| 1 | Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit, with piano type switch, phenolic laminated sheet, suitable size M.S. box and eart;hing the point with 1.5 Sqm FRLS PVC insulated coper conductor single core cable etc as required. Group C |
| 2 | Wiring for light/ power plug with 2x4 Sqmm FRSL PVC recessed steel conduit alongwith 1 No. 4 Sqmm FRLS PVC insulated copper conductor single core cable for loop earthing as required. |
| 3 | Supplying and fixing metal box of 150mm X 60mm deep (nominal size) on surface or in recess with suitable size of phenolic laminated sheet cover in front including providing and fixing 3 pin 5/6 A socket outlet and 5/6 A Piano type switch, connections, painting etc. as required. |
| 4 | Supplying and fixing metal box of 180mm X 100mm X 60mm deep (nominal size) on surface or in recess with suitable size of phenolic laminated sheet cover in front including providing and fixing 6 pin 5/6 A& 15/16 A socket outlet and 151/6 A Piano type switch, connections, painting etc. as required. |
| 5 | Installaiton, testing and commissioning of pre-wired flouorescent fitting/ compact fluorescent fitting of all types, complete with all accessories and tube/ lamp etc. directly on ceiling/ wall, including connections with 1.5 Sqmm FRSL PVC insulared, copper conductor, single core cable and earthing etc. as required. |
| 6 | Supplying and fixing brass batten/ Angle holder including connectjion etc. as required. |
| 7 | Supplying and fixing 3 pin, 5A ceiling rose on the existing junction box/ wooden block including connections etc. as required. |
| 8 | Supplying and fixing following piano t;ype switch/ socket on the existing switch box/ cover including connections etc. as requred. |
| 9 | Supplying and fixing metal box of following sizes (nominal size) on surface or in recess with suitable size of phenolic laminated sheet cover in front including painting etc. as required 150mmX150mmX60mm deep. |
| 10 | Wiring for circuit/ submain wiring alongwith earth wire with the following size of FRSL PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required. |
| 11 | Supplying and fixing of following sizes of medium class PVC conduit along with acccessories in surfaces/ recess including cutting the wall and maiing good the same in case of recessed conduit as required. 25mm dia |
| 12 | Supplying and fixing following way, single pole and neutral, sheet steel, MCB distribution board, 240 V, on surface/recess, complete with tinned copper bus bar, neutral bus bar, each bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator) 2+16 ways |
| 13 | Supplying and fixing following rating, double pole, 240 V, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required 40 Amps |
| 14 | Supplying and fixing 5 A to 32 A rating, 240/415 V, 10 KA, \\"C\\" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commisssioning etc. as required |
| 15 | Earthing with GI earth plate 600 mm x 600 mm x 6 mm thick including accessories, and providing masonry enclosure with cover with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal/ coke and salt as required |
| 16 | S/F of 1100 volt heavy duty PVC cable for service connection of 10 Sqmm Twin Core Aluminum conductor of approved make with ISI mark |
| 17 | S/F house service bracket (hook type) complete with 3 mtr long GI pipe of 40 mm dia med grade 02 nos 90 degree bend MS hook and stay |
| 18 | S/F of LED tube light fitting 1 x 18 watt (4' long) of approved brand |
| 19 | S/F of celing fan of 1200 mm sweep incl wiring to the down rod upto 30 cm & regulator of standard quality Please Enable Macros to View BoQ information |