Sales : +91-777 804 8217
| Sl. No. | Item Description |
| 1 | Sub Head No.1 (E&M Work) |
| 2 | Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS/HFFR PVC insulated copper conductor single core cable in surface/ recessed medium class PVC conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm FRLS/HFFR PVC insulated copper conductor single core cable etc. as required. |
| 3 | Group-B |
| 4 | Wiring for group controlled (looped) light point/fan point/exhaust fan point/ call bell point (without independent switch etc.) with 1.5 sq. mm FRLS/HFFR PVC insulated copper conductor single core cable in surface/ recessed PVC conduit, and earthing the point with 1.5 sq. mm FRLS/HFFR PVC insulated copper conductor single core cable etc. as required. |
| 5 | Group-B |
| 6 | Rewiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS/HFFR PVC insulated copper conductor single core cable and 1.5 sq.mm FRLS/HFFR PVC insulated copper conductor single core cable as earth wire in existing surface/ recessed steel/PVC conduit including dismantling as required. |
| 7 | Group-B |
| 8 | wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface /recessed steel conduit as reqd. |
| 9 | 2 X 1.5 sq. mm + 1 X 1.5 sq. mm earth wire |
| 10 | 2 X 4 sq. mm + 1 X 4 sq. mm earth wire |
| 11 | 4 X 4 sq. mm + 2 X 4 sq. mm earth wire |
| 12 | Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/recess including cutting the wall and making good the same in case of recessed conduit as required. |
| 13 | 25 mm |
| 14 | Supplying and fixing of 5 Ampers to 32 Ampers rating, 240/415 Volts, 10 kA, breaking capacity \\"C\\" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. |
| 15 | Single pole |
| 16 | Single pole & Neutral |
| 17 | Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface/recessed steel/ PVC conduit required. as |
| 18 | 3 x 1.5 sq. mm |
| 19 | 6 x 1.5 sq. mm |
| 20 | 3 x 4 sq. mm |
| 21 | 6 x 4 sq. mm |
| 22 | Supplying, installation, Testing & Commissioning of Flood Light, powder coated pressure die cast aluminum body with built in or separate driver as per the requirement with Driver efficiency >85%, Input voltage:Input voltage: 140-270 Volt AC, freq 50/60 hz, Operating temp range 15 deg to 50 deg centigrade, internal surge protection of 5 KV L,N,E as per IEC 61000-4-5, Driver efficiency >85%, THD < 10% as per IEC 61000-3-2, P. F.≥0.95, IP-66,IK-10, CRI >80. under voltage and over voltage protection, EMI-EMC as per CISPR-15, lenses for beam angle 30 deg- 120deg as per the application and the project requirement deg, suitable tilt able fitting, life time (LED, Driver & electrical circuitry) of minimum 50000 Burning Hours with 70% of initial Lumen maintained till life ends as per LM80 extrapolation IES TM-21-11 report, CCT 3000°K / 4000°K / 5700°K /6000°K/6500°K (As per ANSI Bin) SDCM(Standard Deviation Color Matching) <5, Maximum power consumption should not more than the specified rating and Fixture shall be of relevant BIS standard complete in all respect i/c connections with 1.5 sq mm FRLS, PVC insulated copper conductor single core cable and earthing etc. as required with Minimum 5 year OEM warranty. System lumen efficacy ≥120 and <135 lm/Watt output. LM79 & LM80 Test report from NABL lab for all testing required for LED fixtures as per BIS shall be submitted. Shape size and CCT shall be as approved by Engineer-in-Charge as per requirement. (Thermal management: heat sink of aluminum housing such that LED junction temperature shall not rise above 90°C). |
| 23 | 200 Watt |
| 24 | Supplying and laying of following size DWC HDPE pipe ISI marked along with all accessories like socket, bend, couplers etc. conforming to IS 14930, Part II complete with fitting and cutting, jointing etc.direct in ground (75 cm below ground level) including excavation and refilling the trench but excluding sand cushioning and protective covering etc., complete as required |
| 25 | 63 mm dia (OD-63 mm & ID-51 mm nominal) |
| 26 | 90 mm dia (OD-90 mm & ID-76 mm nominal) |
| 27 | Supplying and fixing 6 modular GI box with 6 modular base and cover plate, complete with 2 nos. 15/16A modular switches and 2 nos. 6-pin 15/16A modular sockets, including making necessary connections with 3 × 1.5 sq.mm copper single core PVC insulated wire in existing conduit, testing and commissioning etc. as required. |
| 28 | Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 6 pin 5/6 & 15/16 A modular socket outlet and 15/16 A modular switch, connections etc. as required |
| 29 | Supplying and fixing two module stepped type electronic fan regulator on the existing modular plate switch box including connections but excluding modular plate etc. as required. |
| 30 | Supplying and installing following size of perforated painted with powder coating M.S. cable trays with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with M.S. suspenders including bolts & nuts, painting suspenders etc. as required. |
| 31 | 150 mm width X 50 mm depth X 1.6 mm thickness meter |
| 32 | 300 mm width X 50 mm depth X 1.6 mm thickness |
| 33 | Supplying and fixing following way, single pole and neutral, sheet steel, MCB distribution board, 240 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator) |
| 34 | 16 way, Double door |
| 35 | 6 way, Double door |
| 36 | 8 way, Double door |
| 37 | Supplying and fixing following size/ modules, GI box alongwith modular base & cover plate for modular switches in recess etc. as required. |
| 38 | 1 or 2 Module (75 mmX75 mm) |
| 39 | 3 Module (100 mmX75 mm) |
| 40 | 6 Module (150 mmX75 mm) |
| 41 | 8 Module (125 mmX125 mm) |
| 42 | 12 Module (200 mmX150 mm) |
| 43 | Supplying and fixing following modular switch/socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required. |
| 44 | 5/6 Amp Switch |
| 45 | TV antenna socket outlet |
| 46 | 15/16 Amp Switch |
| 47 | 15/16 Amp Soclet Outlet |
| 48 | Earthing with G.I. earth pipe 4.5 Meter long, 40 mm dia including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe etc. with charcoal/ coke and salt as required |
| 49 | Providing and fixing 25 mm X 5 mm G.I. strip on surface or in recess for connections etc. as required. |
| 50 | Supply, Installation, Testing and Commissioning of BEE rated, ceiling fan with squirrel cage induction Motor, class of insulation: B, 3 nos. metal( Aliminium alloy blades, 30 cm long down rod, 2 nos. canopies, shackle kit, safety rope, copper winding, steel/Al body, Power Factor not less than 0.9 , 350 RPM (tolerance as per IS : 374-2019), THD less than 10%, remote or electronic regulator unit of suitable wattage for speed control and all remaining accessories including safety pin, nut bolts, washers, temperature rise=75 degree C (max.), insulation resistance more than 2 mega ohm, suitable for 230 V, 50 Hz, single phase AC Ceiling Fan compliant to IS 374:2019 fan Supply, earthing etc. complete as reqd. |
| 51 | Fancy Ceiling Fan 1200mm, rated voltage 230 V, 50 Hz (Design , Colour and Make will be decided by Engineer in charge). |
| 52 | Supplying, laying of 3 Core 10 sq mm size PVC insulated and PVC sheathed/ XLPE aluminum conductor armoured power cable of 1.1 KV grade in following manner etc complete as required. |
| 53 | on Surface/wall. |
| 54 | Direct in Pipe |
| 55 | Supplying, laying of 3.50 Core 50 sq mm size PVC insulated and PVC sheathed/ XLPE aluminum conductor armoured power cable of 1.1 KV grade in following manner etc complete as required. |
| 56 | Direct in Pipe |
| 57 | on Surface/wall |
| 58 | Supplying, laying of 4 Core 25 sq mm size PVC insulated and PVC sheathed/ XLPE aluminum conductor armoured power cable of 1.1 KV grade in following manner etc complete as required. |
| 59 | Direct in Pipe |
| 60 | on Surface/wall |
| 61 | Supplying, laying of 4 Core 16 sq mm size PVC insulated and PVC sheathed/ XLPE aluminum conductor armoured power cable of 1.1 KV grade in following manner etc complete as required. |
| 62 | Direct in Pipe |
| 63 | on Surface/wall |
| 64 | Supplying, Installation, Testing and Commissioning of 300 mm Sweep 900 RPM Heavy Duty ISI Marked Exhaust fan with louvers & shutters in the existing opening, including making good the same, connection, testing, commissioning etc. as reqd. |
| 65 | Supplying, installation, testing and commissioning of 250 mm sweep fresh air fan working on 230 +/- 10 V single phase 50 Hz Frequency complete with shutter in existing hole of suitable size making good the same i/c connections, interconnections etc. complete as required |
| 66 | Supplying and fixing of PVC cable management system / wall trunking with cover of following sizes including internal, external, flat single cover and T- cover, end cap and other accessories on the wall so as to make complete as required. |
| 67 | 80 mmx50mm |
| 68 | Providing & Laying of refrigerant copper piping of size 1/4\\" or 3/8\\" & 5/8\\" diameter (thickness of copper pipe not less than 1.6mm) from indoor unit to outdoor unit of split type Air Conditioner unit along with 4 core 2.5 sq.mm PVC insulated and PVC sheathed flexible copper conductor cable including 20 mm size of cotton thread ribbed PVC flexible pipe from drip tray of Air Conditioner unit to drain pipe along with necessary support complete etc all as per Direction of Engineer-in-charge. |
| 69 | Supplying & Drawing of 3x4 sqmm size of PVC insulated & pvc sheathed copper conductor round multicore flexible cable for indoor to outdoor and upto nearest power point i/c providing suitable copper lugs connection etc as required. |
| 70 | Supplying, installation, testing & commissioning of following capacity water storage vertical /horizontal type geyser working on 230 +/- 10 V single phase 50 Hz Frequency, tank with altra thick super cold rolled steel plates, puff insolation, rated pressure: 8 bar, Temperature range 75 degree C, heating indicator, temperature setting: manual, power consumption: min 2 kw i/c Thermostate, Thermal cut off, mltifactional sefety valve complete with necessary accessories & flexible heavy duty pvc connection of sutiable length (2 Nos.) and 25 amp plug top etc, as reqd. |
| 71 | 25 ltrs. Rating Minimum 4 star |
| 72 | 35 ltrs. Rating Minimum 4 star |
| 73 | Supplying, Installation, Testing & Commissioning of SMC pole Box of size 250mm x 200mm x 105mm with hinged cover on surface/ recess/pole complete with aluminium connector strip - 2 Nos, MS Clamp - 2 Nos., 6-32amp. C series SPMCB-1 No., having IP: 66 protection connection etc. as reqd. |
| 74 | Supply, installation, testing and commissioning of following watt LED Decorative post top fitting with aluminium die cast housing, Polycarbonate / Pamma prismatic clear/frosted diffuser with operating range of 100-270V, PF>0.95, luminious efficiency > 100 lumens/watt, CCT 3000k-6500k (CCT shall be decided by Engineer-in-charge), IP 65 with 4KV surge protection i/c connections & interconnections etc as required. |
| 75 | 40-45 Watt |
| 76 | Supplying and fixing decorative/fancy following modular switch/socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required. |
| 77 | RJ-45 modular type computer sockets |
| 78 | Supply, installation, testing and commissioning of 4 kg capacity ABC type portable fire extinguisher, filled with dry chemical powder (mono-ammonium phosphate based), confirming to IS:15683 with ISI marking, complete with pressure gauge, squeeze lever, safety pin, discharge hose/nozzle, wall mounting bracket and initial refilling charge. The extinguisher shall be suitable for Class A, B & C fires, stored pressure type with operating temperature range –5°C to +55°C. The rate shall include mounting on wall at approved locations, testing and demonstration as required and as directed by the Engineer-in-Charge, complete in all respects. |
| 79 | Supply, installation, testing and commissioning of 4.5 kg capacity CO₂ type portable fire extinguisher, confirming to IS:15683, complete with discharge horn, high-pressure hose, wheel-type valve, safety pin, and wall-mounting bracket. The extinguisher shall be ISI marked, made of seamless M.S. cylinder duly hydrostatically tested, filled with CO₂ gas as per standard, and suitable for Class B and electrical fires. The rate shall include fixing in position at approved locations, testing, and demonstration as required and as directed by the Engineer-in-Charge, complete in all respects. |
| 80 | Supplying, Installation, Testing & Commissioning of following fixture /fitting with all accessories directly on ceiling / wall i/c connection with 1.5 sq.mm FR PVC insulated copper conductor single core cable and earthing etc as required. |
| 81 | Mirror LED light/ Picture light fitting with aluminium/ polycarbonate housing |
| 82 | Supplying, Installation, Testing & Commissioning of minimum 5 watt / meter LED strip light for Cove in ceiling or other spaces at site of work including driver having colour temperature 3000K - 6500K etc complete as required (CCT shall be decided by Engineer-in-Charge). |
| 83 | Supply, Installation, Testing and Commissioning of LED Round Ring Light of 600 mm diameter with system power 44 W and colour temperature 4000K (neutral white). The luminaire shall provide soft and uniform illumination with a modern open circular design, suitable for contemporary interiors. The fitting shall have minimum 50,000 burning hours LED life, be energy-efficient and low-maintenance, and suitable for ceiling mounting, complete with driver, mounting accessories, wiring connections, testing and commissioning. etc as reqd |
| 84 | Supply, Installation, Testing and Commissioning of LED Round Ring Light of 1200 mm diameter with system power 87-90 W and colour temperature 4000K (neutral white). The luminaire shall provide soft and uniform illumination with a modern open circular design, suitable for contemporary interiors. The fitting shall have minimum 50,000 burning hours LED life, be energy-efficient and low-maintenance, and suitable for ceiling mounting, complete with driver, mounting accessories, wiring connections, testing and commissioning. etc as reqd |
| 85 | Design, fabrication, supplying, testing & commissioning of the following cubical Feeder Pillar (Double Door) of size not less than 1750 mm X 1950 mm X 375 mm deep, floor mounted ,dust & vermin proof made out of 2.0 mm thickness CRCA sheet suitable for 415Volts, 3Phase, 4wire, 50 Hz, AC supply system of IP-55 Ingress protection, incoming & outgoing MCCB/MCB ,suitable Aluminium busbar, including internal wiring, painting with powder coating paint etc, as per approved drawing as required. Panel board shall have provision of entering of cables from the Bottom only. The bus bar shall also be insulated with heat shrinkable sleeves,front doors of switch compartment shall have door lock arrangement of all outgoing etc as required :- i/c making the MS Angle stand made up of 50X 50 X6 mm size i/c grouting the legs in RCC foundation complete etc as reqd. |
| 86 | Incoming |
| 87 | 1 No.-250 A FP 25 KA breaking capacity MCCB with Thermal magnetic Based O/C & S/C Protection with Spreader Terminals & Extended Rotary Operating Mechanism |
| 88 | Metering |
| 89 | 1 No. 96X96 mm Digital Ammeter Meter |
| 90 | 1 No. 96X96 mm Digital Voltmeter Meter |
| 91 | 3 Nos 400/5Ampers CT's 10VA Class-1 |
| 92 | 3 Nos LED type R,Y,B incating Lamps |
| 93 | 3 nos, 6 Ampers MCB,s for voltmeter & Indicating Lamp circuit |
| 94 | Busbar |
| 95 | 1 set of 400 Ampers TPN Aluminium Bus Bar of suitable length covred with heat shrinkable insulated sleeve |
| 96 | Outgoing |
| 97 | 05 No.-125 Ampere 25 KA TP MCCB |
| 98 | 01 No.-110 Amper TP Power Contactor |
| 99 | 01 No.-Timer |
| 100 | MISCELLANEOUS:- |
| 101 | Nuts, Bolts, Washers, Ferul Numbers, Cable Ties, Tie Base, Copper PVC Control Wire, Power Wire, Copper Thimbles, Panel Locks, I-Hooks, PVC Tape, Insulators E-type, L-Type , Round Type, MCB Chanel, Pvc Chanel, Connector Chanel, Connectors, Foam Gaskit Etc. |
| 102 | Note- All MCCB's & MCBs shall be thermal magnetic release |
| 103 | Sub Head No. II (Audio Video System) |
| 104 | Supply installation, testing and commissioning of Video Conferencing System complete with codec is a modular video conferencing engine built for enterprise-grade large meeting environments, supporting both H.323 and SIP up to 6 Mbps bandwidth with IPv4/IPv6 dual-stack networking. It delivers people video resolutions up to 4K Ultra HD at 30 fps and 1080p at 60 fps, with support for H.264 AVC, High Profile, H.265 (HEVC), SVC, H.263, and RTV video standards. Content sharing is enabled via HDMI input and USB-C, with resolutions supported up to UHD (3840×2160). The codec integrates advanced audio processing, including automatic gain control, adaptive echo cancellation, noise suppression, Noise Block AI, Acoustic Fence, keyboard noise reduction, and Active Lip Sync. It supports a wide range of audio codecs, such as Siren 22, G.719, G.722.1 Annex C, G.722, G.711, and G.729A. Connectivity includes 2× HDMI outputs, 1× HDMI input, 1× USB-C, 2× USB-A, 1× line-in and line-out (3.5 mm), 1× RJ-45 for network (PoE+ IEEE 802.3at class 4/5/6), and an auxiliary LLN port for peripherals. The device is managed via the Poly Lens cloud and supports remote APIs (REST/CLI). It operates within 0–40 °C, with dimensions of approximately 248 × 152 × 35 mm and weight around 0.8 kg. |
| 105 | The smart PTZ camera integrates seamlessly with the G62 and features a 4K UHD (3840×2160) 8 MP image sensor, 12× optical zoom, and 16× digital zoom. It offers a wide field of view of up to 107° (diagonal), with motorized pan (±170°) and tilt (±30°) functions. Intelligent framing is enabled via Poly Director AI, supporting Presenter Tracking and Group Framing for automated meeting experiences. The camera provides flexible connectivity through USB-B and Ethernet (PoE+ 802.3at), with optional 12 VDC input. A dual-microphone beamforming array is integrated for localized audio pickup. Physical specifications include dimensions of approximately |
| 106 | 200 × 150 × 165 mm and a weight of 1.79 kg. The camera includes wall mount accessories and remote control, and it is certified for Microsoft Teams and Zoom Rooms. The Touch controller complements the system with a 10-inch high-resolution interactive display for meeting scheduling, room control, and call management. It includes multi-colored LED indicators for room status and a simplified single-cable installation for both power and data over Ethernet (PoE). The TC10 integrates with the Poly ecosystem and can be centrally managed through Poly Lens, enabling IT administrators to monitor, configure, and update devices remotely. Together, the Poly Studio G62 codec, Poly Studio E60 camera, and Poly TC10 controller deliver a complete modular video conferencing solution, providing 4K video, enterprise-grade audio, AI-powered intelligent camera tracking, and intuitive room control, making it suitable for medium-to-large conference rooms requiring reliable, scalable, and future-proof collaboration infrastructure |
| 107 | Providing and installation of HD VC Web Cloud License having 12 months subscription, compatible with existing video conferencing system, which allows hosting of up to 50 participants through web and mobile platforms. The license shall support unlimited 1:1 meetings, HD video conferencing, desktop and application sharing, eco mode operation, and other standard collaboration features. The license shall be fully integrated with the existing VC setup, enabling seamless connectivity, recording, and participant management. Includes activation, configuration, testing, demonstration, and documentation of license credentials, complete as required and as directed by the Engineer-in-Charge. |
| 108 | Sub Head No. III (CCTV System) |
| 109 | Supplying Installation Testing and Commissioning of 4MP IP IR Outdoor Bullet Camera having following specifications and features etc :-1) Signal System: PAL/NTSC, Signal to Noise Ratio: > 50 dB, Camera should display Camera title, Date & Time in live & recorded video2)Image Sensor: 1/2.8\\" or better progressive Scan CMOS get color image even at night condition(Minimum Illumination: 0.006 Lux@ F1.4, AGC ON, 0 lux with IR or better) True Day & Night High Performance Mechanical IR cut filter with auto switch, Integrated IR Source (Auto, Manual)- Inbuilt IR LED's with effective distance upto 50 meter or better and 30 meter for colour view in night, Imaging: 1/3s to 1/30000s electronic shutter support, Auto Gain Control , White Balance- Auto, Back Light Compensation, Multi zone Privacy Masking, HLC, Digital Watermarking.3) Compression (Minimum): Video:- H.265 or better, Audio:- G.711U/A, G.711Mu, G.726, AAC, G.7234) Wide Dynamic Range:- WDR (120dB or more)5) Digital Noise Reduction:- DNR (3D) On/Off |
| 110 | 6) Video Streaming & Frame Rates :- Triple streaming , configurable Main stream: 4MP (2560×1440)25/30fps Sub streams minimum: 720P@25/30 fps7) Image Setting: Rotate Mode, saturation, brightness, contrast, sharpness adjustable through client software or web browser, Edge Analytics: Tripwire, Intrusion, Motion Detection 8) Cyber Security: AES 256-bit Encryption, Configuration encryption, trusted execution, Digest, security logs, account lockout, video encryption, IP/MAC filtering, HTTPS, trusted upgrade.9) Onboard Storage: Camera should support built-in Micro SD/ SDHC/ SDXC Card slot upto 512 GB. It should be supplied with minimum 128GB memory Card.10) Recording Management: Format SD, overwrite, storage management, video to NAS device,11) Alarm Trigger : Motion/tampering detection; network disconnection detection; IP conflict detection; memory card state detection; memory space detection12)Network Protocol: SFTP, IPv6, IPv4, DNS,RTCP, NTP, RTP, HTTP, HTTPS, SNMP TCP/IP, PPPoE, NFS, UDP, ICMP, SSL, DHCP, SMTP, RTSPS, unicast,13) System Capability: ONVIF, Camera shall support open source VMS14) Ethernet: 1 RJ 45 10/100 Ethernet port15) Audio : It should support 1 x Built-In Mic and 1/1 Alarm In/ Out for External Mic. and Speakers as per site requirement.16) Power Input: The camera should support simultaneous dual power input—12 VDC (via power adapter) and PoE (802.3af)—to ensure continuous operation in the event of a failure in one power source. 17) Power Requirement: 12VDC/24 VDC/PoE (802.3af)/ePoE18) Housing/ Enclosure:- IP67 weather proof, IK10, Metallic body19) Operating Condition:- Ambient Temperature:- (- )05°C to 50°C, humidity 95% (max) (non-condensing) 20) IR life: 40000 hours or higher21) Video Bit rate: 32 KBPS - 8 MBPS or better22) Standards: BIS with ER, STQC Certified, CE, FCCand RoHS.4MP @ 25/30fps@1440P (2560x1440) Outdoor Bullet Camera with 2.7 to 4 mm ~12 to 13.5mm or better Varifocal Motorized lens |
| 111 | Supplying Installation Testing and Commissioning of following Channel Network Video Recorder (NVR) with camera licenses to record for all channels having specifications and features etc as mentioned below :1) Network Video Recorder Embedded/ Installed OS (Linux) along with Camera Licenses for number of channels of NVR to record per NVR and to provide a live view, storage and simultaneously Multi-channel playback of all IP, IR camera or more and must be ONVIF with minimum support of 256Mbps incoming Bandwidth. 2) NVR should support H.265 or better, H.264, MJPEG, MPEG4 support3) Must support 1 channel Input, 1 channel Output, RCA for Two-way Talk4) Intelligent auto power on when power resumes after power outage.5) Storage: It should support minimum 2 SATA Slots with 20TB capacity/ Slot.6) Connectivity Interface: 1 Nos. x 10/100/1000 Mbps Ethernet Ports, 1x RS485, 1x RS2327) Backup Interface : Its should have 2 Nosx USB port (1x USB3.0, 1xUSB2.0)8) Video Output Ports: 1x HDMI and 1 VGA9) Alarm Ports: It should have 4/1 Ch In/ Out ports to connect various type of external sensors and output devices like hooter/ Siren etc.10) Email & SMS Altert options: Option for SMS/ Email Alerts to minimum 5 designated mobile number for power failure, HDD failure, vandalism, tempring, network disconnection and panic11) Web & Mobile Application: Web, Mobile app ( For iPhone, iPad, Android Phone) for alerts and viewing.12) Protocols: HTTP, HTTPS, TCP/IP, IPv4, UDP, NTP, DHCP, DNS, SMTP, UPnP, DDNS, Alarm Server, IP Search, Multicast, Auto Registration, ONVIF (Profile T, Profile S, Profile G), CGI, SDK and OEM Cloud for remote monitoring without any public IP need.13) Standards: CE, FCC, RoHS and BIS Certified14) Power Supply : Should support 12VDC, 4Amp or AC100-240V, 50/60Hz Power supply. |
| 112 | 15) Operating Condition : Ambient Temperature (-5°C to 50°C), humidity 90% (max) (non-condensing)16) The VMS, NVR application shall support all the features & functionalities of the offered cameras. 17) VMS should consist of Base license and Channel Licenses. VMS should be provided with camera Licenses , with no dependency of VMS licenses by binding with the MAC address of the cameras to achieve the functionality.18) The NVR OEM shall be responsible for providing a mobile application compatible with both Android and iOS devices, enabling remote monitoring and playback of cameras/NVR footage. 19) The OEM must provide its own DDNS server hosted in India, eliminating the need for a public IP address for remote monitoring over the Internet.20) Must support Resolution: 7680x4320 (8K), 3840*2160, 1920×1080, 1280×1024,1280×720, 1024×76821) Must support recording resolution upto 32MP22) Must support Continuous, Alarm, Motion, Instant, Panic Recording Mode23) When alarm recording is enabled and an event occurs, you can click the alarm icon on monitoring page to view the alert details. The snapshot function is supported on monitoring and playback page24) The Network Video Recorder (NVR) shall be configured to send email whenever a system message is created or an alarm event occurs. The email server shall be a valid SMTP server. Each recipient email address shall be configured to receive any combination of critical, warning, or informational messages or alarm notifications. When an alarm occurs, the email message includes the NVR name, time of alarm and a list of camera that is configured to record upon alarm25) It should support Network Support: HTTP, TCP/IP, SMTP, DHCP, DNS, DDNS, FTP, NTP, UPnP, Multi IP Setting. Convert multiple recording files to one avi/MP4 file.26) General AI Based Search: Search Pictures by channel, time, event type, target classification (Fall Detection, People Approach Detection, People No. Exception Detection, People Staying Detection, Violence Detection.27) Alarm Notifications based on: Motion detection, video tampering, video loss, scene changing, PIR alarm, Camera external alarm, Face detection, face recognition, perimeter protection (intrusion and tripwire), ANPR, people counting, stereo analysis, crowd distribution, heat map, Disk Full, Storage Error, IP Conflict and abnormal behavior of fan28) Alarm Notification should be linked with Recording, snapshots, Camera external alarm output, buzzer, logs, presets and email. |
| 113 | 29) Built-In Artificial Intelligence: NVR should have built-in AI :- - 2 Channel face detection and recognition, - Minimum4 Channel perimeter protection, - Minimum 8 Channel Smart Motion Detection30) Face Recognition Database Capacity: It should support total Blacklist and Whitelist capacity of Minimum 20,000 Faces or more with Face Detection speed of 12 face images/sec.31) Face & Human Attributes Search: Search Pictures/ Video by Gender, age group, glasses, expressions, face mask, beard, Top color, top type, hat, bag, age, gender and umbrella.32) ANPR Capability: It should support ANPR Camera with License plate, plate color, vehicle body, vehicle model, vehicle logo, calling, seatbelt, vehicle registration location etc vehicle attributes.33) Alarm Notifications based on: Motion detection, video tampering, video loss, scene changing, PIR alarm, Camera external alarm, Face detection, face recognition, perimeter protection (intrusion and tripwire), ANPR, people counting, stereo analysis, crowd distribution, heat map, Disk Full, Storage Error, IP Conflict and abnormal behavior of fan,cybersecurity exception 34) Alarm Notification should be linked with Recording, snapshots, Camera external alarm output, buzzer, logs, presets and email.35) General AI Based Search: Search Pictures by channel, time, event type, target classification (Fall Detection, People Approach Detection, People No. Exception Detection, People Staying Detection, Violence Detection.36) Smart playback function: Should support smart search for the selected area in the video and smart playback to improve the playback efficiency37) VCA (Video Content Analytic): Should support multiple video contented analytics based on camera analytics16 Channel Network Video Recorder (NVR) having display split :- Main screen: 1/4/8/9/16, 2nd screen: 1/4/8/9/16 |
| 114 | Supplying, Installation, Testing and Commissioning following capacity Serveillance grade Hard Disk with upto 256MB/s Transfer Rate, 256 MB Cache, 7200 RPM Disk Speed, 3.5 inch form factor, SATA Interface, BSMI, ICES-003/NNB-003, CE, FCC, KC, Maghreb, RCM, UKCA, VCCI, CB-Scheme, TUV, UL Certifications. |
| 115 | 20 TB |
| 116 | Supplying, Installation, Testing and Commissioning of following size LED display (LED monitor) industrial grade with 3840x2160 resolution or better, USB playback, bluetooth and miracast connectivity, 4X HDMI 2.0, DP 1.2, HDR 10/10+, brightness: 500-nits or better, Video wall mode should be available, contrast ratio: 1200:1, OPS slot, viewing angle (H/V): 170°/ 170°, response time less than 12ms, Display control shall be on monitor screen and programmable with remote (remote shall be supplied with system), Key Board, Optical Mouse, etc. as required. |
| 117 | 32 inch or larger |
| 118 | Supplying, installation, Testing and commissioning of following capacity 24 port Layer 2 indoor Network Switch having features and specifications etc. as mentioned here under: At least 24 X RJ-45 Gigabit Ethernet Ports and additional 2 X 10G Base -T with 4 X SFP Ports with non-blocking architecture by having Switching capacity of min. 168Gbps and packet forwarding rate of 125Mpps or higher, 16K MAC table. Console Port, USB port, Stacking support of min. 8 units per stack. Internal dual AC Power supply, STP, RSTP, MSTP, BPDU Filter, BPDU Restriction, Min. 9K Jumbo Frame, LBD, IGMP Snooping V1/V2/V3, MLD Snopping V1/V2. IGMP /MLD Groups 1K or more, IPv4/IPv6 Loopback Interface, 16 L3 IP Interface, Ipv6 ND, VRRPv3, UDP Helper, ECMP. VLAN: 802.1Ǫ, Port based, Ǫ-in-Ǫ, Multicast VLAN, Protocol VLAN, VLAN Trunking, DHCP Snopping, Server, server Screening. RADIUS , TACACS+ Authentication, ǪoS: 802.1P, 8 queues per port, ǪoS : WRR, Strict+WRR, WRED, 802.1p. ACL: MAC based, IPv4C IPv6, TCP/UDP Port number, time based ACL, TFTP Client, NMP V1, v2c, v3, SNMP traps, RMON, DHCP server, relay, client, LLDP, LLDP-MED, OAM, Dying Gasp, 802.3ah, sflow, RIP, OSPF v2/v3, policy based route, SSL, SSH. 6 kV surge protection on all Gigabit Ethernet ports and on all GE RJ-45 access ports. Certifications: UL, CE, FCC, RoHS, MTCTE, OEM/Product must be on Trusted Telecom Portal of Department of Telecommunication, Government of India etc. complete as required. |
| 119 | 24 port PoE Layer 2 Network Switch with PoE Support of 370W or higher with each copper port supporting 802.3at PoE+ min |
| 120 | Supplying and fixing of following size Wall Mount Rack having Fixed Structure with 0.8mm CRCA Sheet, completely knocked-down condition (CKD) Shape, Vertical Mounting Rail 1.6 mm with 'U'Marking, Minimum 2 cable entry/exit provision at Top and bottom with rubber protection, Front 5mm Toughened Glass with lock, wall mounting kit, Powder coated Color- RAL- 7035, complied with UL & RoHS, 2 x 6 sockets 16A power distribution units, 3 numbers closed cable organizer, Hardware mounting screws packet of 20 x 1 number, etc. complete as required |
| 121 | 9 U Rack |
| 122 | Supplying, drawing, Installation, Testing and commissioning of armoured CAT6 UTP LSZH 23AWG Twisted Pair Cable in existing conduit/ on surface,/in ground etc. complete as required. |
| 123 | Sub Head No. IV (LAN System) |
| 124 | Supplying, Installation Testing and Commissioning of Managed 24 port L2 switch compatible for 19\\"rack mountable 1U having minimum 2GB RAM and 1 GB Flash memory, through put of minimum 90 NPPS, with retardant hot swappable power supply, modules/SFP, fan tray and should support MAC address 16000, stacking with dedicated stacking/MLAG ports of 80 GBPS stacking bandwidth, stack minimum 4 switches, Minimum 4 number of uplink interface , +. Power Output Capability 30W per port simultaneously, Minimum 48 x 1000Base-T (from Day 1), 4 x 1G/10G Uplink Interfaces. Should be loaded with 2X10Gbps MM SFPs from Day 1, should support protocol support SVIs (inter VLAN Routing), Static routing, OSPF, PIM, IEEE Standards 802.1d, 802.1s, 802.1w, 802.3ad, 802.3x, 802.1p, 802.1q, 802.3, 802.3u, 802.3ab, 802.3z, 802.3ae, 802.3 , minimum 500 IPV4 routes, 500 IPV6 routes with IPv6 ready logo, 802.1x authentication and accounting, IPv4 and IPv6 ACLs, Dynamic VLAN assignment, IP Source Guard, 802.1x, DHCP Option 82 or equivalent, Dynamic ARP Inspection (DAI), MAC Limiting, Sticky MAC or equivalent, Proxy ARP, IPv6 Security IPv6 RA Guard, IPv6 DHCP Guard/DHCP Snooping, IPv6 Neighbor Discovery Inspection and IPv6 Source Guard, Access List/ Firewall Filters, QoS, IPv6, SSHv2, SNMPv2c, SNMPv3, NTP, RADIUS and TACACS+, Jumbo frame, Telemetry & Visibility using Netflow /jflow/sflow, SPAN, RSPAN, management functionality using open APIs/ NETCONF/RESTCONF using https/ YANG/ XML data models for external tools to automatically provision network resources/configuration or through https, switch should be EAL3/ NDPP/ NDcPP certified under Common Criteria OR should satisfy the TEC -ER /IR/GR standard complete with 1 Years Guarantee and software/firmware support etc complete as required. |
| 125 | Supplying, Installation, Testing and commissioning of small form-Pluggable (SFP) for Network Switches. Must be hot Pluggable, RoHS Complaint, etc. complete as required. i) 10 G SFP + Single Mode/Multi Mode |
| 126 | Supplying and fixing of following size Wall Mount Rack having Fixed Structure with 0.8mm CRCA Sheet, completely knocked-down condition (CKD) Shape, Vertical Mounting Rail 1.6 mm with 'U'Marking, Minimum 2 cable entry/exit provision at Top and bottom with rubber protection, Front 5mm Toughened Glass with lock, wall mounting kit, Powder coated Color- RAL- 7035, complied with UL & RoHS, 2 x 6 sockets 16A power distribution units, 3 numbers closed cable organizer, Hardware mounting screws packet of 20 x 1 number, etc. complete as required |
| 127 | 9 U Rack |
| 128 | Supplying and drawing of UTP 4 pair CAT 6 LAN Cable in the existing surface/recessed Steel/ PVC conduit as required |
| 129 | 1 run of cable |
| 130 | Supply, Installation, Testing and Commissioning of Wi-Fi 6 (IEEE 802.11ax) Dual-Band Access Point supporting 2.4 GHz and 5 GHz bands, with internal embedded omni-directional antennas having minimum antenna gain of 3.5 dBi (2.4 GHz) and 5.5 dBi (5 GHz). The access point shall support PoE (IEEE 802.3af/at), Gigabit Ethernet uplink, multiple SSIDs, WPA2/WPA3 security, and shall be suitable for ceiling/wall mounting, complete with configuration, testing and commissioning. |
| 131 | Supplying, Installation, Testing and commissioning of following CAT6 Patch Cord should have ETL/UL verification program certificate for compliance with ANSI/TIA-568.2-D etc. complete as required |
| 132 | Copper Patch Cords of length 1m (3ft) |
| 133 | Copper Patch Cords of length 3m (10ft) |
| 134 | Supplying Installation Testing and Commissioning of 24 port Cat6 Patch Panel loaded. Must be of 1U height with clear label holders and white label with the panel 24 Ports Cat-6 Patch Panel should have ETL/UL verification program certificate for compliance with ANSI/TIA-568.2-D etc. complete as required |
| 135 | Sub Head No. V (IPBAX) |
| 136 | Supply, Installation, testing & Commissioning of IP based EPABX System of 4 P&T 16 Digital Lines 16 Analog lines & 16 IP extension with License with all standard feature complete with programming complete etc. as reqd. |
| 137 | Supplying, fixing, testing and commissioning of Hands Free Push Button Caller ID feature phone having incoming & outgoing memories, display, watch, alarm, hold facility etc. as required |
| 138 | Supplying, fixing, testing and commissioning of 12 Key Master Console phone with trunk display status line busy status, incoming & outgoing call facility etc. as required. |
| 139 | Supplying & Fixing of Main Distribution box with module etc as required |
| 140 | 50 Pairs |
| 141 | SITC of HDMI to HDMI cable 1.5 Mtr etc. as reqd. |
| 142 | SITC of HDMI to HDMI cable 5 Mtr etc. as reqd. |
| 143 | Sub Head No. VI (Solar Plant) |
| 144 | Supplying Installation, Testing and Commissioning of on-grid Solar Photovoltaic Power Plant conforming to various applicable standards BIS, IEC, MNRE guidelines, the Central Electricity Authority Regulations and CPWD Specifications as amended up to date, consisting of Mono/Poly Crystalline silicon solar cells module, net metering facility, necessary control, protections, earthing, cabling, mounting structure, junction boxes, power conditioning units, Real time online web interfaced Data Monitoring System, Distribution panels, grid connecting arrangement, conduits, pipes, cable trays and other accessories etc. as required. a) High Energy Efficiency Solar Photovoltaic Module of capacity 330 Wp or above, manufactured in India, conforming to IS 14286/IEC 61215, IS/IEC 61730- Part-1, IS/IEC 61730-Part-2. Solar Photovoltaic Module conversion efficiency shall not be less than 23% at STC with temperature coefficient of Pmax better than -0.30% per 0C. PV modules used in solar power plants/ systems must be warranted for their output peak watt capacity, which should not be less than 90% at the end of 10 years and 80% at the end of 25 years. Solar Modules shall be designed to operate in relative humidity upto 100% with temperature between -10 0C and +85 0C. Further, each PV module used in any solar power project must have Radio frequency identification tag with information such as name of manufacturer, month and year of manufacturing, country of origin (separately for Solar cell and module), I-V curve, Unique Serial No and Model No of the module, Wattage, Im, Vm and FF name of test lab issuing IEC certificate. |
| 145 | b)Power Conditioning Unit (PCU) of 350-800 V DC Input voltage range and 415 V AC, three phase, 4 wire, 50Hz +/- 2.5 Hz, output voltage suitable to generate AC with a variation of 10% at nominal voltage. Power with efficiency not less than 97%, total harmonic distortion less than 3% and suitable for ambient temperature from 0 to 50 0C, Minimum IP-65 for outdoor and Minimum IP 21 for indoor, Built-in meter and data logger, MPPT, switching devices IGBT/MOSFETs and controller Microprocessor /DSP. PCU/inverter shall be capable of complete automatic operation including wake-up, synchronization & shutdown. The PCU shall be able to withstand unbalanced load conforming to IEC standard with shutdown/standby mode. It must be provided with grid islanding along with manual disconnect pole isolation switch besides automatic disconnection. Minimum protections: Mains Under / Over Voltage, Over current, Over/Under grid frequency, Over temperature, Surge voltage induced at output due to external source, Short-circuit, Lightening, Anti Islanding (for grid synch. Mode) and other protections as per applicable standards. LCD/LED display of minimum parameters: DC input voltage, DC current, AC Voltage and current (all 3 phases, in case of 3 phase), Instantaneous & cumulative AC output power, Daily DC energy produced and other parameters applicable standard. Communication interface RS 485 / RS 232 |
| 146 | c) Module mounting structure: The roof top solar plant generation units shall be installed by using supporting Aluminium/Galvanized MS structure (mass of zinc coating shall be as per IS4759 ) having minimum head room clearance of 2.4 meter above the terrace level / ground level. The mounting structure would be designed to sustain wind load and seismic parameter of the site of installation. All the structure shall be design as per applicable BIS code and the material shall also confirm the applicable BIS Code. Structural material shall be corrosion resistant and electrolytically compatible with the materials used in the module frame, its fasteners, nuts and bolts. The suitable arrangements for maintenance and cleaning shall be provided. |
| 147 | d) Real time online web interfaced Data Monitoring System complete with accessories for various parameters such as Solar Irradiance, temperature, AC Output Voltage and current, Output Power, Power factor, DC Input Voltage and Current, Time Active, Time disabled, Time Idle, Power produced and other parameters as per standard practices. |
| 148 | e) Array junction box & Main junction box with IP 65 protection and termination arrangement for incoming and outgoing cable along with glands, lugs and other accessories etc. as required. Each junction box shall be made of GRP/FRP/Powder Coated Aluminium /cast aluminium alloy with full dust, water & vermin proof arrangement with High quality Suitable capacity Metal Oxide Varistors(MOVs) (semiconductor diode with resistant applied voltage)/ surge arrestors and suitable Reverse Blocking Diodes, isolation switches isolate the DC input to Inverter, copper bus bar etc. |
| 149 | f) Lightning, surge voltage protection, earthing protection and grid islanding.g) Cables: Connections & Interconnections by required size IR/UV protected XLPE insulated copper conductor 1.1 kV grade armored power and control cables(ISI Marked) along with supplying & fixing of necessary channel/conduit, GI cable trays, supports, lugs, thimble and other accessories etc. as required. h) DC Distribution Board And AC Distribution Panel Board: IP65, free standing, metal cladded, having copper bus bar, having required protection and control gears, connection-interconnection, etc. as required. Please Enable Macros to View BoQ information |
| SR No | FileName | File Description |
| 1 | Click here to download tender document | Tender Documents |
| 2 | Click here to download tender document | Tender Documents |
| 3 | Click here to download tender document | Tender Documents |
| 4 | Click here to download tender document | Tender Documents |
Copyright © 2026 · All Rights Reserved. Terms of Usage | Privacy Policy
For Tender Information Services Visit : TenderDetail