| 1 | Supplying and fixing following size/ modules, GI box along with modular base & cover plate for modular switches in recess etc. as required.IP44 or better (dust/moisture resistant) |
| 2 | 4 Module (125mmX75mm) |
| 3 | 8 Module (125mmX125mm) |
| 4 | 12 Module (200mmX150mm)For sockets in midway of longwall |
| 5 | Supplying and fixing following modular switch/ socketon the existing modular plate & switch box includingconnections but excluding modular plate etc. as required. |
| 6 | 3 pin 5/6 A socket outlet |
| 7 | 6 pin 15/16 A socket outlet |
| 8 | Supplying and fixing metal box of following sizes (nominal size) on surface or in recess with suitable size of phenolic laminated sheet cover in front including painting etc. as required.150 mm X 150 mm X 60 mm deep |
| 9 | Providing and fixing suitable size 3 way connector/terminal for cable connection, including making connections, dressing, insulating, testing and commissioning, complete as required. |
| 10 | Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required. 2 X 6 sq. mm (19mm) |
| 11 | Supply of following type of XLPE POWER CABLE of 1.1 kv grade armoured Al. cable compulsory ISI mark confirming to IS:7098/ PART –I / 88 with amendment no.1 as required.3X6 Sq.mm armoured |
| 12 | Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size on wall surface as required. Upto 35 sq. mm (clamped with 1mm thick saddle) |
| 13 | Wiring for circuit/ submain wiring along with earth wire with the following sizes of FRLS/HFFR PVC insulated copper conductor, single core cable in surface/recessed steel conduit as required. 2 X 1.5 sq. mm + 1 X 1.5 sq. mm earth wire |
| 14 | Wiring for circuit/ submain wiring along with earth wire with the following sizes of FRLS/HFFR PVC insulated copper conductor, single core cable in surface/recessed steel conduit as required. 2 X 2.5 sq. mm + 1 X 2.5 sq. mm earth wire |
| 15 | Supplying and fixing DP sheet steel enclosure on surface/ recess along with 25/32 A 240 V \\"C\\" curve DP MCB complete with connections, testing and commissioning etc. as required |
| 16 | Earthing with G.I. earth pipe 4.5 Meter long, 40 mm dia including accessories, and providing masonryenclosure with cover plate having locking arrangement and watering pipe etc. with charcoal/ coke and salt as required |
| 17 | Providing and laying earth connection from earth electrode with 6 SWG dia G.I. Wire in 15 mm dia G.I. pipe from earth electrode including connection with G.I. thimble excavation and re-filling as required. |
| 18 | Providing and fixing 6 SWG dia G.I. wire on surface or in recess for loop earthing as required. |
| 19 | Supplying and fixing 6 A rating, 240/415 V, 10 kA, \\"C\\" curve, miniature circuit breaker suitable forinductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. |
| 20 | Supplying and fixing 10 A rating, 240/415 V, 10 kA, \\"C\\" curve, miniature circuit breaker suitable forinductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. Please Enable Macros to View BoQ information |