| 1 | Taking down carefully copper/aluminium point wiring (light, fan, socket or power) complete, (fittings such as switches, ceiling roses, pendants, regulators sockets etc. to be measured separately), removing materials to store for keeping in safe custody for reuse at site and making good disturbed surfaces of walls, floors, etc. |
| 2 | M&L point wiring complete with 1.5 Sqm sincle core PVC insulated unsheathed FRLS cable 1100 volts grade (ISI marked) with multi stranded copper conductor drawn through and including PVC casing and caping fixed to wall/roof, ceiling etc and incl provn of 1.5 sqmm PVC insulated multistranded unsheathed copper conductor cable FRLS (ISI marked) as earth continuity conductor, fabricated sunken terminal box made out of 1.60 mm thick sheet steel duly painted concealed in walls, with 3mm thick bakelite/PVC sheet ISI marked top cover with brass/chromium plated screws and cup washers for housing switches, socket outlets, fan regulators etc, all as specified and as directed for the following :- |
| 3 | One light point/exhaust fan/fan point controlled by one switch |
| 4 | One socket point controlled by one switch on same board |
| 5 | One socket point controlled by one switch on independent board |
| 6 | M&L for point wiring with two single core PVC insulated, unsheathed, FRLS multistranded unsheathed copper conductor cable of size 2.5 sqmm and one single core PVC insulated unsheathed FRLS stranded copper conductor of size 2.5 sqmm green in colour as earth lead through and including PVC casing & caping with all fittings & accessories ISI marked including provn of MS sunken boxes of appropriate size & thickness fixed flush to wall for 15/16 A switch-socket point on independent board complete. |
| 7 | S&F switch piano flush type AC 230 Volts 6 Amps single pole one way (to be fitted with new light point) complete all specified and directed |
| 8 | S&F socket outlet 3 pin, 6 Amps on same board AC 230 volts flush type complete all as specified and directed. |
| 9 | Supply & fix switch socket combination outlet, 5 pin, 6 Amps, multipurpose, flush, non shutter, non inter locking type, 230 volt flush type, white/ivory finish with fixing hole complete all as specified and directed by Engineer in charge. |
| 10 | Supply & fix switch socket combination, 6 pin, 15/16Amps, multipurpose , flush, shutter type, 230 volt flush type, white/ivory finish with fixing hole complete all as specified and directed by Engineer in charge. |
| 11 | Supply and fixing in replacement of 10W LED pride plus Neo Batten 6500k,220V, White, Decorative ultra slim round profile LED lighting fixture with extruded polycarbonate, environmental friendly, energy efficient, connecting up with three core flexible copper conductor cable of suitable size from ceiling rose complete. all as specified and as directed. Make-Havells Model No. LHEXACP7PN1W010 or equivalent in Philips/Bajaj/Crompton. |
| 12 | Supply and fixing in replacement of 20W LED pride essential Batten 6500k,220V, White, Decorative ultra slim square profile LED lighting fixture with extruded polycarbonate, environmental friendly, energy efficient, connecting up with three core flexible copper conductor cable of suitable size from ceiling rose complete. all as specified and as directed. Make-Havells Model No. LHEXAWP7UN1W020 or equivalent in Philips/Bajaj/Crompton. |
| 13 | Supply and fixing in replacement of LED Panel Square, slim compact, aluminum die cast edge LED recess mounted downlight fixture panel fitting 18 watt, 220 V AC recessed type with high efficiency PMMA diffuser soft glare free even light distribution with driver suitable for roof ceiling, connecting up with Driver three core flexible copper conductor cable and fixture, complete all as specified and directed by Engr-in-Charge.Make-Havells Model No. LHEBAEP7IZ1W018 or equivalent in Philips/Bajaj/Crompton. |
| 14 | S&F in replacement Electronic constant current Driver for LED fitting of 15/18 watt, 240 volts, 50 Hz. Make - Havells Cat No LSSLNW0170 /Philips/Bajaj/Crompton/Luker |
| 15 | Supply and fix in repairs electronic fan regulator, 120/280W 250V stepped type, flush type complete all as specified and as directed. |
| 16 | Supply and fix in repairs Socket outlet 3 pin, 6 Amps flush type 230 Volts, AC, with ISI mark complete all as specified and directed. |
| 17 | Supply & fix in repairs switch socket combination outlet, 5 pin, 6 Amps, multipurpose, flush, non shutter, non inter locking type, 230 volt flush type, white/ivory finish with fixing hole complete all as specified and directed by Engineer in charge. |
| 18 | Supply & fix in repairs switch socket combination, 6 pin, 15/16Amps, multipurpose , flush, shutter type, 230 volt flush type, white/ivory finish with fixing hole complete all as specified and directed by Engineer in charge. |
| 19 | Supply & fix in repairs Ceiling rose in poly carbonate 3 plates flush type 6 Amps, 250 volts AC complete all as specified and directed. |
| 20 | Supply & fix in repairs switch socket combination outlet, 5 pin, 6 Amps, multipurpose, flush, non shutter, non inter locking type, 230 volt , PVC Box type, white/ivory finish with pvc surface box complete all as specified and directed by Engineer in charge. |
| 21 | Supply & fix in repairs switch socket combination, 6 pin, 15/16Amps, multipurpose , flush, shutter type, 230 volt, PVC box type, white/ivory finish with PVC surface box complete all as specified and directed by Engineer in charge. |
| 22 | Supply and fix in repairs Bell electric Ding Dong 230 Volts, AC, with ISI mark complete all as specified and directed. |
| 23 | Supply & fix in repairs Modular switch one way 6A,240volts 50Hz, 1 Module complete all as specified and as directed. |
| 24 | Supply & fix in repairs bell push switch piano flush type 6A, 240volts 50Hz, 1 Module complete all as specified and as directed. |
| 25 | Supply & fix in repairs Modular switch one way 16A,240volts 50Hz, 1 Module complete all as specified and as directed. |
| 26 | Supply & fix in repairs Modular switch socket outlet, 6 Amps, 2 and 3 pin combined, 240volts 50Hz, 2 Module complete all as specified and as directed. |
| 27 | Supply & fix in repairs Modular switch socket outlet, 6/16 Amps, 2 and 3 pin combined, 240volts 50Hz, 2 Module complete all as specified and as directed. |
| 28 | Supply & fix in repairs Modular rotary type stepped regulator, 120 w, 240volts 50Hz, 1/2 Module complete all as specified and as directed. |
| 29 | Supply & fix in repairs modular white cover plate with frame 3 module complete all as specified and directed. |
| 30 | Supply & fix in repairs modular white cover plate with frame 4 module complete all as specified and directed. |
| 31 | Supply & fix in repairs modular white cover plate with frame 6 module complete all as specified and directed. |
| 32 | Supply & fix in repairs modular white cover plate with frame 8 module complete all as specified and directed. |
| 33 | S&F in replacement of 2.5 MFD fan capacitor of apporved make for ceiling fan, Including taking down old existing unserviceable complete all as specified and directed. Make : Havells /L&T/Surya |
| 34 | Supply & fix in repairs MCB SP 6-32 amp rating 240V, 10KA 'B' curve miniature circuit breaker (MCB) of single pole in the MCB DB,IP 20 transparent lebel holder fully insulated safety shutters suitable for cable up to 35 Sqmm cross sectional area complete including suitable size copper Lugs complete all as specified and directed. Make: Indo Asian/ L&T/Crompton Greaves/Havells |
| 35 | Supply & fix in repairs MCB SPN 40-63 amp rating 240V, 10KA 'C' curve miniature circuit breaker (MCB) of single pole in the MCB DB complete with connection testing and commissioning complete all as specified and directed. Make: Indo Asian/ L&T/Crompton Greaves/Havells |
| 36 | Supply & fixing in repairs Triple pole and neutral (TPN) 40 to 100AMP 415V 10KA 'C' curve miniature circuit breaker (MCB) in the DB complete with connection testing and commissioning complete all as specified and directed. Make: Indo Asian/ L&T/Crompton Greaves/Havells |
| 37 | Supply & fixing in replacement Boxes junctions, plastic, round/square, four terminals complete all as directed. |
| 38 | Supply & fixing in repairs single pole and neutral enclouser with a two pin and earth plug and socket complete with one MCB single pole 20 Amps complete all as specified and directed. |
| 39 | Supply & fixing in repairs Distribution board (DB) made out of sheet metal enclosure (CRCA sheet), dust and vermin proof, SPN 8 way with 200 Amps rated copper bus bar double door protection, neutral bar,earth bar, single pole and neutral 240 volts, MCBs used as incommer flush to wall complete all as specified and as directed. |
| 40 | Material and labour for Sub main wiring using two runs of single core PVC insulated cable (FRLS) 4 sqmm copper conductor multi stranded and one run of 4 sqmm copper conductor insulated cable (FRLS)using as earth wire drawn through and including suitable size casing capping including taking down old aluminium/Copper Sub main wirng, complete all as specified and directed. Note- 3 run of 4 sq mm PVC copper wire and One run of PVC casing caping shall be measured and paid as one unit. |
| 41 | Material and labour for Sub main wiring using two runs of single core PVC insulated cable (FR) 10 sqmm copper conductor multi stranded and one run of 10 sqmm copper conductor insulated cable (FR)using as earth wire drawn through and including suitable size PVC casing caping including taking down old aluminium/Copper Sub main wirng complete all as specified and directed. Note- 3 run of 10 sq mm PVC copper wire and One run of PVC casing caping shall be measured and paid as one unit. |
| 42 | Supply & fix in repairs switch piano flush type AC 230 Volts 6 Amps single pole one way complete all specified and directed |
| 43 | Taking down unserviceable Ceiling/Exhaust/wall mounted Fan(any size), sealing cable end, dismantling blades and removing fan and blades to store, complete all as specified and directed by Engineer-in-Charge. |
| 44 | Supply and fix in repair rigid non-metalic PVC conduit of 25 mm dia including all fitting such as bends, elbow, coupler lock nut etc, complete all as specified and directed by Engineer-in-Charge. |
| 45 | Supply and fix in repair rigid non-metalic PVC conduit of 20 mm dia including all fitting such as bends, elbow, coupler lock nut etc, complete all as specified and directed by Engineer-in-Charge. |
| 46 | M&L for Re-winding the existing unserviceable Ceiling fans of any make but of size 1200 mm sweep, opening the ceiling fan, removing the burnt copper winding after testing, cutting the rotor coil, cleaning the rotor & the stator and rewinding with and including super enamelled copper wire of approved quality of existing gauge, replacing the wornout bearings, over-hauling, lubricating with fresh grease, re-assembling and testing for satisfatory operation complete all as specified and directed by Engineer-in-Charge. |
| 47 | M&L for Re-winding the existing unserviceable Exhaust fans of any make but of size 300/375 mm sweep, opening of Exhaust fans, removing the burnt copper winding after testing, cutting the rotor coil, cleaning the rotor & the stator and rewinding with and including super enamelled copper wire of approved quality of existing gauge, over-hauling, lubricating with fresh grease re-assembling and testing for satisfatory operation complete all as specified and directed by Engineer-in-Charge. |
| 48 | Material and Labour for Scraping down old paint of ceiling fan of any sweep complete body & blade including down rod filling the cavities with filler and making smooth surface by applying sand paper painting the ceiling fan by means spray gun/brush with synthetic enamel white paint and writing the MES No. with black paint complete all as specified and directed by Engineer in charge. |
| 49 | Material and Labour forscraping down old paint of exhaust fan of any sweep complete body & blade, filling the cavities with filler and making smooth surface by applying sand paper painting the exhaust fan by means spray gun/brush with synthetic enamel white paint and writing the MES No. with black paint complete all as specified and directed by Engineer in charge. |
| 50 | Supply & fixing replacement of Exhaust Fan of size 250 mm sweep with louvers, with plastic body AC 230 V, 50 Hz, and connecting to ceiling rose terminals with 23/.0076 flexible cable and making good the disturbed surface to match with existing finishes complete all specified and directed. |
| 51 | S&F in repair PVC casing capping size 20mm including all accessories, fixing arrangement, screws, etc complete all as specified and directed. Make: Modi |
| 52 | S&F in repair PVC casing capping size 25mm including all accessories, fixing arrangement, screws, etc complete all as specified and directed. Make: Modi |
| 53 | S&F in repair PVC casing capping size 32mm including all accessories fixing, arrangement, screws, etc complete all as specified and directed. Make: Modi |
| 54 | S&F in repair 25mm Flex corrugated flexible hose pipes made with strong pipes of virgin plastic, highly flexible, anti-distortion, good bending performance, well strech, complete all as specified and directed. Make: Modi |
| 55 | S&F in replacement PVC surface mounting 1 module Gang Box for mounting of switches with fixing accessories, screws etc. Including taking down old existing broken complete all as specified and directed. |
| 56 | S&F in replacement PVC surface mounting 4 module Gang Box for mounting of switches with fixing accessories, screws etc. Including taking down old existing broken complete all as specified and directed. |
| 57 | S&F in replacement PVC surface mounting 8 module Gang Box for mounting of switches with fixing accessories, screws etc. Including taking down old existing broken complete all as specified and directed. |
| 58 | S&F in replacement PVC surface mounting 12 module Gang Box for mounting of switches with fixing accessories, screws etc. Including taking down old existing broken complete all as specified and directed. |
| 59 | S&F in repairs HFFR PVC insulated multistranded copper conductor cable single core of size 1.5 Sqmm, 1100 volt, complete all as specified and directed. Make - Havells, polycab, & finolex etc as approved by GE. |
| 60 | S&F in repairs HFFR PVC insulated multistranded copper conductor cable single core of size 2.5 Sqmm, 1100 volt, complete all as specified and directed. Make - Havells, polycab, & finolex etc as approved by GE. |
| 61 | S&F in repairs FR round PVC insulated multistranded copper conductor cable Twin core of size 1.5 Sqmm, 110 volt, complete all as specified and directed. Make - Havells, polycab, & finolex etc as approved by GE. |
| 62 | S&F in repairs FR round PVC insulated multistranded copper conductor cable Twin core of size 2.5 Sqmm, 1100 volt, complete all as specified and directed. Make - Havells, polycab, & finolex etc as approved by GE. |
| 63 | Earthing complete with galvanised steel earth plate electrode 60 cm x60 cm x 6 mm thick buried directly in ground ,(Earth pit not less than 2.25 meter deep below ground level) with top edge of plate not less than 1.5 meter below normal ground level ,connected to and including galvanised iron earth wire 32 X 6 mm by means of nut, bolts, check nuts and washers of galvanised iron or steel and provision of charcoal dust and common salt packed all around the earth plate including necessary excavation and earth work in any type of soil and testing complete all as specified and directed and shown in electrical plate number 3 of MES SSR part-I(2009)Note: Unit rate quoted shall be deemed to be included the following (a) Excavation and earth work for drilling hole for electrode in any type of Soil. (b) PCC pit in cement concrete 1:2:4 type B-1, Pre cast RCC cover with suitable handle 40 mm thick in PCC 1:2:4 type B-1, reinforced with welded steel wire fabric weighing not less than1.87 Kg/ Sq meter. (c) Funnel with watering pipe of GI 20 mm nominal bore light grade and lugs etc complete all as specified and directed (d) 40 mm nominal bore medium grade GI protection pipe 7.5 meter long for protection of earthing lead complete all as specified and directed. (e) Requisite quantity of common salt and charcoal. (f) Testing of earthing. |
| 64 | M&L for making high conductive, corrosion resistant, maintenance free Chemical earthing comprising of chemical earth enhancing non ferrous compounding containing Bentonite powder in earth pit (Approximate qty 50 kg) of bore hole of > 150mm and depth upto 3.3mtr (approx) and comprising of CPRI approved Copper earth electrode, Double pipe (Pipe-in pipe) technology based chemically pre- filled with crystalline compound with outer pipe 80mm dia and inner pipe 40mm dia and 3.00 mtr long made of high conductive copper terminal strip 50*6 mm at top, technically required to achieve resistance of 1 ohm along with heavy duty high density lockable plastic cover cum inspection chamber mounted on earthing electrode shall be fixed stainless steel fastners including all other required accessories to complete the job of earth pit with earth termination to achieve rod resistance 1 ohms, including taking down unservicable items complete all as specified and directed by Engineer-In-Charge.Note :- (i) Cost of earth strip and GI protection for connecting with Earth Lead shall be measured and paid separately.(ii) The unit rate quoted shall deemed to include the cost of boring of earth polymer chamber with cover and test point. |
| 65 | M&L for chemical earthing with copper earth plate of size 900mmx900mmx5mm thick buried directly in ground (earth pit depth not less than 3 Mtr below normal ground level) with top edge of the plate not less than 2.25 Mtrs below normal ground level, earth plate surrounded from all sides by 30 cm thick and packed layers of charcoal dust, salt and magnesium sulphate in alternate layers and electrode connections by using copper strip lead 50x6mm size by means of copper brazing, provision of 63mm dia GI medium grade pipe for protection of earth strip and 40mm dia GI pipe medium grade 4mm holes at every 15 cm all around the pipe for watering arrangement, funnel, wire mesh and heavy duty polymer earth pit chamber with cover including necessary excavation in any type of soil, returning filling in, removal of surplus soil to a distance not exceeding 50 Mtr and testing of earthing all as specified and directed by Engnieer-in-Charge. (The earth resistance shall be not be more than 0.50 Ohms). |
| 66 | Note :-(i) Charcoal (dust) - 400 Kg, Salt - 200 Kg & Magnesium sulphate (fine crystal) - 100 Kgs.(ii) Copper strip shall be brazed with copper earth electrode.(iii) Alternate layers of charcoal and salt to be laid in the earth pit all around the copper plate i.e. minimum 30 cm all around the plate (i.e. all the six faces) at least 5 layers to be laid.(iv) Alternate layers of charcoal and salt (15 cm each) and a 10 cm layer of magnesium sulphate to be laid.(v) Copper shall pour sufficient amount of water in earth pit before and after earthing and to be rammed properly.(vi) Copper strip is to extended upto the equipment and connected by brazing with the help of brazing strips. Provsion for GI Pipe medium grade 63 mm shall be made upto equipment for protection of earth lead. |
| 67 | M & L Earth continuity conductor or main earthing lead fixed to wall on batten or recess or chases or buried in ground or drawn in conduit/pipe or fixed to poles or any other indicated situation for loop earthing etc. as required but 25x4mm galvanised iron strip all as directed by Engr-in-charge. |
| 68 | M&L for copper strip of size 20x3.15mm fixed on epoxy earth strip insulator of size 25x3.15mm incuding fixing screws and fastners for roof conductors and down conductors above ground level and fixing complete all as specified and directed. |
| 69 | M&L for earth continuity conductor or main earthing lead fixed to wall on batten or recess or chases or buried in ground or drawn in conduit / pipe or fixed to poles or any other indicated situation for loop earthing etc as required GI or steel wire 4.00mm dia complete all as specified and directed. |
| 70 | Supply & fixing Air termination rod, single pointed, copper rod 12mm dia and 300mm long complete all as specified & directed |
| 71 | Supply & fixing Test point terminal block made of gun metal or phosphorus bronze size 75x75x25mm drilled and screwed including 3 nos. 8mm dia 25mm long hex. head screw complete all as specified & directed |
| 72 | M&L for disconnecting the joints made with nut, bolts and washers of earth lead conductors of any type (copper/GI/aluminium) and jointing by means of exothermal joints or brazing by using silver/copper/brass brazing strips complete all as specified and as directed by Engineer-in-Charge. |
| 73 | Supply, laying in trenches or under floor or fixed on walls including all pipe fittings PVC pipe ISI Marked of size 20 mm dia for earthing lead protection including saddle clamps, fastners, nuts, bolts, washers complete all as specified and directed. |
| 74 | Supply, laying in trenches or under floor or fixed on walls including all pipe fittings PVC pipe ISI Marked of size 25 mm dia for earthing lead protection including saddle clamps, fastners, nuts, bolts, washers complete all as specified and directed. |
| 75 | Material & labour for dismantling the existing broken earth pits and supply and fixing prefabricated PCC earth pit covers made of PCC 1:2:4 type B1 using 20mm graded stone aggregate evenly finished, 40mm thick chamber cover made of 1:2:4 type B1 using 20mm graded stone aggregate and reinforced with 8 mm dia TMT bars at 100 c/c on both ways precast chamber cover with lifting handle 16mm dia round bar complete all as specified and directed. Please Enable Macros to View BoQ information |
| 76 | Material & labour for dismantling the existing broken earth pits and supply and fixing prefabricated PCC earth pit covers made of PCC 1:2:4 type B1 using 20mm graded stone aggregate evenly finished, 40mm thick chamber cover made of 1:2:4 type B1 using 20mm graded stone aggregate and reinforced with 8 mm dia TMT bars at 100 c/c on both ways precast chamber cover with lifting handle 16mm dia round bar complete all as specified and directed. Please Enable Macros to View BoQ information |