| 1 | Supply of Prefabricated E-House Container | Supply of Prefabricated Containerized Substation E-House having IP54 enclosure with 2 hr fire rated thermal insulation sandwich panel suitable for accommodating HT LT switchgear panel transformers battery bank battery charger and APFC panels as per technical specification |
| 2 | Installation of E-House Container | Installation of the prefabricated containerized substation E-House at site including all necessary activities for proper placement and fixing as per OEM drawings and instructions of Engineer in charge |
| 3 | Supply of 6.6kV HT VCB GIS Switchgear Panel | Supply of 6.6kV Eco-Friendly Indoor type green GIS VCB Switchgear Panel with maximum system voltage 12kV 500MVA rupturing capacity comprising 2 incomer 1 buscoupler 2 outgoing feeders 2 transformer feeders and 2 set bus PT as per technical specification |
| 4 | Installation Testing Commissioning of HT Switchgear Panel | Installation testing and commissioning of the 6.6kV HT GIS VCB Switchgear Panel inside the E-House as per technical specification and in the presence of MbPA representative |
| 5 | Supply of 24V DC SMF VRLA Battery Bank | Supply of 24V DC SMF-VRLA Battery Bank of suitable load rating for HT and LT switchgear panels with minimum 1 hour backup including battery stand inter-battery wiring terminal connectors accessories and BHMS as per technical specification |
| 6 | Installation Testing Commissioning of Battery Bank | Installation testing and commissioning of 24V DC SMF-VRLA Battery Bank inside the E-House as per technical specification and in the presence of MbPA representative |
| 7 | Supply of Float and Float Cum Boost Charger | Supply of Float and Float-Cum Boost Charger suitable for battery bank including incoming and outgoing cables wires connection in HT switchgear and control panels with full wave rectification for 440V 3 phase 4 wire 50Hz AC input supply as per technical specification |
| 8 | Installation Testing Commissioning of Float Cum Boost Charger | Installation testing and commissioning of Float and Float cum Boost Charger inside the E-House as per technical specification and in the presence of MbPA representative |
| 9 | Supply of Indoor LT Switchgear Panel | Supply of IEC 61439 compliant OEM LT panel with TPN 2000A copper busbar 50KA 1 sec STC comprising 2 incomer ACB 1 buscoupler ACB 10 outgoing ACB 5 MCCB 400A 2 MCCB 250A 2 MCCB for APFC and 5 MCB outgoings as per technical specification |
| 10 | Installation Testing Commissioning of LT Switchgear Panel | Installation testing and commissioning of LT Switchgear Panel inside the E-House as per technical specification and in the presence of MbPA representative |
| 11 | Supply of 1000KVA Dry Type Transformer 2 Sets | Supply of 1000 KVA 6.6KV to 0.433KV DYN-11 copper wound AN cooling cast resin dry type indoor transformer IP00 with off load tap links WTI scanner class F insulation HT and LT cable boxes and standard accessories as per ECBC 2021 2 sets |
| 12 | Installation Testing Commissioning of Dry Type Transformer | Installation testing and commissioning of 1000KVA dry type transformer at site inside the E-House as per technical specification and in the presence of MbPA representative 2 numbers |
| 13 | Supply of Smart Local Monitoring HMI System | Supply of wall mounted Smart Local Monitoring HMI Box with Windows 10 IOT Intel Core i5 processor 8GB RAM 64GB memory 15.6 inch touch screen IEC 61850 Client Master application software for complete substation monitoring as per technical specification |
| 14 | Installation Testing Commissioning of Smart Monitoring System | Installation testing and commissioning of Smart Local Monitoring HMI System including integration with protection relays via IEC 61850 Ed 2 LAN as per technical specification and in the presence of MbPA representative |
| 15 | Supply of APFC Panel 200 KVAr 2 Sets | Supply of cubicle type free standing floor mounted APFC Panels of 200 KVAr capacity conforming to IEC 61439 with MCCB incomer capacitor banks detuned reactors APFC relay and all accessories as per technical specification 2 sets |
| 16 | Installation Testing Commissioning of APFC Panel | Installation testing and commissioning of APFC panels inside the E-House as per technical specification and in the presence of MbPA representative 2 numbers |
| 17 | Supply of Fire Alarm Detection System | Supply of fire detection and alarm system comprising fire alarm control panel multi-area detection module multi sensor heat and smoke detectors break glass manual call points indoor and outdoor alarm hooters with AC shutdown interlock as per technical specification |
| 18 | Installation Testing Commissioning of Fire Alarm System | Installation testing and commissioning of fire detection and alarm system as per technical specification and in the presence of MbPA representative |
| 19 | Supply of Fire Extinguishers | Supply of fire extinguishers as per IS 3034-1993 of suitable capacity and type for the E-House substation application complete with all accessories and mountings |
| 20 | Installation of Fire Extinguisher | Installation of fire extinguishers at designated locations inside the E-House as per directions of Engineer in charge |
| 21 | Supply of Split Air Conditioners with Controller | Supply of minimum 2 nos 2 Ton copper coil inverter split air conditioners of heavy duty industrial type along with AC controller for E-House control room as per technical specification similar to O General Hitachi Samsung or equivalent |
| 22 | Installation Testing Commissioning of Air Conditioners | Installation testing and commissioning of split air conditioners and AC controller inside the E-House as per technical specification and in the presence of MbPA representative |
| 23 | Supply of HT LT Touch Proof Termination Kits | Supply of suitable type touch proof termination kits as required for HT and LT power and control cables to and within the container equipment as per technical specification |
| 24 | Installation Testing Commissioning of Termination Kits | Installation testing and commissioning of HT and LT touch proof termination kits inside the E-House as per technical specification and in the presence of MbPA representative |
| 25 | Supply of UPS with Battery | Supply of 600VA UPS system along with SMF-VRLA battery conforming to JISC-8702 Pt 1 2 and 3 with single phase 230V AC 50Hz output for E-House emergency illumination complete with all accessories |
| 26 | Installation Testing Commissioning of UPS | Installation testing and commissioning of UPS system with battery inside the E-House as per technical specification and in the presence of MbPA representative |
| 27 | Supply and Making of Chemical Earthing Pits | Supply and making of chemical earthing pit using chemical earth electrode with minimum 25 Kg chemical powder cement concrete chamber 500x500x200mm CI RCC cover earthing rod 17.2mm dia 3 mtr long copper bonded 250 microns as per IS 3043-2018 and IEC 62561 16 numbers |
| 28 | GI Earthing Flat 50mm x 6mm for Substation Equipment | Supply and laying of galvanized MS earthing flat 50mm x 6mm for HT LT APFC battery charger and transformer body earthing of substation equipment as per technical specification |
| 29 | Copper Earthing Flat 50mm x 6mm for Transformer Neutral | Supply and laying of copper earthing flat 50mm x 6mm for transformer neutral earthing of the substation as per technical specification |
| 30 | Supply of HT XLPE Cable 3Cx240sqmm to Tank Bunder SS | Supply and delivery of XLPE insulated PVC sheathed armoured screened cable 3C x 240 sqmm 6.6kV UE 11kV E grade aluminium conductor as per IS 7098 Part 2 for 6.6kV feeder from Workshop Substation to Tank Bunder Substation |
| 31 | Supply of HT XLPE Cable 3Cx240sqmm to PV Dock SS | Supply and delivery of XLPE insulated PVC sheathed armoured screened cable 3C x 240 sqmm 6.6kV UE 11kV E grade aluminium conductor as per IS 7098 Part 2 for 6.6kV feeder from Workshop Substation to PandV Dock Substation |
| 32 | Supply of HT XLPE Cable 3Cx240sqmm to Central SS | Supply and delivery of XLPE insulated PVC sheathed armoured screened cable 3C x 240 sqmm 6.6kV UE 11kV E grade aluminium conductor as per IS 7098 Part 2 for 6.6kV feeder from Workshop Substation to Central Substation CSS |
| 33 | Supply of HT XLPE Cable 3Cx240sqmm to RO-RO PAX SS | Supply and delivery of XLPE insulated PVC sheathed armoured screened cable 3C x 240 sqmm 6.6kV UE 11kV E grade aluminium conductor as per IS 7098 Part 2 for 6.6kV feeder from Workshop Substation to RO-RO PAX Terminal Substation |
| 34 | Tracing and Cutting of Existing Buried HT Cable Feeder | Tracing out existing buried 6.6kV HT cable laid feeder identification of existing feeder cable puncture and cutting in presence of MbPA representative contractor to arrange all necessary testing kits required for the same |
| 35 | Supply of Straight Through HT Cable Joint Kit | Supply of straight through joint for HT cable 3C x 240 sqmm XLPE insulated armoured aluminium conductor 11kV E 6.6kV UE grade using heat shrinkable Raychem make jointing kit with ferrules tape etc complete in all respect |
| 36 | Making of HT Cable Straight Through Joint | Making of HT cable 6.6kV UE 11kV E grade straight through jointing work for cable 3C x 240 sqmm XLPE to XLPE in the presence of MbPA representative |
| 37 | High Potential Testing of HT Cable Joints | Carrying out necessary High Potential Test before and after making joints using calibrated testing equipment with complete test reports in the presence of MbPA representative |
| 38 | Phase Sequence Testing and Commissioning of HT Cable | Carrying out necessary Phase Sequence test using calibrated testing equipment with complete test reports and commissioning the cable in all respect in the presence of MbPA representative |
| 39 | Supply of Straight Through Transition HT Cable Joint Optional | Supply of straight through transition joint for HT cable 3C x 240 sqmm XLPE insulated armoured aluminium conductor 11kV E grade using heat shrinkable Raychem make jointing kit with ferrules tape etc complete in all respect Optional |
| 40 | Making of HT Cable Transition Joint PILC to XLPE Optional | Making of HT cable 6.6kV UE 11kV E grade straight through transition jointing work for cable 3C x 240 sqmm PILC to XLPE in the presence of MbPA representative Optional |
| 41 | Excavation of HT Cable Trench in Soft Soil or Asphalt | Excavating suitable trench for HT cable in any type of soft soil or asphalt including cleaning cable trenches tentative size 1.0 mtr W x 1.2 mtr D x 300 mtr L |
| 42 | HT Cable Trench Excavation in Concrete Road Optional | Excavating suitable trench for HT cable in concrete or stone road including cleaning cable trenches tentative size 1.0 mtr W x 1.2 mtr D x 85 mtr L Optional |
| 43 | Laying of HT XLPE Cable 3Cx240sqmm in Excavated Trench | Laying of incoming and outgoing 3C x 240 sqmm XLPE aluminium armoured cable in excavated cable trench at depth 1200mm including cleaning dressing providing screened sand and RCC tiles engraved MbPA 6600 Volts as per drawing |
| 44 | Laying of HT Cable in RCC Pipe or Existing Duct | Laying of HT cable in RCC pipe HDPE pipe existing duct or CC trench including all necessary activities as per specification |
| 45 | Supply of 200mm Dia RCC Pipe NP2 Class with Collars | Supply of RCC pipe 200mm dia NP2 class of standard length with collars including cement concreting closing ends of pipes after passing cable across road culverts drains etc |
| 46 | Laying of RCC Pipe and Fixing of Collars | Laying of RCC pipe 200mm dia NP2 class and fixing of collars at site including all necessary activities as per specification |
| 47 | Supply of LT XLPE Cable 3.5Cx400sqmm to FP 6A | Supply and delivery of 3.5C x 400 sqmm aluminium conductor XLPE insulated PVC sheathed 1100 volts grade armoured cable heavy duty conforming to IS 1554 7098 Part-I for outgoing to Feeder Pillar 6A |
| 48 | Supply of LT XLPE Cable 3.5Cx400sqmm to FP 11 | Supply and delivery of 3.5C x 400 sqmm aluminium conductor XLPE insulated PVC sheathed 1100 volts grade armoured cable heavy duty conforming to IS 1554 7098 Part-I for outgoing to Feeder Pillar 11 |
| 49 | Supply of LT XLPE Cable 3.5Cx300sqmm to FP 1A | Supply and delivery of 3.5C x 300 sqmm aluminium conductor XLPE insulated PVC sheathed 1100 volts grade armoured cable heavy duty conforming to IS 1554 7098 Part-I for outgoing to Feeder Pillar 1A |
| 50 | Supply of LT XLPE Cable 3.5Cx300sqmm to FP 3 | Supply and delivery of 3.5C x 300 sqmm aluminium conductor XLPE insulated PVC sheathed 1100 volts grade armoured cable heavy duty conforming to IS 1554 7098 Part-I for outgoing to Feeder Pillar 3 |
| 51 | Supply of LT XLPE Cable 3.5Cx300sqmm to FP 4 | Supply and delivery of 3.5C x 300 sqmm aluminium conductor XLPE insulated PVC sheathed 1100 volts grade armoured cable heavy duty conforming to IS 1554 7098 Part-I for outgoing to Feeder Pillar 4 |
| 52 | Supply of LT XLPE Cable 3.5Cx300sqmm to FP 5 | Supply and delivery of 3.5C x 300 sqmm aluminium conductor XLPE insulated PVC sheathed 1100 volts grade armoured cable heavy duty conforming to IS 1554 7098 Part-I for outgoing to Feeder Pillar 5 |
| 53 | Supply of LT XLPE Cable 3.5Cx300sqmm to FP 6B | Supply and delivery of 3.5C x 300 sqmm aluminium conductor XLPE insulated PVC sheathed 1100 volts grade armoured cable heavy duty conforming to IS 1554 7098 Part-I for outgoing to Feeder Pillar 6B |
| 54 | Supply of LT XLPE Cable 3.5Cx300sqmm to FP 6C | Supply and delivery of 3.5C x 300 sqmm aluminium conductor XLPE insulated PVC sheathed 1100 volts grade armoured cable heavy duty conforming to IS 1554 7098 Part-I for outgoing to Feeder Pillar 6C |
| 55 | LT Cable Trench Excavation in Asphalt Paver Area | Excavating suitable trench for LT cable in asphalt soil or paver block footpath with curb stone including cleaning cable trenches tentative size 0.8 mtr W x 0.9 mtr D x 700 mtr L |
| 56 | Laying of LT Cable 3.5Cx300 or 400sqmm in Excavated Trench | Laying of incoming and outgoing 3.5C x 300 or 400 sqmm LT XLPE armoured cables in excavated cable trench including dressing providing screened sand and red bricks as per specification |
| 57 | Laying LT Cable 3.5Cx300 or 400sqmm in Pipe or Duct | Laying of incoming and outgoing 3.5C x 300 or 400 sqmm LT XLPE armoured cables in RCC pipe HDPE pipe existing duct CC trench or saddling on wall as per specification |
| 58 | Supply of LT XLPE Cable 3.5Cx70sqmm to Old CME Building | Supply and delivery of 3.5C x 70 sqmm aluminium conductor XLPE insulated PVC sheathed 1100 volts grade armoured cable for outgoing to old CME building SBI from FP No 4 Nirman Bhavan |
| 59 | Excavation of LT Cable Trench for 70sqmm Cable | Excavating suitable trench for LT cable in asphalt soil or paver block footpath with cup stone including cleaning cable trenches tentative size 0.8 mtr W x 0.9 mtr D x 150 mtr L |
| 60 | Laying of LT Cable 3.5Cx70sqmm in Excavated Trench | Laying of incoming and outgoing 3.5C x 70 sqmm LT XLPE armoured cables in excavated cable trench including dressing providing screened sand and red bricks as per specification |
| 61 | Laying of LT Cable 3.5Cx70sqmm in RCC Pipe or Duct | Laying of incoming and outgoing 3.5C x 70 sqmm LT XLPE armoured cables in RCC pipe HDPE pipe existing duct CC trench or saddling on wall as per specification |
| 62 | Cable Termination Material for 3.5Cx70sqmm LT Cable | Supply of material for both cable end termination and connection with double compression brass glands and aluminium lugs for 3.5C x 70 sqmm XLPE PVC cable 1100 volts grade 2 ends |
| 63 | Cable Termination Installation for 3.5Cx70sqmm LT Cable | Installation of both cable end termination and connection with double compression brass glands and aluminium lugs for 3.5C x 70 sqmm XLPE PVC cable 1100 volts grade 2 ends |
| 64 | Cable Termination Material for 3.5Cx300sqmm LT Cable | Supply of material for both cable end termination and connection with double compression brass glands and aluminium lugs for 3.5C x 300 sqmm XLPE PVC cable 1100 volts grade 6 ends |
| 65 | Cable Termination Installation for 3.5Cx300sqmm LT Cable | Installation of both cable end termination and connection with double compression brass glands and aluminium lugs for 3.5C x 300 sqmm XLPE PVC cable 1100 volts grade 6 ends |
| 66 | Cable Termination Material for 3.5Cx400sqmm LT Cable | Supply of material for both cable end termination and connection with double compression brass glands and aluminium lugs for 3.5C x 400 sqmm XLPE PVC cable 1100 volts grade 2 ends |
| 67 | Cable Termination Installation for 3.5Cx400sqmm LT Cable | Installation of both cable end termination and connection with double compression brass glands and aluminium lugs for 3.5C x 400 sqmm XLPE PVC cable 1100 volts grade 2 ends |
| 68 | E-House Foundation Civil Work | Suitable quantity dimensions and grade of concrete for E-House foundation columns including soil excavation as per OEM design drawings and structural design approved by BMC registered structural engineer |
| 69 | E-House Shed Supply and Installation | Supply and installation of E-House shed including foundation columns I-beams angles and covering sheets as per design drawings approved by BMC registered structural engineer |
| 70 | Rubble Packing 250mm Thick for Cable Trench Reinstatement | Providing and laying approved quality rubble packing 250mm thick hand set including filling interstices with stone chips grit stone dust watering and consolidation as specified and as directed |
| 71 | Stone Metal 40-90mm Layer for Trench Reinstatement | Providing and laying 40mm to 90mm size stone metal of approved quality to required thickness in layers not exceeding 120mm consolidated with roller including filling interstices with grit stone dust sand as directed |
| 72 | Water Bound Macadam WBM Layer for Trench Reinstatement | Providing and laying water bound macadam WBM layer 100mm consolidated thickness with 40 to 63mm metal consolidated with roller including watering blending with sand stone dust grit brick powder as specified |
| 73 | M10 Grade RMC Concrete Levelling Course | Providing and laying M10 grade ready mix cement concrete from approved RMC plant in levelling course of required thickness including transit mixer form work plate vibrator curing etc as specified |
| 74 | M40 Grade RMC Concrete Road Pavement | Providing and laying M40 grade ready mix cement concrete from approved RMC plant in road pavement bays including form work power driven screed plate and needle vibrators brooming vatas bitumen curing as specified |
| 75 | Interlocking Paver Blocks 100mm Thick | Providing and laying approved coloured cement concrete interlocking paver blocks 100mm thick with sand bedding minimum 50mm and filling joints with fine sand as directed |
| 76 | Asphaltic Macadam Bitumen Grade 60 70 Regulating Course | Providing and laying hot pre-mixed asphaltic macadam Bitumen grade 60 70 with anti-stripping agent 0.5 percent by weight in regulating course and rolling with 8 to 10 tonne road roller as specified payment by weight |
| 77 | Asphaltic Concrete Wearing Course Bitumen Grade 60 70 | Providing and laying hot pre-mixed asphaltic concrete wearing course Bitumen grade 60 70 with anti-stripping agent 0.50 percent by weight of required thickness and rolling with 8 to 10 tonne road roller as specified payment by weight |
| 78 | Transporting Surplus Excavated Material Outside MbPA Estate | Transporting surplus excavated material stones debris kutchra from MbPA estate including loading and taking away materials anywhere outside MbPA estate as directed |
| 79 | Dismantling of Existing Workshop Substation Equipment | Dismantling of existing HT LT panel transformers APFC panel battery charger and bank cables and cable terminations of existing workshop substation and shifting removed electrical equipment to MbPA store as per instructions of Engineer |