| 1 | Main Distribution panel: Fabrication, Supplying, Installation, Testing and Commissioning of Outdoor LT cubical type of suitable size and not less than 300mm deep made out of CRCA sheet steel 3.1mm thick CRCA sheet powder coated, processed with 7 tank process having sealing arrangement, dust, vermin, duly compartmentalised having 4 strip TPN Aluminium busbar with cable alleys, detachable cable terminating plates at the bottom, ventilator louvers with wire mess,all end terminations included inside the various chambers, danger notice boards, sign wirting.The panel shall be mounted on the floor and should be supported with bottom C-channel as rasied platform and as suitable for site conditions or as per directions of Engineer In-charge and having following switch gears, instruments and accessories mounted inside the cubicle panel i/c connection, interconnection with copper thimbles, earthing etc complete and as per CPWD specification as reqd. |
| 2 | Incoming :-250 A FP MCCB 36 KA Ics = 100% Icu with thermal magnetic release with spreader terminals and rotary Handle - 1 No.TPN aluminium bus bars of 300 AMP rating - 1 setMeteringLED Multifunction Digital Meter (VAF ) type with inbuilt selector switch - 1 no. LED type RYB phase indicating lamps, ON, OFF, trip indicating lamps and with toggle switches with MCB control - 1 Set Outgoing :- a) 125A 36kA FP MCCB with Rotary Handle and with ON/OFF and TRIP CKT indication lamps- 01 Nos b) 100A 30kA FP MCCB with Rotary Handle and with ON/OFF and TRIP CKT indication lamps- 01 Nos as Spare c) 63A FP MCCB - 4 nosOther items of panel:a) Aluminium Earth strip 25 x 5 mm size full width of the panel with earth stud at both ends-1 set.b)Incoming/Outgoing complete Sign writing - 1 job. c) Danger notice plate - 1 No. |
| 3 | Wall mounted Sub panel for Spark Plasma Sintering Set: Fabrication, Supplying, Installation, Testing and Commissioning of Outdoor LT cubical type of suitable size and not less than 150mm deep made out of CRCA sheet steel powder coated, processed with 7 tank process having sealing arrangement, dust, vermin, duly compartmentalised having 4 strip TPN Aluminium busbar with cable alleys, detachable cable terminating plates at the bottom, ventilator louvers with wire mess,end termination, danger notice boards, sign wirting.The panel shall be mounted on the wall/pillar as per directions of Engineer In-charge and having following switch gears, instruments and accessories mounted inside the cubicle panel i/c connection, interconnection with copper thimbles, earthing etc complete and as per CPWD specification as reqd. |
| 4 | Incoming :-125 A FP MCCB 36 KA Ics = 100% Icu with thermal magnetic release with spreader terminals and rotary Handle - 1 No.Metering/Indications: LED type RYB phase indicating lamps, ON, OFF, trip indicating lamps and with toggle switches with MCB control - 1 Set Outgoing :- a) 100A 30kA FP MCCB with Rotary Handle and with ON/OFF and TRIP CKT indication lamps- 01 Nos b) 40 A TPN - 1 noOther items of panel:a) Aluminium Earth strip 25 x 5 mm size full width of the panel with earth stud at both ends-1 set.b)Incoming/Outgoing complete Sign writing - 1 job. c) Danger notice plate - 1 No. |
| 5 | Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size on cable tray as required |
| 6 | a) Above 185 sq. mm and upto 400 sq. mm (clamped with 40x3mm MS flat clamp) |
| 7 | b) Above 35 sq. mm and upto 95 sq. mm (clamped with25x3mm MS flat clamp) |
| 8 | Supplying and installaton following size of perforated painted with powder coating M.S. cable trays with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with two numbers MS/GI Suspenders i/c base of suitable size MS/GI angle, bolts & nuts, painting suspenders, fastener etc as required. |
| 9 | a) 150 mm width X 50 mm depth X 1.6 mm thickness |
| 10 | Supplying and installation following size of perforated painted with powder coating M.S. cable trays bends with perforation not more than 17.5%, joined with connectors, suspended from the ceiling with two numbers MS/GI Suspenders i/c base of suitable size MS/GI angle, bolts & nuts, painting suspenders, fastener etc as required. |
| 11 | a) 150 mm width X 50 mm depth X 1.6 mm thickness |
| 12 | Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required. |
| 13 | a) 3½ X 240 sq. mm (62mm) |
| 14 | b) 3½ X 70 sq. mm (38mm) |
| 15 | Supply of following size ISI marked, FRLS/HFFR PVC insulated, single core copper conductor wire/cable |
| 16 | a) 4 sq. mm |
| 17 | b) 10 sq. mm |
| 18 | Running of the following sizes of FRLS/HFFR PVC insulated copper conductor, single core cable after laying medium class 32mm PVC conduit along with necessary bends, divders, jointersm etc laid on surface as required. |
| 19 | a) 4 runs (RYBN) of 1 X 10 sq.mm copper cable as a unit mtr |
| 20 | b) 4 runs (RYBN) of 1 X 4 sq.mm copper cable as a unit mtr |
| 21 | Supplying and making end termination with copper lugs (pin or ring type as per site condition) for following size of PVC insulated wire/cable and necessary compression gland/Rubber Ring Wiring Grommets support at the panel enclosure as required. |
| 22 | a) 1 core x 4 sqmm |
| 23 | b) 1 core X 10 sqmm |
| 24 | Supply and installation of following rating T&PN along with outdoor compatible metal enclosure with water proof cover on top and ease of opening and operation. Access for incomer/outgoing termination of wires/cable should be available |
| 25 | a) 32/40A T&PN C Curve with metal enclosure anti rust coating |
| 26 | b) 25A T&PN C Curve with metal enclosure anti rust coating |
| 27 | c) 63A T&PN C Curve with metal enclosure anti rust coating and provision for cable terminations |
| 28 | Earthing with copper earth plate 600 mm X 600 mm X 3 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 Meter long etc. with charcoal/ coke and salt as required |
| 29 | Supplying and laying 25 mm X 5 mm copper strip at 0.50 metre below ground as strip earth electrode, including connection/ terminating with nut, bolt, spring, washer etc. as required. (Jointing shall be done by overlapping and with 2 sets of brass nut bolt & spring washer spaced at 50mm) |
| 30 | Providing and fixing 25 mm X 5 mm copper strip on surface or in recess for connections etc. as required. Please Enable Macros to View BoQ information |