| 1 | DG set |
| 2 | OD132408/2025-2026:Supply & Installation of 25 KVA Diesel Generator set including required control devices, protection such as suitable breaker and accoustic enclosure and DG set is to be Compliance with CPCB-4 plus norms and as per technical details given below on suitable size CC foundation. 1. Engine.a) Make of Engine - Krilosker/ Cummins b).Type of Engine - Diesel Engine. c). No. of Cylinders - As per manufactures standards.d). Method of cooling - Water cooled with radiator e). Aspiration - Turbo charged after cooled f). Design - Suitable for generating set operation. g). Out put - Required HP as per manufacturers standards at 1500 rpm under NTP condition. 2). Standard accessories with Diesel Engine a). Fly wheel to suit flexible coupling b.) Close Coupling. c.) Air cleaner. d.) Radiator with fan provided with fan guard e). Fuel Pump. f). Mechanical governor. g). Fuel filter. h.) Lubricating oil filter. i.) Exhaust silencer. j). Exhaust Muffler k). Battery Charging Generator 3.) Engine Instrument Panel with the following items. a). Starting switch with key or button b). Lubricating oil pressure gauge. c). Water temperature gauge. d). RPM Indicator with hour meter. e). Battery charging ammeter. f). Fuel indicator 4). Safety Controls for Engine a). Trip for low lubricating oil pressure. b). Trip for high water temperature. c). Alarm for low fuel level 6). Brushless Alternator a). Make - Stamford/ Cummins b). Type - Self exited and self regulated. c.) Capacity - 25 KVA/ 20.0 kW @ 0.8 PF d.) System of Voltage - 3 Phase, 415 V, 4 wire system e). Speed - 1500 rpm. f). Voltage regulation band - +/- 5% of rated voltage g). Frequency : 50 Hz h). Insulation - Class F / H The alternator should confirm to IS 4722 and warranted for 3 years. Operation and service manual , spares and tools shall be provided. 8. Fuel Tank Suitable size built in type integrated with the acoustic enclosure with connection shall be done as per standards 9. Battery. Suitable capacity fully charged battery with leads and terminals of appropriate AH capacity as per Manufactures requirement. 10. Supplying and providing the standard Electric control panel integrated withacoustic enclosure comprising of the following. a) Suitable braker b) Digital Multi function meter with accuracy class 1 to read parameters such as KW, PF, voltage, Current Frequency etc: c) Digital type single function KWH meter with accuracy class 1, Exhaust Piping shall be vent to the top of the nearest tallest building if required . If the pipe cannot be clamped/fixed to the building or any other structure of permanent nature necessary fabricated structures using channel section or angle iron sections of adequatemechanical strength, duly painted with 2 coats of Heat retardant aluminium paint shall be provided for the support of the exhaust pipe. (Additional piping will be measured excluding the standard length of pipe supplied by the manufacturer.) |
| 3 | OD132397/2025-2026:Supply and filling high speed Diesel for generator |
| 4 | OD132401/2025-2026:Supply and providing 12V, 2A Automatic Battery charger suitable for 100Ah Battery, having . Full protection against battery overcharging & reverse polarity. Over voltage, overload & short circuit protection, reverse battery protection. Digital meters for voltage & current display , Battery connecting terminals with lead wire, Float and Boost Charging Mode , LED Indication for charger status indication, etc: and giving necessary connections as required |
| 5 | OD132405/2025-2026:Charges for conducting load test of 25KVA DG set at standardized Factory bed as per standard norms and condition. ie in various steps load up to full load for 3 hours & 10% over load for 20 minutes and the rate includes hire and rent of test bed equipment's, labour charges ,loading and unloading and fuel etc.The test certificate should be given the client in standard format |
| 6 | OD132399/2025-2026:Providing, laying, testing and commissioning of 'C' class heavy duty MS pipe conforming to IS:1239 I/c fittings like elbows, tees, flanges, tapers, nuts, bolts, gaskets etc fixing the pipe on the wall/ ceiling with suitable clamps and painting with two or more coats of synthetic enamel paint of required shade complete as required. 50MM |
| 7 | 90.12.7.41:Supply, laying and clamping of 1 no. PVC insulated and PVC sheathed armoured aluminium power cable, 1.1 KV grade of the following sizes using clamps noted along with the cables, spacing of clamps not exceeding 60cms, making good the damages , colour washing etc. as required.4 core 16 sq mm with factory made clamp |
| 8 | 90.12.5.41:Supply & laying of one number PVC insulated and PVC sheathed armoured aluminium power cable of 1.1KV grade of the following sizes in the existing RCC/ HUME / STONE WARE/ GI/ DWC pipe as required.4 core 16 sq mm |
| 9 | 9.1.33:Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.4 X 16 sq. mm (28mm) |
| 10 | 90.12.5.2:Supply & laying of one number PVC insulated and PVC sheathed armoured aluminium power cable of 1.1KV grade of the following sizes in the existing RCC/ HUME / STONE WARE/ GI/ DWC pipe as required.2 core 6 sq mm |
| 11 | 90.12.7.2:Supply, laying and clamping of 1 no. PVC insulated and PVC sheathed armoured aluminium power cable, 1.1 KV grade of the following sizes using clamps noted along with the cables, spacing of clamps not exceeding 60cms, making good the damages , colour washing etc. as required.2 core 6 sq mm with factory made clamp |
| 12 | 90.12.10.2:Supply & laying of DWC pipe in ordinary soil 0.75m below ground level including excavation50/38 mm or nearest size |
| 13 | 9.1.1:Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.2 X 6 sq. mm (19mm) |
| 14 | OD154620/2025-2026:Supply and installation testing and Commissioning of 63A Enclosure type Automatic transfer Switch with Automatic and manual changeover options, with suitable rated contactors, on delay timer for generator, phase failure detectors and DG/KSEB incicator lamps |
| 15 | 90.11.1.19:Supply and installation of sheet steel, phosphatised and painted, dust and vermin proof enclosure of MCB DB including copper /brass bus bar, neutral link, earth bus and DIN rail suitable for fixing MCB/ isolator etc. fixed on wall using suitable anchor bolts or fixed in recess including cutting hole on the wall , making good the damages, colour washing etc. as required6 way (8+12) - double cover TPN vertical DB with provision for fixing MCCB as incomer and SP/ TP MCB as outgoing (IP 42/43) |
| 16 | 90.14.10.3:Supply, conveyance and fixing the following types & current rated control gears & switchgears conforming to IS 13947 suitable for 440 V, 50 Hz, AC supply in the existing panel assembly as required.16 A-100A, 16 kA (Ics=100%Icu), 4 pole, current limiting type MCCB having thermal setting range of 80 - 100% with thermal magnetic release having adjustable OL |
| 17 | 2.13.1:Supplying and fixing following rating, four pole, 415 volts, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required.40 amps |
| 18 | 2.10.4:Supplying and fixing 5A to 32 A rating, 240/415 volts, 10 kA, \\"\\"C\\"\\" curve, miniaturecircuit breaker suitable for inductive load of following poles in the existing MCBDB complete with connections, testing and commissioning etc. as required.Triple pole |
| 19 | OD149484/2025-2026:Supply and installation of L&T make MK 1 fully automatic strar delta starter for 7.5HP Motor relay range 6-10A coil Voltage 415V AC |
| 20 | 1.17.30:Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.3 x 6 sq. mm |
| 21 | 2.23.1:Supplying and fixing Cable End Boxes (IP 43) suitable for following single poleand neutral, sheet steel, MCB distribution board, 240 volts, on surface/ recess,complete with testing and commissioning etc. as required.For 6 way, Double door SPN MCBDB |
| 22 | 2.14.1:Supplying and fixing following rating, double pole, (single phase and neutral),240 volts, residual current circuit breaker (RCCB), having a sensitivity current 30 milli amperes in the existing MCB DB complete with connections, testing and commissioning etc. as required.25 amps |
| 23 | 2.10.1:Supplying and fixing 5A to 32 A rating, 240/415 volts, 10 kA, \\"\\"C\\"\\" curve, miniaturecircuit breaker suitable for inductive load of following poles in the existing MCBDB complete with connections, testing and commissioning etc. as required.Single pole |
| 24 | 2.12.1:Supplying and fixing following rating, double pole, 240 volts, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required.40 amps |
| 25 | OD132400/2025-2026:Supply and providing Red, Green, Black, Yellow, Orange colours LED indicators, AC/DC 22.5mm cut out dia |
| 26 | OD132407/2025-2026:Supply and providing Blue colour LED indicator lamp, AC/DC, 22.5 cm cut out dia- |
| 27 | OD132406/2025-2026:Carrying out control wiring for panel with normal meters and indication lamps alone with 650/1100 V grade PVC insulated stranded single core copper conductor cables 1.50 sq mm single run with required sockets.conforming to IS 694 part I 1990 for interconnecting the control devices/ equipments including providing suitable size insulated sockets at the termination points or soldered properly, providing numbering ferrules for the proper identification of the wiring, keeping the wiring firm by suitable tie/ tie mounts/ PVC duct etc as required. |
| 28 | OD132398/2025-2026:Painting letters or figures of the following sizes with enamel paint as identification mark to SB, DB, panel board etc as required- 2.50 cm, 4 cm or 5 cm height |
| 29 | 5.4:Earthing with G.I. earth plate 600 mm X 600 mm X 6 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal/ coke and salt as required. |
| 30 | OD160910/2025-2026:Supply and fixing 2 x 25mm X 3 mm copper strip test joint for the earthing system. |
| 31 | 90.16.1.3:Supply and drawing bare earthing conductors of the following sizes along with wiring/ cables and giving connection as required3.15 mm copper conductor ( 10 SWG) |
| 32 | 90.16.1.5:Supply and drawing bare earthing conductors of the following sizes along with wiring/ cables and giving connection as required4.75 mm copper conductor (6 SWG) |
| 33 | 90.16.5.5:Supply of superior quality copper earth socket for the following size of earth conductor including crimping etc. as required.4.75 mm (6 SWG) |
| 34 | 14.1:Excavation for foundation in soft soil including dressing of sides and ramming of bottoms, lift upto 1.5 m including getting out the excavated soil and disposal of surplus excavated soil as directed, within a lead of 50 metres. |
| 35 | 14.9:Providing and laying in position cement concrete 1 :3:6 (1 cement : 3 coarse sand : 6 graded stone aggregate 40 mm nominal size) in foundation of pump, DG set etc. including form work etc. as required. |
| 36 | OD132402/2025-2026:Reinforcement for R.C.C works, bend tied and placed in position (plain grill requiring bend cold) using tor steel as required. |
| 37 | 14.12:Providing 15mm thick cement plaster of mix 1:4(1 cement: 4 fine sand) at all levels |
| 38 | OD132409/2025-2026:Charges for preparation of Electrical/fire Drawing per A3 sheet first copy. |
| 39 | OD132403/2025-2026:Copying charges of Electrical/fire Drawing per A3 sheet additional copies |
| 40 | 1.21.1:Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/ recess including cutting the wall and making good the same in case of recessed conduit as required.20 mm |
| 41 | 1.1.3:Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed steel conduit, with piano type switch, phenolic laminated sheet, suitable size MS box and earthing the point with 1.5 sq.mm. FRLS PVC insulated copper conductor single core cable etc as required.Group C |
| 42 | 90.3.19.3:Supply conveyance, installation, testing and commissioning the light fittings of following types made from CRCA sheet 0.5mm thickness with all accessories and lamps directly on wall and giving connections with 16/0.20 mm 3 core PVC insulated and sheathed round copper conductor flex wire or extending the original wiring and giving connections as required1200 mm 1X20W LED Lamp with box type fixture |
| 43 | 1.17.3:Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.3 X 1.5 sq.mm |
| 44 | 1.17.12:Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.3 x 2.5 sq. mm |
| 45 | 1.24.3:Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.15/16 amp switch |
| 46 | 1.24.5:Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.6 pin 15/16 amp socket outlet |
| 47 | 1.27.2:Supplying and fixing following size/ modules, GI box alongwith modular base & cover plate for modular switches in recess etc as required.3 Module (100mmX75mm) |
| 48 | OD132411/2025-2026:Fire extinguisher:- Supply and installation of ABC type fire extinguisher 5kg capacity consisting of M.S cylindrical body, squeeze lever discharge valve fitted with pressure indicating gauge internal discharge tube, 30cm long high pressure discharge hose, nozzle etc. |
| 49 | OD164191/2025-2026:Supply and fixing DPDT glass relay(240V/16A) with base in the existing enclosure and giving connection as required- |
| 50 | OD164192/2025-2026:Supply and fixing 32 A AC3, MCX 03, 4 Pole power contactor (L&T) conforming to IS/IEC 60947-4-1 & IEC60947-4-1 in the existing enclosure and giving connection as required- |
| 51 | OD164193/2025-2026:Supply and renewing Single phase preventer relay( L&T make9032-Sz5/equivalent) for AC Units in place of the existing faulty ones and giving connections etc as required- |
| 52 | OD164194/2025-2026:Supply and providing 250x200x105mm syntex make junction box |
| 53 | 90.14.5:Supply and fabrication conveyance and installation of angle iron frame work for wall mounting panel board |
| 54 | OD157413/2025-2026:Electrical Inspectorate and KSEB Charges for Approvals and Load enhancement (Amount will be reimbursed after the production of the original bill) |
| 55 | OD176388/2025-2026:Provision for correcting the existing installation as per the direction from electrical inspectorate after submitting drawing for approval and inspection (The item rate as per the present DSR with quoted variation) Non competition item App rate Rs 10000.00 |
| 56 | Civil items |
| 57 | OD176239/2025-2026:Providing Aluminium traffold roofing sheet 0.40mm thick including vertical/ curvedsurfacefixed with polymer coated J or L hooks, bolts and nuts 8 mm diameter with bitumenand G.I. limpet washers orwith G.I. limpet washers filled with white lead, ( up to any pitch in horizontal /vertical or curved surfaces),excluding the cost of purlins, rafters and trusses and including cutting to size andshape wherever required.(based on 12.1.1) |
| 58 | 50.10.1:Steel work in built up G I tubular ( round, square or rectangular hollow tubes etc.) trusses etc., including cutting, hoisting,fixing in position and applying a priming coat of approved steel primer, including welding and bolted with special shaped washers etc. complete Please Enable Macros to View BoQ information |