| 1 | Item Rate BoQ BoQ_Ver3.0 Item Rate Normal INR Only INR Select, Excess (+), Less (-) Less (-) Tender Inviting Authority: GE Utilities Udhampur Name of Work: Repair/Maintenance of starter and control panels for pumping system in AOR of GE (Utilities) Udhampur Contract No: GE/U-55/2026-27 Bidder Name : PRICE SCHEDULE(This BOQ template must not be modified/replaced by the bidder and the same should be uploaded after filling the relevent columns, else the bidder is liable to be rejected for this tender. Bidders are allowed to enter the Bidder Name and Values only ) NUMBER # TEXT # TEXT # NUMBER # TEXT # NUMBER NUMBER TEXT TEXT # NUMBER # TEXT# TEXT # NUMBER # NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER # NUMBER # TEXT TEXT NUMBER # NUMBER # DATE NUMBER # NUMBER # TEXT # Ser.No. Item Description Item Code / Make Quantity Units Estimated Rate Addition / Deduction Addition / Deduction Values Currency Convertion against each Item Quoted Currency in INR / Other Currency BASIC RATE In Figures To be entered by the Bidder Rs. P Excise Duty VAT Freight Charges ( Unloading & Stacking) Any Other Taxes/Duties/Levies Other Taxes 2 IIIrd Party i.e DGS&D / RITES etc Inspection Charges @0.34%+Service Tax Less for Cenvat Credit,if any respect of Supplies Under full Excise Duty Category TOTAL AMOUNT Without Taxes TOTAL AMOUNT TOTAL AMOUNT In Words |
| 2 | Supply , fixing, commissining and testing in replacement of Fully automatic star delta motor starter in sheet steel enclosure type HGS series with single phase protection feature motor rating AC 3 phase 415 volts, 50 Hz for motor of capacity 100 HP . Make-Havells or equivalent in L&T/ABB/ Schneider, complete all as specified and directed by Engineer-in-Charge. |
| 3 | Description all as per serial item No 1.00 here-in- before but of size 75 HP, complete all as specified and directed by Engineer-in-Charge. |
| 4 | Description all as per serial item No 1.00 here-in- before but of size 60 HP, complete all as specified and directed by Engineer-in-Charge. |
| 5 | Description all as per serial item No 1.00 here-in- before but of size 50 HP, complete all as specified and directed by Engineer-in-Charge. |
| 6 | Description all as per serial item No 1.00 here-in- before but of size 40 HP, complete all as specified and directed by Engineer-in-Charge. |
| 7 | Description all as per serial item No 1.00 here-in- before but of size 30 HP, complete all as specified and directed by Engineer-in-Charge. |
| 8 | Description all as per serial item No 1.00 here-in- before but of size 20 HP, complete all as specified and directed by Engineer-in-Charge. |
| 9 | Description all as per serial item No 1.00 here-in- before but of size 15 HP, complete all as specified and directed by Engineer-in-Charge. |
| 10 | S&F in replacement of DOL starter in sheet steel enclosure type for 7.5 to 10 HP,3 phase complete all as specified and directed by Engineer-in-Charge.Make-Havells or equivalent in L&T/Indo Asian |
| 11 | S&F in replacement of DOL starter in sheet steel enclosure type for 1 to 5 HP,3 phase complete all as specified and directed by Engineer-in-Charge.Make-Havells or equivalent in L&T/Indo Asian |
| 12 | M&L to in replacement soft starter of capacity 250 KW, 470Amp, suitable for 270 HP motor replacement should be carried out by the authorised dealer of soft starter and certificate will be provided by the cont from the dealer of soft starter, complete all as specified and directed by Engineer-in-Charge. |
| 13 | M&L to in replacement soft starter of capacity 200 KW, 370Amp, suitable for 170 HP motor replacement should be carried out by the authorised dealer of soft starter and certificate will be provided by the cont from the dealer of soft starter, complete all as specified and directed by Engineer-in-Charge. |
| 14 | M&L to in replacement soft starter of capacity 110 KW, 210Amp, suitable for 100 HP motor replacement should be carried out by the authorised dealer of soft starter and certificate will be provided by the cont from the dealer of soft starter, complete all as specified and directed by Engineer-in-Charge. |
| 15 | M&L to repair /servicing of star delta starter of cap 75/100 HP motor including replacement of defetive contactor,relay and other connected items , complete all as specified and directed by Engineer-in-Charge. Note : -S&F of replacement parts, shall be measured and paid for separately under the relevant items of Schedule ‘A’. |
| 16 | S&F Thermal overload relay Rated current 100 A (AC-3), operating voltage voltage up to 690V AC,insulation voltage 1000 V, Impulse voltage 8 kV, HGST 100 conforms to IEC 60947-4-1complete all as specified and directed by Engineer-in-Charge. |
| 17 | S&F star-delta timer adjustable \\"Star time\\" (1-30 Sc) and \\" Pause time\\" (30-150 Mimiseconds) designed for DIN rail mounting inside eletrical control panels complete all as specified and directed by Engineer-in-Charge. |
| 18 | S&F Therminal Block 6 way for Starter panel complete all as specified and directed by Engineer-in-Charge. |
| 19 | S&F Start push button (Green) and Motor stop push button (Red) complete all as specified and directed by Engineer-in-Charge. |
| 20 | S&F contact kit 4 pole contactor 25 Amp complete all as specified and directed by Engineer-in-Charge. |
| 21 | M&L to repair /servicing of star delta starter of cap 50/60 HP motor including replacement of defetive contactor,relay and other connected items , complete all as specified and directed by Engineer-in-Charge. Note : -S&F of replacement parts, shall be measured and paid for separately under the relevant items of Schedule ‘A’. |
| 22 | S&F Thermal overload relay Rated current 100 A (AC-3), operating voltage voltage up to 690V AC,insulation voltage 1000 V, Impulse voltage 8 kV, HGST 100 conforms to IEC 60947-4-1 complete all as specified and directed by Engineer-in-Charge. |
| 23 | S&F star-delta timer adjustable \\"Star time\\" (1-30 Sc) and \\" Pause time\\" (30-150 Mimiseconds) designed for DIN rail mounting inside eletrical control panels complete all as specified and directed by Engineer-in-Charge. |
| 24 | S&F Therminal Block 6 way for Starter panel complete all as specified and directed by Engineer-in-Charge. |
| 25 | S&F Start push button (Green) and Motor stop push button (Red) complete all as specified and directed by Engineer-in-Charge. |
| 26 | S&F contact kit 4 pole contactor 25 Amp complete all as specified and directed by Engineer-in-Charge. |
| 27 | Supply and laying DWC (Double wall corruguated) pipe 77/63 mm conforming to IS-14930/ IS-16205 for protection of earth strip/cable including necessary snap fit coupler reqd for fixing, complete all as specified and directed by Engineer-in-Charge. |
| 28 | Supply and laying DWC (Double wall corruguated) pipe 90/76 mm conforming to IS-14930/ IS-16205 for protection of earth strip/cable including necessary snap fit coupler reqd for fixing, complete all as specified and directed by Engineer-in-Charge. |
| 29 | M&L in replacement of PVC insulated heavy duty industrial cables single core copper conductor(flexible) PVC insulated cable 1100 volt nominal area of conductor 185 sqmm inculding taking down existing old unserviceable cable of complete all as specified and directed by Engineer-in-Charge. |
| 30 | M&L in replacement of PVC insulated heavy duty industrial cables single core copper conductor(flexible) PVC insulated cable 1100 volt nominal area of conductor 150 sqmm inculding taking down existing old unserviceable cable of complete all as specified and directed by Engineer-in-Charge. |
| 31 | M&L in replacement of PVC insulated heavy duty industrial cables single core copper conductor(flexible) PVC insulated cable 1100 volt nominal area of conductor 120 sqmm inculding taking down existing old unserviceable cable of complete all as specified and directed by Engineer-in-Charge. |
| 32 | M&L in replacement of PVC insulated heavy duty industrial cables single core copper conductor(flexible) PVC insulated cable 1100 volt nominal area of conductor 50 sqmm inculding taking down existing old unserviceable cable of complete all as specified and directed by Engineer-in-Charge. |
| 33 | M&L in replacement of PVC insulated heavy duty industrial cables single core copper conductor(flexible) PVC insulated cable 1100 volt nominal area of conductor 35 sqmm inculding taking down existing old unserviceable cable of complete all as specified and directed by Engineer-in-Charge. |
| 34 | S&F in replacement of power contactor 4 pole with AC coil AC-3 duty rating at 415 Volts 50 Hz, frame size1 suitable for 270 HP centrifugal pump set as per Havells cat part No. IHPAC330400*, complete all as specified and directed by Engineer-in-Charge. |
| 35 | S&F in replacement of power contactor 4 pole with AC coil AC-3 duty rating at 415 Volts 50 Hz, frame size1 suitable for 170 HP centrifugal pump set as per Havells cat part No. IHPAC115100*, complete all as specified and directed by Engineer-in-Charge. |
| 36 | Supply and lay in replacement MCCB 4 Pole, 415 V, Adjustable type, 400 Amps with breaking capacity 36 KA complete connection complete all as specified and directed by Engineer-in-Charge. |
| 37 | Supply and lay in replacement MCCB 4 Pole, 415 V, Adjustable type, 630 Amps with breaking capacity 50 KA complete connection complete all as specified and directed by Engineer-in-Charge. |
| 38 | M&L for Lt control panel designing, fabrication, providing,installation,testing and commissioning of LT control panel 415 volts, AC-3 Phase, 50 Hz. The panel shall be dust and vermin proof fabricated out of 14/16 SWG CR Sheet supported on M.S angle of suitable size and provision for erection/ fixing it on the ground/wall.The panel should be sturdy enough for vibration free operation and should be equipped with suitable locking/sealing arrangements. The structure should be provided suitable entry and exit holes for incoming and outgoing cables. The panel should have equipped with following components, complete all as specified and directed by Engineer-in-Charge :- |
| 39 | (a) Soft Stater suitable for 270 H.P induction motor. (i) The soft stater shall be designed, built and tested according to the lastest editions of application IEC standards,i.e EN60947-4-2. Soft stater shall be thyristor based with operation voltage: 208 - 600vac,50/60 Hz.(ii) The soft Stater shall have coated PCBAs to withstand harsh environments. (iii) The soft stater shall integrate motor and ,load protection, which shall under no cirsumstances be disabled when the integrated bypass is used, Motor overload Protection, Motor Underload Protection Underload protection over voltage & under voltage protection, single phase short circuit and thermal protection, Loacked Rotor Protection Manual or Automatic Reset,Thermal Memory, Thermal memory Thermal Capacity Reset Level, Phase Reversal. |
| 40 | (b) To achieve type1 corrdination, MCCB for 270 HP induction motor, 4 Pole,50 KA,lcs=100% lcu.(c) To achieve type2 corrdination , semiconductor fuses of suitable rating.(d) Line Contactor of suitable rating equivalent to AF370.(f) The panel should have ammeter digital type with CTs and selector seitch of suitable capapcity.(g) Voltmeter digital type with selector switch -01 No of suitable capacity.(h) Set of indicating lamp LED type -01 Set.(Note: Lt panel board should be as per IS/IEC 61439-1:2011 & IS/IEC 61439-2:2011) |
| 41 | M&L for Lt control panel designing,fabrication,providing,installation,testing and commissioning of LT control panel 415 volts, AC-3 Phase, 50 Hz. The panel shall be dust and vermin proof fabricated out of 14/16 SWG CR Sheet supported on M.S angle of suitable size and provision for erection/ fixing it on the ground/wall.The panel should be sturdy enough for vibration free operation and should be equipped with suitable locking/sealing arrangements. The structure should be provided suitable entry and exit holes for incoming and outgoing cables. The panel should have equipped with following components, complete all as specified and directed by Engineer-in-Charge:- |
| 42 | (a) Soft Stater suitable for 170 H.P induction motor. (i) The soft stater shall be designed, built and tested according to the lastest editions of application IEC standards,i.e EN60947-4-2. Soft stater shall be thyristor based with operation voltage: 208 - 600vac,50/60 Hz.(ii) The soft Stater shall have coated PCBAs to withstand harsh environments. (iii) The soft stater shall integrate motor and ,load protection, which shall under no cirsumstances be disabled when the integrated bypass is used, Motor overload Protection, Motor Underload Protection Loacked Rotor Protection Manual or Automatic Reset,Thermal Memory, Thermal memory Thermal Capacity Reset Level, Phase Reversal. |
| 43 | (b) To achieve type1 corrdination, MCCB 100 Amp, 4 Pole,50 KA,lcs=100% lcu.-01 Nos(c) To achieve type2 corrdination , semiconductor fuses of suitable rating.(d) Line Contactor of suitable rating equivalent to AF370.(f) The panel should have ammeter digital type with CTs and selector seitch of suitable capapcity.(g) Voltmeter digital type with selector switch -01 No of suitable capacity (h) To achieve type1 corrdination, MCCB for 170 HP induction motor, 4 Pole,50 KA,lcs=100% lcu.-01 Nos(i) Set of indicating lamp LED type -01 Set.(Note: Lt panel board should be as per IS/IEC 61439-1:2011 & IS/IEC 61439-2:2011) |
| 44 | M&L for Lt control panel designing, fabrication, providing,installation,testing and commissioning of LT control panel 415 volts, AC-3 Phase, 50 Hz. The panel shall be dust and vermin proof fabricated out of 3.15 mm CRCA Sheet supported on M.S angle of suitable size and provision for erection/ fixing it on the ground/wall.The panel should be sturdy enough for vibration free operation and should be equipped with suitable locking/sealing arrangements. The structure should be provided suitable entry and exit holes for incoming and outgoing cables. The panel should have equipped with following components, complete all as specified and directed by Engineer-in-Charge :- |
| 45 | (a) Variable frequency drive starter 62 Amp, 30 Kw, 40 HP 415 V, 3 phase-02 Nos(i) The VFD shall be designed, built and tested according to the lastest editions of application IEC standards,i.e EN60947-4-2. VFD shall be thyristor based with operation voltage: 208 - 600vac,50/60 Hz.(ii) The VFD shall have coated PCBAs to withstand harsh environments. (iii) The VFD shall integrate motor and ,load protection, which shall under no cirsumstances be disabled when the integrated bypass is used, Motor overload Protection, Motor Underload Protection Underload protection over voltage & under voltage protection, single phase short circuit and thermal protection, Loacked Rotor Protection Manual or Automatic Reset,Thermal Memory, Thermal memory Thermal Capacity Reset Level, Phase Reversal. |
| 46 | (b) To achieve type1 corrdination, MCCB 160Ap, 4 Pole,36 KA,lcs=100% lcu-01 nos(c) To achieve type2 corrdination , semiconductor fuses of suitable rating.-01 Nos(d) Line Contactor of suitable rating equivalent to 100 Amp.-01 Nos(e) Starter should consist of MPCB ( Motor Protection circuit breaker) of suitable capacity of the starter-01 Nos(f) The panel should have ammeter digital type with CTs and selector seitch of suitable capapcity.-01 Set(g) Voltmeter digital type with selector switch -01 No of suitable capacity. (i) To achieve type1 corrdination, MCCB 100Ap, 4 Pole,16 KA,lcs=100% lcu-02 nos(h) Set of indicating lamp LED type -01 Set.(Note: Lt panel board should be as per IS/IEC 61439-1:2011 & IS/IEC 61439-2:2011) |
| 47 | M&L for Lt control panel designing, fabrication, providing,installation,testing and commissioning of LT control panel 415 volts, AC-3 Phase, 50 Hz. The panel shall be dust and vermin proof fabricated out of 3.15 mm CRCA Sheet supported on M.S angle of suitable size and provision for erection/ fixing it on the ground/wall.The panel should be sturdy enough for vibration free operation and should be equipped with suitable locking/sealing arrangements. The structure should be provided suitable entry and exit holes for incoming and outgoing cables. The panel should have equipped with following components, complete all as specified and directed by Engineer-in-Charge :- |
| 48 | (a) Variable frequency drive starter 62 Amp, 30 Kw, 40 HP 415 V, 3 phase.-01 and VFD 33 Amp, 15 Kw, 20 HP-01 Nos(i) The VFD shall be designed, built and tested according to the lastest editions of application IEC standards,i.e EN60947-4-2. VFD shall be thyristor based with operation voltage: 208 - 600vac,50/60 Hz.(ii) The VFD shall have coated PCBAs to withstand harsh environments. (iii) The VFD shall integrate motor and ,load protection, which shall under no cirsumstances be disabled when the integrated bypass is used, Motor overload Protection, Motor Underload Protection Underload protection over voltage & under voltage protection, single phase short circuit and thermal protection, Loacked Rotor Protection Manual or Automatic Reset,Thermal Memory, Thermal memory Thermal Capacity Reset Level, Phase Reversal. |
| 49 | (b) To achieve type1 corrdination, MCCB 100Amp, 4 Pole,16 KA,lcs=100% lcu.-02 Nos(c) To achieve type2 corrdination , semiconductor fuses of suitable rating.(d) Line Contactor of suitable rating equivalent to 100 Amp-01 Nos(e) Starter should consist of MPCB ( Motor Protection circuit breaker) of suitable capacity of the starter.-01 Nos (f)To achieve type1 corrdination, MCCB 63Amp, 4 Pole,36 KA,lcs=100% lcu.-02 Nos(g) The panel should have ammeter digital type with CTs and selector seitch of suitable capapcity-01 Set(h) Voltmeter digital type with selector switch -01 No of suitable capacity.-01 set (i)To achieve type1 corrdination, MCCB 63Amp, 4 Pole,16 KA,lcs=100% lcu.-01 Nos(h) Set of indicating lamp LED type -01 Set.(Note: Lt panel board should be as per IS/IEC 61439-1:2011 & IS/IEC 61439-2:2011) |
| 50 | M&L for Lt control panel designing, fabrication, providing,installation,testing and commissioning of LT control panel 415 volts, AC-3 Phase, 50 Hz. The panel shall be dust and vermin proof fabricated out of 3.15 mm CRCA Sheet supported on M.S angle of suitable size and provision for erection/ fixing it on the ground/wall.The panel should be sturdy enough for vibration free operation and should be equipped with suitable locking/sealing arrangements. The structure should be provided suitable entry and exit holes for incoming and outgoing cables. The panel should have equipped with following components, complete all as specified and directed by Engineer-in-Charge :- |
| 51 | (a) Variable frequency drive starter 62 Amp, 30 Kw, 40 HP 415 V, 3 phase.-01 and VFD 39 Amp, 18.5 Kw, 25 HP-01 Nos(i) The VFD shall be designed, built and tested according to the lastest editions of application IEC standards,i.e EN60947-4-2. VFD shall be thyristor based with operation voltage: 208 - 600vac,50/60 Hz.(ii) The VFD shall have coated PCBAs to withstand harsh environments. (iii) The VFD shall integrate motor and ,load protection, which shall under no cirsumstances be disabled when the integrated bypass is used, Motor overload Protection, Motor Underload Protection Underload protection over voltage & under voltage protection, single phase short circuit and thermal protection, Loacked Rotor Protection Manual or Automatic Reset,Thermal Memory, Thermal memory Thermal Capacity Reset Level, Phase Reversal. |
| 52 | (b) To achieve type1 corrdination, MCCB 100Amp, 4 Pole,16 KA,lcs=100% lcu.-02 Nos(c) To achieve type2 corrdination , semiconductor fuses of suitable rating.(d) Line Contactor of suitable rating equivalent to 100 Amp-01 Nos(e) Starter should consist of MPCB ( Motor Protection circuit breaker) of suitable capacity of the starter.-01 Nos (f)To achieve type1 corrdination, MCCB 63Amp, 4 Pole,36 KA,lcs=100% lcu.-02 Nos(g) The panel should have ammeter digital type with CTs and selector seitch of suitable capapcity-01 Set(h) Voltmeter digital type with selector switch -01 No of suitable capacity.-01 set (i)To achieve type1 corrdination, MCCB 63Amp, 4 Pole,16 KA,lcs=100% lcu.-01 Nos(h) Set of indicating lamp LED type -01 Set.(Note: Lt panel board should be as per IS/IEC 61439-1:2011 & IS/IEC 61439-2:2011) |
| 53 | M&L for earthing complete with galvanised steel earth plate electrode 60 cm x 60 cm x 6.0mm thick buried directly in ground, (Earth pit not less than 2.25 mtr deep below ground level) with top edge of plate not less than 1.5 mtr below normal ground level, connected to galvanised iron strip 32×6mm as earthing lead by means of bolts, nuts, check nuts and washers of galvanised standard iron or steel all as specified or indicated in electrical plate no 3 of MES Part-I, including testing on completion including the material and labour of the following :-(a) Excavation and earth work for drilling hole for electrode in any type of soil. (b) PCC pit in cement concrete 1:2:4 type B-1.(c) Precast RCC cover with suitable handle 40 mm thick in PCC 1:2:4 type B-1, reinforced with welded steel wire fabric weighing not less than 1.87 Kg/Sqm.(d) Funnel with watering pipe of GI 20 mm nominal bore medium grade and copper lugs etc all as specified. (e) 15 mm nominal bore light grade GI protection pipe 7.5 mtr long for protection of earthing lead from mechanical injury or tempering. (f) Requisite quantity of common salt and charcoal.(g) Testing of earthing. |
| 54 | Note : On testing after completion of earthing, if the desired earth resistance is not obtained, the earthing will be re-done by the contractor at his own risk and cost to the entire satisfaction of the Engineer-in-Charge. |
| 55 | S& F HDPE Heavy Duty Plastic Pallets size 1200x1200 mm,load capacity static 4000 kg, weight-18 Kg minimum use in stock complete all as specified and directed by Engineer-in-Charge. |
| 56 | S&F in replacement HRC fuse 315 Amp, 500V ac, 120ka, type-VSK 315, as per IS:13703 part II complete all as specified and directed by Engineer-in-Charge. |
| 57 | S&F in replacement HRC fuse 500 Amp, -690/700V ac, 120ka, type-VSK 315, as per IS:13703 part II complete all as specified and directed by Engineer-in-Charge. Total in Figures 0.0 0.0 INR Zero Only 4.0 Construction of chamber for 100mm sluice plates item5 10.0 Nos Quoted Rate in Figures Select 0.0 0.0 Zero Only Quoted Rate in Words INR Zero Only Please Enable Macros to View BoQ information |