| 1 | Supplying and fixing 12 way, Double door, single pole and neutral, sheet steel, MCB distribution board, 240 V, on surface/ recess,complete with tinned copper bus bar, neutral bus bar, earth bar,din bar, interconnections, powder painted including earthing etc.as required. (But without MCB/RCCB/Isolator) |
| 2 | Supplying and fixing 5 A to 32 A rating, 240/415 V, 10 kA, “C” curve, miniature circuit breaker suitable for inductive load of Single pole in the existing MCB DB complete with connections, testing and commissioning etc. as required. |
| 3 | Supplying and fixing 63A rating, double pole, 240 volts, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required. |
| 4 | Wiring for circuit/ submain wiring along with earth wire with the 2 x 10 Sq mm + 1 x 6 Sq mm earth wire of FRLS PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required |
| 5 | Wiring for circuit/ submain wiring along with earth wire with the 2 x 4 Sq mm + 1 x 4 Sq mm earth wire of FRLS PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required |
| 6 | Wiring for circuit/ submain wiring along with earth wire with the 2 x 2.5 Sq mm + 1 x 2.5 Sq mm earth wire of FRLS PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required |
| 7 | Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable etc. as required. Group C |
| 8 | Wiring for twin control light point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit, 2 way modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable etc. as required |
| 9 | Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 6 pin 5/6 & 15/16 A modular socket outlet and 15/16 A modular switch, connections etc. as required. |
| 10 | Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 3 pin 5/6 A modular socket outlet and 5/6 A modular switch, connections etc. as required. |
| 11 | Supply Installation & commissioning of pre-wired, LED Tube Light fitting 18/20 Watt, complete with all accessories and tube etc directly on celing/wall including connection with 1.5 Sq mm FRLS PVC insulated copper conductor, single core cable and earthing etc as required |
| 12 | Supplying and fixing two module stepped type electronic fan regulator on the existing modular plate switch box including connections but excluding modular plate etc. as required. |
| 13 | Supply Installation & commissioning of LED Lamp 5/7 Watt |
| 14 | Supplying and fixing brass batten/ angle holder including connection etc. as required |
| 15 | Supplying and fixing 3 pin, 5 A ceiling rose on the existing junction box/ wooden block including connections etc. as required. |
| 16 | Supplying and fixing call bell/ buzzer suitable for single phase, 230 V, complete as required Please Enable Macros to View BoQ information |