| 1 | Supply, installation, testing & commissioning of 3 phase, 50Hz, 11KV, 800Amp, 26.3KA/3Sec. incoming VCB panel with copper busbarfor indoor substations. The VCB should be floor mounted trolley type horizontal isolation, horizontal draw out, type Breaker confirming to IEC-62271-100 & Panel as per IEC- 6227I-200, & IEC-60694 as amended up to date., (As per Complete Item No. 1 of the DNIT) |
| 2 | DSR item No.5.9 Supplying and laying 25 mm X 5 mm G.I strip at 0.50 metre below ground as strip earth electrode, including connection/ terminating with G.I. nut, bolt, spring, washer etc. as required. (Jointing shall be done by overlapping and with 2 sets of G.I. nut bolt & spring washer spaced at 50mm) |
| 3 | DSR item No.23.4.1 supplying and making in door cable end termination The heat shrink able jointing kit complete with all accessories including lugs suitable for following size of 3core,XLPEaluminiumconductorcableof11KV grade as required: |
| 4 | 50/70sq.mm |
| 5 | S/E of 4 nos. sand buckets of 10 Ltr. Capacity each made out of 24 Gauge G.I sheet. The buckets with sand shall be hanged on Suitable size of angle iron stand fabricated out of 1 ¼ x 1 ¼ x1/8” angle iron having hooks for hanging the buckets in two rows. The job includes the cost of painting with two coats of red paint of superior quality after one coat of primer on buckets and stands to complete the job up to the entire satisfaction of the Engineer–in–charge. |
| 6 | Supply of Erection of medium size first aid box made of 16 gauge MS sheet of size 14”x7”x5” with 6 wound dressings, 3 burn dressings, 13 gms absorbent cotton wool, one dressing scissors, one bottle of spirit of sal volatile, 1 tube of burn ointment (Burnol) tablets of aspiring, 1 No. artificial respirator. |
| 7 | Supply and Erection of shock treatment chart written in Hindi and English and local language duly framed in wood frame with glass complete as required as per India Electricity Act. (Safety rules). |
| 8 | S/E rubber mat of size 6’x3’ 12mm thick (ISI marked) Wide of superior quality and of approved make as approved by the Engineer –in- Charger /EC to be laid on floor in HT room in Front of panels and transformers. |
| 9 | Supply and erection of M.S. sheet danger notice plate at least 2 mm thick. |
| 10 | Supply and Erection of Fire Extinguishers ISI marked duly erected/ hung on wall with hooks including the cost of hooks with all material &labour required to complete the job in all respect upto the entire satisfaction of the Engineer-in-charge of work. |
| 11 | CO2 type of 9 Kg capacity fire extinguishers conforming to IS. |
| 12 | Supplying and laying of one number 11KV Grade XLPE insulated, PVC sheathed, armoured, Aluminium conductor cable confirming to IS 7098/Part 2/1985 with latest amendments of earthed system of following sizes to be laid in the existing HUME/RCC/DWC/GI Pipe etc as required at site to the entire satisfaction of the Engineer-in-Charge of work. The cable should be of Polycab/ RPG/ Unistar (Universal)/ Havells/ Finolex/ R.R. Kabel make only. |
| 13 | Size 50 Sq. mm 3 core |
| 14 | S/E of M.S Chequred plate 5mm thick to cover the loose cables trench. The M.S Chequred plate shall be 2’ width, So as to cover the all trench as per reqd. at site of work. (As per Complete Item No. 11 of the DNIT). |
| 15 | S/E of Angle iron frame of the size 50 mm x 50 mm x 6 mm at the top of the trench. The cost including the cost of welding of angle frame and petty including required to complete the job as per satisfaction of EIC. |
| 16 | Providing and fixing of insulated continuous line sand witch PUF wall panels of 50 mm thickness of make Jindal meetc / Lioyd / Satmax / Sintex / Rinac (Confirming to IS12436) having pre-painted galvanized 0.5 mm thick iron sheet on both sides having polyurethane foam of density 42 Kg/cum in between these sheets. (As per Complete Item No. 13 of the DNIT). |
| 17 | Providing and fixing of insulated continuous line sand-witched PUF ceiling panels of 30 mm thickness of make Jindal meetc / Lioyd / Satmax / Sintex / Rinac (Confirming to IS12436) having pre-painted galvanized 0.5 mm thick iron sheet on both sides having polyurethane foam of density 42 Kg/cum in between these sheets.(As per Complete Item No. 14 of the DNIT). |
| 18 | DSR Item No. 10.2 (Civil)Structural steel work riveted, bolted or welded in built up sections, trusses and framed work, including cutting, hoisting, fixing in position and applying a priming coat of approved steel primer all complete. |
| 19 | S/E/T/C of Stationary Battery charger set comprising of 2 Nos. 12volts 100AH maintenance free batteries of make Exide, Amaron duly houses in cabinet of size (LxWxD) 36”x24”x18” made of 14 gauge CRCE sheet having 4 Nos. legs of 8” length made of M.S.,(As per Complete Item No. 16 of the DNIT). |
| 20 | The battery charger should be suitable for boost mode and trickle mode with display of input & output voltage and current. |
| 21 | Suitable Miniature circuit breaker shall be provided for protection at input supply and output of the battery charger. |
| 22 | Dehydration of Transformer oil. The job includes the cost of labour and material required to complete the job. |
| 23 | Supply and filling of transformer oil (Dehydrate oil) in the existing transformer. The job includes the cost of all petty material require to complete the job. Please Enable Macros to View BoQ information |