conventional symbol of bone & skull be provided complete and including taking down existing unsv Panel etc complete all as specified and as directed. The panel shall consists of following accessories:- |
| 33 | Incoming Side(i) MCCB 4P of capacity 400 Amps, 415 Volts, 50 Hz, 3 phase breaking capacity 36 KA with thermal magnetic release - 01 No(ii) Digital type Multifunctinal meter CT operated class 1 accuracy suitable for measuring v, A,PF,kW,kva etc 3 Phase, 4 digit, high resolution, LED type with one side programmability – 01 No. (iii) Indicator lamp with holder key flush mounted,LED type Red, yellow, blue with toggle switch– 03 Nos. (iv) Bus bar strips made of Aluminium 600 Amps (Based on 1.6 Amps per sqmm) – 04 Nos aluminium bus bar TPN duly insulated with coloured PVC sleeve as per standard colour code and rigidly mounted on bakelite/DMC insulator bus bar support (Square/round) insulators of suitable size and good insulation resistance Please Enable Macros to View BoQ information |
| 34 | Incoming Side(i) MCCB 4P of capacity 400 Amps, 415 Volts, 50 Hz, 3 phase breaking capacity 36 KA with thermal magnetic release - 01 No(ii) Digital type Multifunctinal meter CT operated class 1 accuracy suitable for measuring v, A,PF,kW,kva etc 3 Phase, 4 digit, high resolution, LED type with one side programmability – 01 No. (iii) Indicator lamp with holder key flush mounted,LED type Red, yellow, blue with toggle switch– 03 Nos. (iv) Bus bar strips made of Aluminium 600 Amps (Based on 1.6 Amps per sqmm) – 04 Nos aluminium bus bar TPN duly insulated with coloured PVC sleeve as per standard colour code and rigidly mounted on bakelite/DMC insulator bus bar support (Square/round) insulators of suitable size and good insulation resistance Please Enable Macros to View BoQ information |