| 1 | Taking down flame proof main switches fuse unit, MCB/Kit kat distribution board any type/size/capacity with steel enclosure along with MCB’s /Kit kat fuse of any amps/ways including wooden board or from steel board and making good disturbed surfaces as existing colour complete all as directed. |
| 2 | Taking down unserviceable flameproof conduit point wiring from existing place ( light, socket or power points) complete with all unserviceable fittings and making good to disturbed surface to wall, floor etc to match with existing surface either by using same colour distemper, putti or white / colour wash all as required and directed by the Engineer-in-Charge. |
| 3 | S&F MCB Distributionn Board flame proof type 6 way ,415 V ,50 Hz including IP 65 Zone1 & Zone 2 with termination box in LM6 type complete with MCB SPN 40A - 01 Nos and MCB SP 10A - 04 Nos all as specified and directed the Engineer-in-Charge. |
| 4 | M & L for flameproof concealed/surface point wiring on wall and surface wiring on ceiling / roof with necessary fixing arrangements with stranded PVC-FRLSH insulated and unsheathed copper stranded conductor of size 1.5 Sqmm, 1100 volts grade drawn in and including 16 gauge stove enameled ERW rigid steel conduit (metallic) not less than 19 mm dia with all MS conduit accessories/ fittings such as junction boxes, bends, tee, elbow etc including PVC-FRLSH insulated and unsheathed copper stranded conductor of size 1.5 Sqmm, 1100 volts grade for continuous earthing including cutting the chases and making good the surface by cement mortar (1:3) and for matching / finishing of new surfaces either by means of plaster of peris/ Putti or distemper / colour wash with same existing colour surfaces all as specified and directed by Engineer-in-Charge for one light, fan point controlled by one switch. complete all as specified & directed. |
| 5 | S&F in replacement of Switch flame proof rotary type with termination box in LM6, 16A, single pole 250V complete all as specified & directed. |
| 6 | Supply and fixing LED light fitting 1x16 Watt flame proof, CMRI certified recommended for gas/ vapor group of IIA & IIIB, Zone 1 & 2 and IP 65 protection with die cast aluminum housing with heat resistant toughened glass with LED tube light fixtures driver, holders, connector etc. Complete with all accessories prewired and including connecting up with three core flexible copper conductor cable with suitable size complete all as specified and directed. |
| 7 | LT Panel supply, fixing and testing CPRI approved factory made outdoor type LT distribution board made out of 3 mm thick CRCA sheet duly powder coated grouted in ground on PCC padestal or fixed in wall of size & sahpe approved by Engineer-in-charge arrangement compartmentalized double door type with suitable compartment for cable alley, and incoming and outgoing cable to be fixed with suitable cable gland and also danger notice board to be embadered and provision for tapping incoming & outgoing electric connections with suitable size of lugs and comprising of the folowing:-INCOMING(a) MCCB, FP, 250 Amp, 415 Volt, 36kA breaking capacity, 50 Hz with thermal magnetic release - 01 No(b) Copper busbar high conductivity 400 Amp rated 3-phase, 03 Nos including neutral bus bar 400 Amp, 01 No - 01 Set(c) Indicating light LED type (RYB) set of three - 01 NoOUTGOING(a) MCCB FP 125 Amp, 415 Volt, 25kA breaking capacity, 50 Hz with thermal magnetic release - 04 Nos(b) MCCB FP 63 Amp, 415 Volt, 25kA breaking capacity, 50 Hz with thermal magnetic release - 01 No(c) Indicating light LED type (RYB) set of three - 01 No(d) Digital Voltmeter 0-500 V, Digital Ammeter 0-400 Amp with CT 400/5 and selector switches - 01 set each(e) Electronic street light Astronomical control timer switch, operating automatic/ mannually of capacity 6 KW,Conforms to IS/IEC 60947-4-1, 3 phase, 415/230 volts, 50 Hz, ISI marked accommodating the following (i) Three phase control switch MCB TPN 40A 10 KA - 01 No (Incoming)(ii) Auto/Manual control switch (iii) Heavy duty 3 Phase Contactor ML-3 with axulllary contact - 01 No (iv) sun light senser cat eye type complete to operate before sun rise & after sun set(v) Astronomical Timer - 01 No. As per specification of Havells cat Part No - IHXTS0306A or equivalent make in L&T,LegrandNote:- (a) Make for individual breaker/articles :- L&T, Seimens or Schinder (b) Contractor will submit fidder piller box drawing, CPRI approval certificate of manufacturer before procurement |
| 8 | S&F outdoor type loop in loop out junction box totally enclosed double door weather and vermin proof, suitably ventilated, 440 Volts, 50 HZ, AC supply, fully compartmentalised cubical type made out of 3mm thick CRCA sheet CPRI approved steel and powder coating including suitable jangle iron/flat iron frame work/supports, excavation and earth work, PCC foundation etc, including 4 Nos Copper bus bar of 200 Amps with indicating lamps of R,Y,B and MCCB TPN, 415 volt adjustable type, 100 Amps with breaking capacity 25 KA - 01 No at incoming side of make L&T, Schenider, or ABB complete all as directed and specified by Engr-in-charge. Note: Contractor will submit junction box drawing, CPRI approval certificate of manufacturer before procurement of the same. |
| 9 | S&F in replacement with Jointing, Testing and commissioning of XLPE insulated screened PVC bedded, galvanized steel strip or wire armoured, electric power cables ( heavy duty) with stranded aluminum conductor, 1100 Volt grade with fixing acessories of 50 Sqmm, 3.5 Core all as specified and directed. |
| 10 | All as per above item No. 9 above but for size of cable 35 sqmm, 3.5 core |
| 11 | All as per above item No. 9 above but for size of cable 10 sqmm, 2 core |
| 12 | Excavation in trenches, in any type of soil not exceeding 1.5 Mtr wide and not exceeding 1.5 Mtr in depth , laying of cable or pipes (where provided for protection of cable) etc and getting out trimming the sides, forming bottom surfaces to required level complete all as specified and all as directed. |
| 13 | M&L for 50 mm dia GI tubing light grade with all necessary fittings laid in trenches, fixed to walls/ poles/ under road/ floor etc for cable protection, complete all as specified and directed. |
| 14 | M&L for 40 mm dia GI tubing light grade with all necessary fittings laid in trenches, fixed to walls/ poles/ under road/ floor etc for cable protection, complete all as specified and directed. |
| 15 | M & L for sand cushioning with a layer of sand 80 mm thick before laying of cable and 150 mm thick after laying of cable in trenches complete all as specified and directed. |
| 16 | Supply and laying of well burnt bricks, sub class 'B' laid flat in trenches for protection of cable complete all as specified and directed. |
| 17 | Returning and filling including spreading, levelling, watering and well ramming in layers not exceeding 25 Cm thick all as specified and directed by Engr-in-Charge. |
| 18 | Removing of surplus soil to a distance not exceeding 50 Mtrs and depositing where directed at a level not exceeding 1.5 Mtr above the starting point complete all as specified. |
| 19 | Supplying & Fixing Copper electrode chemical earthing pipe in pipe technology of high conductive, corrosion resistant, CPRI tested maintenance free chemical earthing pit to achive earth resistance value less than or equal to 3 Ohm & EN voltage < 02 V,pipe in pipe technology based in which primary conductor (Pipe) having 40 MM dia and primary conductor is inserted into secondray conductor having 80 MM dia. The primary conductor is inserted into secondory conductor and space between secondary and primary conductor of earthing electrode should becrystalline compound. The length of this electrodes is min 3000 MM (3 meters) and earth pit's bore hole should be of dia 200 to 250 mm and min depth 3.50 meters. Length of electrode will be increase with connecting of 32 x 6 mm Copper strip extra,and total depth should not less than 3.50 meters. Around the earth electrode earth pit borehole should be backfilled with minimum 50 Kg of ground enhencement compound ERIC Contains mixture of Silica sulphate,Alumina, Iron Oxide, titanium Oxide, Calcium Oxide,Sodium Oxide, Zink Oxide etc. ). including RCC earthing pit having 450 x 450 Cl chamber cover all as directed by Engineer-in-Charge.( Note : If less than 3 Ohm result has not acheived at site the contractor is responsible to do grid system to achieve the desired result and no extra payment shall be made to the contractor for making grid system.) Please Enable Macros to View BoQ information |
| 20 | Supplying & Fixing Copper electrode chemical earthing pipe in pipe technology of high conductive, corrosion resistant, CPRI tested maintenance free chemical earthing pit to achive earth resistance value less than or equal to 3 Ohm & EN voltage < 02 V,pipe in pipe technology based in which primary conductor (Pipe) having 40 MM dia and primary conductor is inserted into secondray conductor having 80 MM dia. The primary conductor is inserted into secondory conductor and space between secondary and primary conductor of earthing electrode should becrystalline compound. The length of this electrodes is min 3000 MM (3 meters) and earth pit's bore hole should be of dia 200 to 250 mm and min depth 3.50 meters. Length of electrode will be increase with connecting of 32 x 6 mm Copper strip extra,and total depth should not less than 3.50 meters. Around the earth electrode earth pit borehole should be backfilled with minimum 50 Kg of ground enhencement compound ERIC Contains mixture of Silica sulphate,Alumina, Iron Oxide, titanium Oxide, Calcium Oxide,Sodium Oxide, Zink Oxide etc. ). including RCC earthing pit having 450 x 450 Cl chamber cover all as directed by Engineer-in-Charge.( Note : If less than 3 Ohm result has not acheived at site the contractor is responsible to do grid system to achieve the desired result and no extra payment shall be made to the contractor for making grid system.) Please Enable Macros to View BoQ information |