| 1 | Item Rate BoQ BoQ_Ver3.0 Item Rate Normal INR Only INR Select, Excess (+), Less (-) Less (-) Tender Inviting Authority: HQ CWE Jhansi Name of Work: REPAIR / RENEWAL INTERNAL ELECTRIFICATION, SUBMAIN WIRING AND RENEWAL TO MCB DB’S SERVICE CONNECTION UNDER GE JHANSI Contract No: CA NO CWE/JHA/J/TOKEN/13 OF 2026-27 Bidder Name : PRICE SCHEDULE(This BOQ template must not be modified/replaced by the bidder and the same should be uploaded after filling the relevent columns, else the bidder is liable to be rejected for this tender. Bidders are allowed to enter the Bidder Name and Values only) NUMBER # TEXT # TEXT # NUMBER # TEXT # NUMBER NUMBER TEXT TEXT # NUMBER # TEXT# TEXT # NUMBER # NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER # NUMBER # TEXT TEXT NUMBER # NUMBER # DATE NUMBER # NUMBER # TEXT # Sl No. Item Description Item Code / Make Quantity Units Estimated Rate Addition / Deduction Addition / Deduction Values Currency Convertion against each Item Quoted Currency in INR / Other Currency BASIC RATE In Figures To be entered by the Bidder Rs. P Excise Duty VAT Freight Charges ( Unloading & Stacking) Any Other Taxes/Duties/Levies Other Taxes 2 IIIrd Party i.e DGS&D / RITES etc Inspection Charges @0.34%+Service Tax Less for Cenvat Credit,if any respect of Supplies Under full Excise Duty Category TOTAL AMOUNT Without Taxes TOTAL AMOUNT With Taxes TOTAL AMOUNT In Words |
| 2 | Taking down carefully existing copper/aluminium point wiring (light, fan, socket or power) complete of any description including fitting such as switches, ceiling roses, pendants, tube light fitting, regulators, sockets, bell push and call bell wooden boards, laminated sheets from sunken boxes, boards, shades light fitting etc and making good the disturbed surfaces of walls, floors, ceiling etc with cement plaster, putty and paint to match with the existing surface complete all as specified and as directed. |
| 3 | M&L for Point wiring with 1.5 Sqmm FRLSH insulated, unsheathed, multistranded, 1100 Volts grade copper conductor cable single core conforming to IS:694 along with one run of 1.5 Sqmm FRLSH insulated copper conductor cable green in colour for continuous earthing drawn through and including medium grade rigid PVC conduit conforming to IS:9537 (Pt-III) and its all accessories/junction boxes/ inspection covers etc of suitable size but not less than 20mm(OD), concealed in wall/ floor etc including provision of pressed steel terminal box with earth dolly of suitable size concealed in wall and covered with 3 mm thick phenolic laminated hylam sheet fixed with brass/GI screws for mounting switches, sockets, fan regulator, etc. complete all as specified and as directed for the following points :- |
| 4 | One light / ceiling fan / exhaust fan / call bell point controlled by one switch |
| 5 | One 6A socket point controlled by one switch on independent board |
| 6 | One 6A socket point controlled by one switch on same board |
| 7 | All as per Ser item No 2.00 here-in-before but one 16A socket point controlled by one 16A switch on independent board with 2.5 sqmm wires. |
| 8 | All as per Ser item No 2.00 here-in-before but with 2.5 Sqmm one 16A socket point controlled by one 16A switch on independent board but just below / above the existing socket points / DBs up to one meter distance in the same vertical plane. |
| 9 | All as per Ser item No 2 here-in-before but with 4 sq mm FRLSH copper wire with 4 Sqmm FRLSH copper earth wire for one 16 Amp socket point controlled by one 16 Amp switch on independent board. |
| 10 | M&L for point wiring for modular fittings complete with 1.5 Sqmm FRLSH insulated, unsheathed, multistranded, 1100 Volts grade copper conductor cable single core conforming to IS:694 along with one run of 1.5 Sqmm FRLSH insulated copper conductor cable green in colour for continuous earthing drawn through and including medium grade rigid PVC conduit conforming to IS:9537 (Pt-III) and its all accessories/junction boxes/ inspection covers etc of suitable size but not less than 20mm(OD), concealed in wall/ floor etc including provision of modular cover plates with frames and 1.50 sq mm PVC insulated unsheathed stranded copper conductor (FRLSH) cable for common earth and connecting to earth dolly all as specified and directed . (Note- rates of chasing/cutting & making goods shall be included in the unit rate) :- |
| 11 | One light / ceiling fan / exhaust fan / call bell point controlled by one switch |
| 12 | One 6A socket point controlled by one switch on independent board |
| 13 | One 6A socket point controlled by one switch on same board |
| 14 | All as per Ser item No 3.00 here-in-before but one 16A socket point controlled by one 16A switch on independent board with 2.5 sqmm wires. |
| 15 | All as per Ser item No 3.00 here-in-before but with 2.5 Sqmm one 16A socket point controlled by one 16A switch on independent board but just below / above the existing socket points / DBs up to one meter distance in the same vertical plane. |
| 16 | All as per Ser item No 3.00 here-in-before but with 4 sq mm FRLSH copper wire with 4 Sqmm FRLSH copper earth wire for one 16 Amp socket point controlled by one 16 Amp switch on independent board. |
| 17 | M&L for point wiring with 1.5 Sqmm PVC insulated FRLSH, unsheathed, copper conductor stranded 1100 volt grade cable in & incl PVC trunking of size not less than 32x12mm ISI marked ivory white with all accessories such as tee, bend, joint cover including anodized MS sunken boxes made out of MS sheet of thickness not less than 1.6 mm with earth dolly and PVC laminated hylem/Anchor ISI marked top cover 3.0 mm thick for mounting of switches/ sockets/ regulator etc and PVC insulated & unsheathed 1100 volt grade copper conductor, stranded 1.5 sqmm. cable as continuous earth lead complete all as specified and colour coding of cables such as Phase - Red, Neutral – Black, and Earth – Green. Make - Polycab/Finolex/Havells |
| 18 | One light / ceiling fan / exhaust fan / call bell point controlled by one switch |
| 19 | One 6A socket point controlled by one switch on independent board |
| 20 | One 6A socket point controlled by one switch on same board |
| 21 | All as per Ser item No 4.00 here-in-before but one 16A socket point controlled by one 16A switch on independent board with 2.5 sqmm wires. |
| 22 | All as per Ser item No 4.00 here-in-before but with 4 sq mm FRLSH copper wire with 4 Sqmm FRLSH copper earth wire for one 16 Amp socket point controlled by one 16 Amp switch on independent board. |
| 23 | M&L for point wiring with 1.5 Sqmm PVC insulated FRLSH, unsheathed, copper conductor stranded 1100 volt grade cable in and existing conduit with all accessories such as tee, bend, joint cover including anodized MS sunken boxes made out of MS sheet of thickness not less than 1.6 mm with earth dolly and PVC laminated hylem/Anchor ISI marked top cover 3.0 mm thick for mounting of switches/ sockets/ regulator etc and PVC insulated & unsheathed 1100 volt grade copper conductor, stranded 1.5 sqmm. cable as continuous earth lead complete all as specified and colour coding of cables such as Phase - Red, Neutral – Black, and Earth – Green. |
| 24 | One light / ceiling fan / exhaust fan / call bell point controlled by one switch |
| 25 | One 6A socket point controlled by one switch on independent board |
| 26 | One 6A socket point controlled by one switch on same board |
| 27 | All as per Ser item No 5.00 here-in-before but one 16A socket point controlled by one 16A switch on independent board with 2.5 sqmm wires. |
| 28 | All as per Ser item No 5.00 here-in-before but one 16A socket point controlled by one 16A switch on independent board but just below / above the existing socket points / DBs up to one meter distance in the same vertical plane. |
| 29 | Taking down submain wiring of any size any type and in any position metalic/non metallic PVC conduit of wooden batten complete all as specified and as directed. |
| 30 | M&L for sub main wiring along with earth wire with FRLSH insulated copper conductor, single core cable drawn through and including medium grade rigid PVC conduit conforming to IS:9537 (Pt-III) and its all accessories/junction boxes/ inspection covers etc of suitable size but not less than 25mm concealed in wall/ floor etc complete all as specified and as directed for the following sizes:- (Note: Three runs of copper cable and one run of PVC conduit shall be measured as one unit length) |
| 31 | 2runs x 4 sqmm(Ph & N) + 1run x 4 sqmm(earth wire) |
| 32 | 2runs x 6 sqmm(Ph & N) + 1run x 6 sqmm(earth wire) |
| 33 | 2runs x 10 sqmm(Ph & N) + 1run x 10 sqmm(earth wire) |
| 34 | M&L for sub main wiring along with earth wire with FRLSH insulated copper conductor, single core cable drawn through in & incl PVC trunking of size not less than 32x12mm ISI marked ivory white and its all accessories complete all as specified and as directed for the following sizes:- (Note: Three runs of copper cable and one run of PVC conduit shall be measured as one unit length) |
| 35 | 2runs x 4 sqmm(Ph & N) + 1run x 4 sqmm(earth wire) |
| 36 | 2runs x 6 sqmm(Ph & N) + 1run x 6 sqmm(earth wire) |
| 37 | Notes for Ser item No 7.00 to 8.02 : (i) Quoted rate shall deemed to include the cost of cutting chases on wall/floor for concealed conduit wiring and making good with cement plaster, putty and paint to match with the existing surface.(ii) If any beam / column / Rock wall is encountered while cutting chases, that particular portion may be provided with PVC casing & capping or surface conduit for drawing cables and surface PVC gang box fully enclosed type for mounting switches, sockets & regulators etc to avoid any damage to the structure. (iii) No cutting shall be done on ceiling for laying PVC conduit for ceiling fan point wiring. Surface conduit or PVC casing capping may be used in that portion. |
| 38 | S&F of Switch piano type, single pole, one way, 6 amps, 240 volts, complete all as specified and as directed. |
| 39 | S&F of Switch piano type, single pole, one way, 16 amps, 240 volts, complete all as specified and as directed. |
| 40 | S&F of electronic fan regulator in 5 steps, 240V, 50Hz complete all as specified and as directed. |
| 41 | S&F of Socket 5 pin, 6 Amp, universal type, 240 volts, complete all as specified and as directed. |
| 42 | S&F of Socket, 6 pin, 6/16 Amp, multipurpose 240 volts, complete all as specified and as directed. |
| 43 | S&F of Modular switch 1 way 6A, 1 module 240V, 50Hz complete all as specified and as directed. |
| 44 | S&F of Modular switch 1 way 16A, 1 module 240V, 50Hz complete all as specified and as directed. |
| 45 | S&F of Modular fan regulator step type in 5 steps, 240V, 50Hz complete all as specified and as directed. |
| 46 | S&F of Modular Socket, 6A - 2/3 pin combined 2 module 240V, 50Hz complete all as specified and as directed. |
| 47 | S&F of Modular Socket 6A/16A - 2/3 pin combined 2 module 240V, 50Hz complete all as specified and as directed. |
| 48 | S&F of Modular blank plate 1 module complete all as specified and as directed. |
| 49 | S&F of Lamp holder, angle type with metal ring, PVC/Polycarbonate body complete all as specified and as directed. |
| 50 | S&F of Ceiling rose, three terminals, bakelite body, 240 volts, complete all as specified and as directed. |
| 51 | S&F of integrated LED batten 20 watt, 4 feet long, full white in Engineering plastic batten with white acrylic cover with built-in electronic driver, pre-wired and connecting up with twisted twin core flexible copper wire of 0.5sqmm from ceiling rose to connector of fitting complete all as specified and as directed. |
| 52 | S&F of integrated LED batten 20 watt, 4 feet long, Tri light (cool white, warm white & Morning white) combination of these in Engineering plastic batten with white acrylic cover with built-in electronic driver, pre-wired and connecting up with twisted twin core flexible copper wire of 0.5sqmm from ceiling rose to connector of fitting complete all as specified and as directed. |
| 53 | S&F of LED street/security light fitting 30 watts with high efficiency long life LEDs with In-built electronic driver and surge protection upto 10 Kv complete housed in pressure die-cast aluminium housing covered with polycarbonate cover with IP66 degree of protection including provision of GI pipe bracket made up of 25mm dia medium grade GI pipe of length 1.50m bent to required shape and fixing on walls with suitable MS clamps(02Nos) made up of 25mmx4mm MS flat, nuts, bolts and washers and provision of 3 core twisted flexible copper cable of size 0.5 sqmm from ceiling rose to connector of fitting complete all as specified and as directed. |
| 54 | S&F of LED street/security light fitting 45 watts with high efficiency long life LEDs with In-built electronic driver and surge protection upto 10 Kv complete housed in pressure die-cast aluminium housing covered with polycarbonate cover with IP66 degree of protection including provision of GI pipe bracket made up of 25mm dia medium grade GI pipe of length 1.50m bent to required shape and fixing on walls with suitable MS clamps(02Nos) made up of 25mmx4mm MS flat, nuts, bolts and washers and provision of 3 core twisted flexible copper cable of size 0.5 sqmm from ceiling rose to connector of fitting complete all as specified and as directed. |
| 55 | S&F of LED post top lantern light fitting 20watts with high efficiency long life LEDs with In-built electronic driver and surge protection upto 10 Kv and complete housed in pressure die-cast aluminium housing covered with polycarbonate cover with IP65 degree of protection including provision of 25mm dia medium grade GI pipe of length 0.50m bent to required shape and fixing on ground/walls with pcc 1:2:4 using 20 mm size stone aggregate upto 30 cm and provision of 3 core twisted flexible copper cable of size 0.5 sqmm from ceiling rose to connector of fitting including taking down existing unserviceable light fitting of any description complete all as specified and as directed. |
| 56 | S&F of sleek round recessed cum surface mounting LED down light 12 W with aluminium die-cast body, finish with drop down PC diffuser warm / full white with optimized heat sink for efficient dissipation including taking down existing unserviceable light fitting of any description complete all as specified and as directed. |
| 57 | S&F LED luminaire 600 mm x 600 mm, 36 watt, 220 V AC recessed type (Cool white & warm white) with high efficiency PMMA diffuser soft glare free light complete with driver, holders & LED lamp suitable for roof ceiling/grid ceiling including connecting up with driver three core flexible copper conductor cases of suitable size complete all as specified and as directed by Engineer-in-Charge. |
| 58 | S&F LED luminaire 600 mm x 600 mm, 36 watt, 220 V AC recessed type (Cool white & warm white) gypsum ceiling with high efficiency PMMA diffuser soft glare free light complete with driver, holders & LED lamp suitable for roof ceiling including connecting up with driver three core flexible copper conductor cases of suitable size complete all as specified and as directed by Engineer-in-Charge. |
| 59 | S&F of modular MCB protected plug and socket board in sheet steel enclosure with 25A rated mini MCB and 20A rated 3 pin plug, 240 V, 50 Hz complete including cutting the wall surfaces for flush mounting of socket board and making good with cement plaster, putty and paint to match with the existing surface all as specified and directed. |
| 60 | Taking down unserviceavle VTPN/ TPN DB with MCB's of any make/capacity complete all as specified and as directed by Engr-in-Charge. |
| 61 | S&F of MCCB / MCB distribution board, Vertical TPN, 4 way, 415 V, 3 phase, AC with MCCB as incomer and MCBs as outgoing in sheet steel powder painted enclosure double door type with minimum IP 43 degree of protection with built in copper bus bar, neutral link and earth link complete including cutting the wall surfaces for flush mounting of DB and making good with cement plaster, putty and paint to match with the existing surfacecomplete all as specified and as directed. Note: MCCB / MCBs shall be measured and paid separately. |
| 62 | S&F of MCB distribution board, TPN, 4 way, 415 V, 3 phase, AC in sheet steel powder painted enclosure double door type with minimum IP 43 degree of protection with built in copper bus bar, neutral link and earth link complete including cutting the wall surfaces for flush mounting of DB and making good with cement plaster, putty and paint to match with the existing surface complete all as specified and as directed. Note: MCBs shall be measured and paid separately. |
| 63 | Taking down unserviceavle Sheet metal box & MCB DB SPN with MCB's of any make/capacity complete all as specified and as directed by Engr-in-Charge. |
| 64 | Supply and fix MCB distribution board, MCB DB SPN, 12 way, 230 Volt, Single phase, AC in sheet steel powder painted enclosure double door type with IP 43 degree of protection with built in copper bus bar, neutral link and earth link complete including cutting the wall surfaces for flush mounting of DB and making good with cement plaster, putty and paint to match with the existing surface all as specified and directed. Notte: (i) MCBs shall be measured and paid separately.(ii) In case cutting & chasing is encountered with any beam / column/Stone wall, the DBs may be installed on stone wall only as directed by Engineer-in-charge. Note: MCBs shall be measured and paid separately. |
| 65 | Supply and fix MCB distribution board, MCB DB SPN, 8 way, 230 Volt, Single phase, AC in sheet steel powder painted enclosure double door type with IP 43 degree of protection with built in copper bus bar, neutral link and earth link complete including cutting the wall surfaces for flush mounting of DB and making good with cement plaster, putty and paint to match with the existing surface all as specified and directed. Notte: (i) MCBs shall be measured and paid separately.(ii) In case cutting & chasing is encountered with any beam / column/Stone wall, the DBs may be installed on stone wall only as directed by Engineer-in-charge. Note: MCBs shall be measured and paid separately. |
| 66 | Supply and fix MCB distribution board, MCB DB SPN, 4 way, 230 Volt, Single phase, AC in sheet steel powder painted enclosure double door type with IP 43 degree of protection with built in copper bus bar, neutral link and earth link complete including cutting the wall surfaces for flush mounting of DB and making good with cement plaster, putty and paint to match with the existing surface all as specified and directed. Notte: (i) MCBs shall be measured and paid separately.(ii) In case cutting & chasing is encountered with any beam / column/Stone wall, the DBs may be installed on stone wall only as directed by Engineer-in-charge. Note: MCBs shall be measured and paid separately. |
| 67 | S&F of MCCB 100A, 16 KA, 4 Pole, 415 V, 50 Hz with fixed thermal magnetic release complete all as specified and as directed. |
| 68 | S&F of MCB 100A, 10 KA, TPN, 415 V, 50 Hz complete all as specified and as directed. |
| 69 | S&F of MCB 63A, 10 KA, TPN, 415 V, 50 Hz complete all as specified and as directed. |
| 70 | S&F of MCB 40A, 10 KA, SPN, 'C' curve, 240 V, 50 Hz complete all as specified and as directed. |
| 71 | S&F of MCB 6 - 32A, 10 KA, single Pole, 'C' curve, 240 V, 50 Hz complete all as specified and as directed. |
| 72 | S&F of call bell ding dong, AC, 240V, 50Hz complete all as specified and as directed. |
| 73 | S&F of Modular Bell Push , flush type, 6Amp, 1 module 50Hz complete all as specified and as directed. |
| 74 | S&F of Bell Push , flush type, 5 Amp 50Hz complete all as specified and as directed. |
| 75 | Supply and fix of ventilating fan with plastic body with louvers, 200mm sweep, single phase, 230 volts, 50 Hz. complete all as specified and as directed. |
| 76 | Supply and fix of ventilating fan with plastic body with louvers, 250mm sweep, single phase, 230 volts, 50 Hz. complete all as specified and as directed. |
| 77 | S&F of Decorative wall light fixture made up of Polycarbonate with and including 7W retrofit LED lamp, full white/ Warm white of approved model complete all as specified and as directed. |
| 78 | S&F in replacement of 3mm thick phenolic laminated hylam sheet of size 9\\" X 11\\" including necessary cutting, drilling holes for fixing of switches, sockets & fan regulators etc and fixing the hylam sheet on existing metal flush box with brass/GI screws with washers complete all as specified and as directed.Note: S&F of switches, sockets & regulators shall be measured and paid separately. |
| 79 | S&F in replacement of 3mm thick phenolic laminated hylam sheet of size 8\\" X 5\\" including necessary cutting and drilling holes for fixing of switches, sockets & fan regulators etc as per site requirement and fixing the hylam sheet on existing metal flush box with new brass/GI screws with washers complete all as specified and as directed. Note: S&F of switches, sockets & regulators shall be measured and paid separately. |
| 80 | Supply and fix in replacement of 3mm thick phenolic laminated hylam sheet of size 5\\" X 5\\" including necessary cutting and drilling holes for fixing of switches, sockets & fan regulators etc as per site requirement and fixing the hylam sheet on existing metal flush box with new brass/GI screws with washers complete all as specified and as directed by Engineer-in-Charge. Note: S&F of switches, sockets & regulators shall be measured and paid separately. |
| 81 | Supply and fix of ceiling fans complete with blades, down rods, and accessories, 230 V, 1200 mm sweep 3 blade, white/Brown colour,. Min air delivery 210 CFM with service value 6.00 BEE. Five star rated, copper winding with brushless direct current motor (BLDC) and connecting up with 3 core x 0.5 sqmm flexible copper conductor cable from ceiling rose including taking out old fan and deposited to store yard complete all as specified and directed. Note: Old Ser/ UNSV fans removed from the site are property of Department, will be deposited at E/M yard |
| 82 | Supply and fix of ceiling fans complete with blades, down rods, and accessories, 230 V, 1400 mm sweep 3 blade, white/Brown colour, Min air delivery 210 CFM with service value 6.00 BEE. Five star rated, copper winding with brushless direct current motor (BLDC) and connecting up with 3 core x 0.5 sqmm flexible copper conductor cable from ceiling rose including taking out old fan and deposited to store yard complete all as specified and directed. Note: Old Ser/ UNSV fans removed from the site are property of Department, will be deposited at E/M yard |
| 83 | Taking down old unserviceable of LT cable of any type and size complete all as specified and as directed. |
| 84 | Supply and laying or fixing or passing through pipe, 1100 volts grade heavy duty cable with PVC insulated stranded aluminium conductor served with an inner sheathing of PVC tape armoured with galvanized steel wire or strip and overall PVC sheathed, 16 sq. mm nominal cross section, 4 core in service connections as per IS 7098(Part 1) including connecting on LT OH line / LT panel /DB with suitable lugs, glands, binding wire etc complete all as specified and as directed. |
| 85 | Supply and laying or fixing or passing through pipe, 1100 volts grade heavy duty cable with XLPE insulated stranded aluminium conductor served with an inner sheathing of PVC tape armoured with galvanised steel wire or strip and overall PVC sheathed, 25 sq mm 4 core in service connections as per IS 7098(Part 1) including connecting on LT OH line / LT panel /DB with suitable lugs, glands, binding wire etc complete all as specified and as directed. |
| 86 | Supply and laying or fixing or passing through pipe, 1100 volts grade heavy duty cable with PVC insulated stranded aluminium conductor served with an inner sheathing of PVC tape armoured with galvanized steel wire or strip and overall PVC sheathed, 10 sq. mm nominal cross section, 2 core in service connections as per IS 7098(Part 1) including connecting on LT OH line / LT panel /DB with suitable lugs, glands, binding wire etc complete all as specified and as directed. |
| 87 | Supply and fix of 1100 volts grade heavy duty cable PVC insulated stranded aluminium conductor twin core, 10 sqmm, served with inner sheathing of PVC tape and overall PVC sheathed in service connections including connecting on LT OH line / energy meter / DB etc complete all as specified and as directed. |
| 88 | Material and labour for Double wall corrugated HDPE pipe, ISI marked of outer dia 50mm, inner dia 38mm with smooth internal and profiled external surface, non-pressure type, laid in trenches/floors/duct or fixed on walls /pole including all connections, accessories like socket, couplers, bends, etc for protection of LT cable XLPE grade 1100 volts complete all as specified and as directed. |
| 89 | Excavation in trenches not exc 1.5 m wide and not exc 1.5 m depth for laying of GI Pipe and getting out in any type of soil complete all as specified and as directed. |
| 90 | Returning, filling in, including leveling, watering and well ramming in layers not exc 25 cm complete all as specified and as directed. |
| 91 | Removing excavated material not exc 50m and depositing where directed at a level not exc 1.5m above the starting point complete all as specified and as directed. |
| 92 | M&L for Earthing complete with galvanised iron earth plate electrode 600mm x 600mm x 6 mm thick buried directly in ground (earth pit not less than 2.25 mtrs deep below ground level) with top edge of the plate not less than 1.5 mtrs below normal ground level connecting to GI wire 4 dia mm as earthing lead by means of bolts, nuts, check nuts and washers of galvanised iron or steel and earth wire protected by 15mm dia GI pipe medium grade and connected to distribution board/earthing test point all as shown in electircal plate No. 3 of SSR Part-I(2009) and testing on completion complete all as specified and as directed. Note :- (a) The unit rate quoted shall also include for excavation, earth work in any type of soil, plain cement concrete 1:3:6 mix, Type C1 pit, 40mm thick RCC 1:2:4 mix type B1 cover reinforced with 8mm dia TMT bras @ 150mm C/C both ways, GI funnel with watering pipe, wire mesh,protection pipe, earth wire upto 7.50m long complete in addition to item No. 1(a) to (e) of preamble (Notes) under sub heading earthing, specified in SSR Part II. (b) Earthing result should be less than 3 Ohm required. |
| 93 | S&F of Deep Recess - mounting COB LED downlights nucleus Deep Recess 10W made of extruded aluminium housing and high lumen LED as a light source with clear diffuser and separate electronic driver complete all as specified and as directed. |
| 94 | Supply and fixing in replacement PVC conduit including fitting such as tee,elbow,bend etc 20mm dia ISI (MMS)grade, incl taking down old unserviceable conduit all as specified and directed. |
| 95 | Supply and fixing in replacement PVC cassing Capping tee,elbow,bend etc 20/25 mm dia ISI ISI (MMS) incl taking down old unservecable cassing capping all as specified and directed. |
| 96 | S&F LED flood light 70 watt 230 V AC outdoor type with thermal management in multiple optics and equipped with IP66 protection, with impact and corrosion resistant complete with driver and lamp complete all as specified and as directed. |
| 97 | S&F of LED bulkhead luminaire 10W in die-cast aluminium alloy/ PVC body heat resistant prismatic glass cover, with specially designed gasket for minimum IP 55 degree of protection complete all as specified and as directed. |
| 98 | S&F of integrated LED batten 10 watt, 2 feet long, full white in Engineering plastic batten with white acrylic cover with built-in electronic driver, pre-wired and connecting up with twisted twin core flexible copper wire of 0.5sqmm from ceiling rose to connector of fitting complete all as specified and as directed. |
| 99 | Supply and fix in replacement of exhaust fan with steel body 300mm sweep with blade , frame and louvers , single phase, 230 volts, 50 Hz. including taking down existing unserviceable exhuast fan of any description complete all as specified and as directed. Note :- Old and u/s exhaust fan deposited to E/M yard store as a govt property. |
| 100 | Supply and fix LED strip, 24 watt, warm / cool white/ tricolour,18 mtr length, flexible PCB body type including driver, IP 20 protection with accessories such as 06A plugtop, flexible cable etc complete all as specified and as directed. |
| 101 | Material and Labour for Point wiring with 1.5 Sqmm Halogen Free Flame Retardant (HFFR) insulated, unsheathed, multistranded, 1100 Volts grade copper conductor cable single core confirming to IS:17048 along with one run of 1.5 Sqmm HFFR insulated copper conductor cable green in colour for continuous earthing drawn through and including stove enameled rigid steel conduit conforming to IS: 9537 (Part- 2) and its all accessories/junction boxes/ inspection covers etc of suitable size but not less than 20mm(OD), on wall/ columns / steel structures / floor etc for one light point controlled by one one way switch complete all as specified and as directed. |
| 102 | Supply and fixing LED light fitting 1 x 16 Watt flame proof, CMRI certified recommended for gas/ vapor group of IIA & IIIB, Zone 1 & 2 and IP 65 protection with die cast aluminum hosing with heat resistant toughened glass with LED tube light fixtures driver, holders, connector etc. Complete with all accessories prewired and including connecting up with three core flexible copper conductor cable with suitable size complete all as specified and as directed. |
| 103 | Supply and fixing of Switch flame proof rotary type with termination box in LM6, 16A, single pole 250V complete all as specified and as directed. |
| 104 | Supply and Fixing of Flameproof cum Waterproof LED Bulk Head light fitting of 15W, IP66 protection of Cast Aluminum alloy material and Heat and Impact resistance toughen 'A' clear glass having Anti corrosive epoxy powder coated finish complete with all accessories pre wired and including connecting up with three core flexible copper conductor cable with sitable size complete all as specified and as directed. |
| 105 | M&L for earthing complete with copper earth plate electrode 600mm x 600mm x 3.15 mm thick buried directly in ground (earth pit not less than 2.25 meters deep below ground level) with top edge of the plate not less than 1.5 meters below normal ground level connecting to copper strip 20x3 mm as earthing lead by means of bolts, nuts, check nuts and washers of copper and earth wire protected by 50mm dia GI pipe medium grade and connected to pole structure/ panel board/earthing test point all as shown in electrical plate No. 3 of SSR Part-I(2009) and testing on completion complete all as specified and as directed. Note :- The unit rate quoted shall also include for excavation, earth work in any type of soil, plain cement concrete 1:3:6 mix, Type C1 pit, 40mm thick RCC 1:2:4 mix type B1 cover reinforced with 8mm dia TMT bras @ 150mm C/C both ways, GI funnel with watering pipe, wire mesh, protection pipe, earth strip up to 7.50m long complete in addition to item No. 1(a) to (e) of preamble (Notes) under sub heading earthing, specified in SSR Part II |
| 106 | M&L for earthing complete with galvanized iron earth plate electrode 600mm x 600mm x 6 mm thick buried directly in ground (earth pit not less than 2.25 meters deep below ground level) with top edge of the plate not less than 1.5 meters below normal ground level connecting to GI strip 32x6 mm as earthing lead by means of bolts, nuts, check nuts and washers of galvanized iron or steel and earth wire protected by 50mm dia GI pipe medium grade and connected to pole structure/ panel board/earthing test point all as shown in electrical plate No. 3 of SSR Part-I(2009) and testing on completion complete all as specified and as directed. Note :- The unit rate quoted shall also include for excavation, earth work in any type of soil, plain cement concrete 1:3:6 mix, Type C1 pit, 40mm thick RCC 1:2:4 mix type B1 cover reinforced with 8mm dia TMT bras @ 150mm C/C both ways, GI funnel with watering pipe, wire mesh, protection pipe, earth strip up to 7.50m long complete in addition to item No. 1(a) to (e) of preamble (Notes) under sub heading earthing, specified in SSR Part II |
| 107 | M&L for Test point terminal block made of gun metal or phosphorus bronze size 75x75x25mm drilled and screwed including 3 nos. 8mm dia 25mm long hex. head screw complete all as specified and as directed by Engineer-in-Charge. |
| 108 | S&F epoxy insulator for fixing aluminium strip |
| 109 | Supply and fixing earth continuity conductor or main earthing lead 32 x 6 mm GI strip laid in pipe/ fixed to poles or any other indicated position including jointing by using GI nuts, bolts and washer in addition to welding complete all as specified and as directed. |
| 110 | Supply & fix single pointed air termination aluminium rod 12mm dia, 300 mm long |
| 111 | S&F Vitalite REC 600 mm x 600 mm, 36 watt( a lighting solutions that emit UVB rays the beneficial component of sunlight resposible for Vitamic D synthesis) operating temperate - 10 to +45 C. CRCA powder coated white in colour with phosphochromate treatment including connecting up with driver three core flexible copper conductor cases of suitable size complete all as specified and as directed by Engineer-in-Charge. Total in Figures 23 0.0 INR Zero Only Quoted Rate in Figures Select 0.0 0.0 Zero Only Quoted Rate in Words INR Zero Only Please Enable Macros to View BoQ information |