| 1 | Excavation in trenches not exc. 1.5 m wide and exceeding 1.5 mtr deep but not exc 3.0 mtr deep in hard/dense soil and getting out for shafts, wells, cesspits, manholes pier holes, cables, pipe etc, complete all as sopecified and directed.32.40+25 |
| 2 | Returning filling in including spreading, levelling, watering and well ramming soil in layers not exc. 25 cms complete all as specified and directed. 20.95+21 |
| 3 | Removing excavated soft soil to a distance not exceeding 50m and depositing where directed at a level not exceeding 1.5 mtr above the starting point complete all as specified and directed.11.45+4 |
| 4 | M&L for river washed and screened, dry sand for filling in trenches below and around underground cables for cushioning of cables etc, complete all as specified and directed.(Note:- Measurement shall be taken after punning down.) |
| 5 | S&F sub class B brick having minimum compressive strength 75 kg/Sqcm laid in trenches for cable protection etc complete all as specified and directed by Engr-in-Charge. |
| 6 | Supply & fixing including testing & commissioning of LT XLPE insulated, screened, PVC bedded,galvanised steel strip or wire armoured,electric power cables (heavyduty) with aluminium conductor, 1100 volts, grade of following sizes laid in trenches/fixed to poles & pannels etc:- (Note:- (i) Layout of cable shall be approved by GE before laying the same at site.(ii) Excavation & earth work shall be measured and paid seperately under respective items.(iii) Manufacturer's test certificate, Tax invoice, purchase voucher & e-way bill shall be produced by contractor in original for verification of Engineer-in-Charge with material laid on site.) |
| 7 | 35 Sqmm 3.5 Core |
| 8 | 50 Sqmm 3.5 Core |
| 9 | 185 Sqmm 3.5 Core |
| 10 | Supply, fixing and testing straight through joint heat shrinkable type with jointing kit suitable for cable PVC/XLPE insulated amoured heavy duty aluminium conductor 1100 Volts grade complete all as specified for the following sizes:- |
| 11 | 25-50 Sqmm x 3.5 core / 4 core |
| 12 | 70-240 Sqmm x 3.5 core / 4 core |
| 13 | Supply, laying jointing,testing DI pipe with class-K-7 spigot socketed ends , conforming to IS-8329 laid in trenches including providing route indicators of suitable height and laying at spacing of @ 50m center to center at GL mentioning name of contractor, date of execution & CA No with name of work & rubber gasket (Tyton) joints with jointing material & route indicators of the following sizes complete all as specified and directed by Engineer-in-Charge. (Note : (i) Excavation & earth work shall be measured & paid separetely under respective items of BOQ.(ii) Contractors will provide route indicators mild steel body with top 150 mm plate 3mm thick and height not less than 300mm above finished GL at suitable intervals as directed by EIC. Cost of route indicators shall be deemed included in quoted unit rates.(iii) DI pipe whole quantity of tender shall be procured by contractor in one time from the authorised dealer of approved make and PV's, MTC & e-way bill will produced by contractor during payment of 1s RAR as material laying at site.(iv) Piece meal site for laying of pipe shall be given by EIC and contractor arrange to transport the DI pipe accordingly at his own arrangement. No any additional payment for transportation will be given to contractor. Contractors are requested to quote rate accordingly.(v) Layout plan for laying of DI pipe shall be given by EIC in writing. |
| 14 | 100 mm bore |
| 15 | 150 mm bore |
| 16 | M&L for DI fittings / specials such as Tees, bends (any type, radius and angle) tapers any type, collars, tail pieces, caps and plugs of the upto 150mm bore sizes confirming to IS:9523 complete all as specified and directed by Engr-in-Charge. |
| 17 | Material and labour for Rubber Gasket Joint (Tyton Joint) including jointing material for DI/CI pipe of following size/bore :- |
| 18 | 100 mm bore |
| 19 | 150 mm bore |
| 20 | Labour for cutting of CI / DI / GI pipe in position for reducing to required length for insertion of new tees, branches etc upto 150 mm bore complete all as specified and directed by Engr-in-Charge. Please Enable Macros to View BoQ information |