| 1 | Carriage of departmental materials from Electricity Store Centre at Hapur / J.E. Store to the site of work, including loading and unloading at both ends. The work shall be executed over kachha and pakka roads as per the directions of the Site In-charge. The scope includes arrangement of suitable transport, labour for loading/unloading, and all necessary Tools & Plants (T&P). The carriage distance shall be up to 0–80 Km, covering stores located at Hapur / Ghaziabad / Bulandshahr. |
| 2 | PCC Pole 8.5 mtr |
| 3 | 11 KV Comp. Poly. Disc Insulator 45 kn |
| 4 | Stay Set 16x1800 |
| 5 | M.S. Angle 65x65x6 mm |
| 6 | 11 KV VCB Outgoing CTR 200/100/5AMP |
| 7 | Earth Rod 2540x20 mm |
| 8 | 11 KV MET. CUB. CTR 20/5 AMP Pilfer Proof |
| 9 | 11 KV Composite Polymer Pin Insulator |
| 10 | ACSR Weasel Conductor |
| 11 | MS Channel 100x50 mm |
| 12 | PCC Pole 11 mtr |
| 13 | GI Wire 6 SWG Rusted |
| 14 | Disc Fitting 45 KN (T&C) |
| 15 | GI Wire 4mm/ 8 SWG |
| 16 | 11 KV G.I. X-ARM Angle 65x65x6 mm V-Type |
| 17 | 11 KV Cable Box O/D 3x120 XLPE |
| 18 | 11 KV Cable Box O/D 3x70 XLPE |
| 19 | 11 KV Cable Box I/D 3x120 XLPE |
| 20 | 11 KV Cable H.T. XLPE 3x120 sq.mm |
| 21 | 11 KV H.T. XLPE Cable 3x70 sq.mm |
| 22 | XLPE Aluminium Cable 1x400 sq.mm. |
| 23 | 11 KV HT TVM |
| 24 | Aluminium Lug 400 sq.mm |
| 25 | 11 KV CT/PT MET. U. O/D TYPE CTR 20/5AMP |
| 26 | Erection and fixing of the following materials as per relevant RESPO/departmental norms and specifications, including proper installation, alignment, tightening, and commissioning at site. the scope of work includes cost of all labour, tools & plants (T&P), machinery, drilling/excavation, safety arrangements, protection of existing utilities, and complete site restoration, along with responsibility of the contractor for obtaining necessary permissions, resolving Right of Way (ROW) issues, and completing the work as per directions of Engineer-in-Charge |
| 27 | 11 KV Comp. Poly. Disc Insulator 45 kn |
| 28 | M.S. Angle 65x65x6 mm |
| 29 | 11 KV VCB Outgoing CTR 200/100/5AMP |
| 30 | 11 KV MET. CUB. CTR 20/5 AMP Pilfer Proof |
| 31 | 11 KV Composite Polymer Pin Insulator |
| 32 | MS Channel 100x50 mm |
| 33 | Disc Fitting 45 KN (T&C) |
| 34 | 11 KV G.I. X-ARM Angle 65x65x6 mm V-Type |
| 35 | XLPE Aluminium Cable 1x400 sq.mm. |
| 36 | 11 KV HT TVM |
| 37 | Aluminium Lug 400 sq.mm |
| 38 | 11 KV CT/PT MET. U. O/D TYPE CTR 20/5AMP |
| 39 | Erection & Fixing of single pole structure of PCC pole 8.5 Mtrs of 11 KV line along with X-Arm and pin insulator after digging of suitable pits providing and fixing of shackle insulators, and complete installation of all requisite accessories strictly as per RESPO drawings/standard norms; including providing and fixing of holding clamps made of M.S. flat of size 35×5 mm with suitable nuts & bolts, stone pad, alignment, tightening and all allied works; the scope of work includes cost of all labour, tools & plants (T&P), machinery, drilling/excavation, safety arrangements, protection of existing utilities, formation of pits, and complete site restoration; the contractor shall also be responsible for obtaining all necessary permissions, resolving Right of Way (ROW) issues, and completing the work as per departmental standards and directions of the Engineer-in-Charge. |
| 40 | Erection of 11KV Double-pole structure after digging of suitable pits on following pole with fabrication and fixing of M.S. Top & Dropper Channel, M.S. T/F Angle, E-Bracket, 11 KV Pin insulator with Pin, Disc Insulator with Disc fitting etc., as per RESPO Drawing/Norms by providing all clamps made of M.S. Flat of size 50x6 mm with proper size nuts and bolts and Stone Pad with jumpering etc work, and as per direction of site incharge. All Clamp & Nut bolt will be provided by contractor. |
| 41 | PCC Pole 8.5 Mtrs |
| 42 | PCC Pole 11 Mtrs |
| 43 | Grouting of following ST/PCC supports in CC 1:3:6 (Cement, sand & 40mm brick ballast) Grouting will be done in the block of size (450x450)mm x1/6th of full length of the support, up to ground level, 300mm plinth above the ground level with CC 1:3:6 (Cement, core sand and Stone grit) with mufting as per drawing, work includes back filling & proper ramming by providing all required grouting materials, as per direction of site incharge. |
| 44 | PCC Pole 8.5 |
| 45 | PCC Pole 11 mtr. Long |
| 46 | Construction of RCC transformer plinth of size 2.0 m × 2.0 m × 1.5 m suitable for 400 kVA transformer, including excavation of earth in all types of soil, dressing, leveling and ramming of bed, providing and laying foundation and plinth work using 1st class bricks (approx. 6000 nos.), cement (approx. 14 bags), fine sand, coarse sand, brick ballast and 40 mm stone ballast, complete in all respect as per standard practice and approved drawings; including providing and fixing of MS Channel 125×65 mm (approx. 54 kg) and MS twisted bar 20 mm dia (approx. 50 kg) for reinforcement and structural support, centering, shuttering, curing, finishing and grouting as required. The item includes backfilling, compaction, disposal of surplus earth, making cable entry/exit provisions and all allied civil works. The scope of work shall include cost of all materials, labour, tools and plants (T&P), loading/unloading, carriage, and all incidental charges. The work also includes compliance of ROW (Right of Way) conditions, obtaining necessary permissions, ensuring barricading, safety arrangements, traffic management if required, and restoration of site to original condition, complete as per direction of Engineer-in-Charge. |
| 47 | Safe loading at store, transportation to site, unloading, erection, testing and commissioning of new 400 kVA, 11/0.433 kV distribution transformer including handling with suitable crane/vehicle, proper placement on plinth/DP structure, alignment, fixing and complete installation with all accessories such as HT/LT connections, bushings, breather with silica gel, conservator assembly, earthing of body and neutral, connection through DO fuse/AB switch on HT side and LT cable/DB on LT side, including cable dressing; testing comprising IR test, ratio test, oil level/leakage check, polarity and continuity test and trial run; complete with cost of all materials, labour, tools and plants T&P, loading unloading, carriage, consumables, safety arrangements, compliance of ROW conditions and restoration of site as per direction of Engineer in charge. |
| 48 | Providing and installation of complete earthing system for 400 kVA, 11/0.433 kV distribution transformer and others using pipe earthing method in water level condition, including boring/drilling up to required depth reaching water lable 80 feet, supply and installation of GI perforated earth electrode pipe of 2 inch diameter and length, backfilling with alternate layers of charcoal/coke and salt, construction of brick masonry chamber with RCC cover, providing and laying GI strip/wire of 50mm x 6mm size from electrode to transformer body and neutral with proper clamping, nut bolts and anti-corrosion treatment; including watering arrangement with funnel and mesh, testing and commissioning of earthing system to achieve earth resistance value not exceeding 1 ohm for transformer body earthing and not exceeding 0.5 ohm for neutral earthing or as per relevant standards. The item includes cost of all materials, labour, tools and plants T&P, excavation, backfilling, carriage, consumables, safety measures and all incidental works, complete as per specification and direction of Engineer in charge. |
| 49 | Providing and erection of MS safety fencing for 400 kVA distribution transformer of size approx. 3.5 m × 3.5 m × 2.5 m height, including supply, fabrication and fixing of MS angle posts of size 50×50×6 mm at suitable spacing (not exceeding 2.5 m c/c), with intermediate horizontals of MS flat/angle, and covering with chain link mesh 8 SWG of 50×50 mm mesh size or expanded metal as approved; complete with excavation of pits, PCC foundation (1:4:8) for posts, grouting, proper alignment and fixing. The work also includes providing and fixing of MS gate of size approx. 1.2 m × 2.1 m with suitable hinges and locking arrangement, danger board, anti-climbing arrangements using barbed wire, and painting with one coat of red oxide primer and two coats of synthetic enamel paint. The item includes cost of all materials, labour, tools and plants T&P, fabrication, cutting, welding, carriage, loading/unloading, erection, finishing and all incidental works, including compliance of ROW conditions, safety measures, barricading and restoration of site, complete as per approved drawing and direction of Engineer-in-Charge. |
| 50 | Providing, installing, testing and commissioning of tailless fuse set of 630A unit suitable for 400 KVA distribution transformer, including dismantling of existing tail connections (if any), supply and fixing of required LT/HT connectors, busbar arrangements, insulated sleeves, and necessary termination accessories; complete modification of transformer LT side to tailless configuration ensuring proper phase segregation, insulation and mechanical strength; including providing and fixing of suitable size aluminium/copper lugs, glands, ferrules, heat shrink sleeves, PVC insulation tape, nut-bolts, washers and all jointing materials as required; making proper cable terminations, dressing and clamping of cables with GI clamps; providing and ensuring effective earthing of the tailless unit with GI strip/wire and connecting to existing earthing system; including painting of modified portion with suitable anti-corrosive paint; complete testing for continuity, insulation resistance and proper load transfer; the work shall be carried out as per relevant IS standards, RESPO/departmental specifications and as directed by Engineer-in-Charge; the rate shall include cost of all materials, labour, tools & plants (T&P), handling, loading/unloading, transportation, and all incidental works required to complete the job in all respects. |
| 51 | Providing, laying, jointing and commissioning of 140 mm dia (OD) PN-4, PE-80 grade UV stabilized HDPE pipe in 6.0 mtr standard length by trenchless (HDD/drilling) method for underground cable protection, including excavation of suitable size launching and receiving pits, alignment and preparation of bore path, drilling, reaming and insertion/pulling of HDPE pipe, jointing by butt fusion/electrofusion with all necessary fittings such as couplers, bends and end caps, ensuring proper alignment and leak-proof joints; including providing and laying of warning tape, route markers and identification system; complete with all required tools & plants (T&P) such as HDD machine, drilling machine, compressor, generator, welding machine, including all consumables, loading/unloading, handling and safe stacking at site; including dewatering (if required), traffic control, barricading and safety measures; also including restoration of road, Footpath, drain or any other surface under ROW (Right of Way) conditions to original condition and disposal of surplus earth/muck; complete in all respects as per relevant IS standards, RESPO/departmental norms and direction of Engineer-in-Charge, with all material, labour, T&P, transportation and incidental charges included in the rate. (Rate will be charge as per actual length of work) |
| 52 | Laying of 11 KV H.T. XLPE Cable 3x70 sq.mm undergound into HDPE Pipe, spare cable shall be left in the loop shape at both ends as per RESPO/Norms, as per direction of site incharge.(Rate will be charge as per actual length of work) |
| 53 | Manually Digging excavation of trench of size 0.50 m width × 1.00 m depth in all types of soil including dressing, levelling and disposal of surplus excavated earth within specified lead as per RESPO/drawing norms and direction of Engineer-in-Charge; supplying and laying of brick masonry (class designated) in cement mortar for side protection, providing and filling of sand cushioning at bottom and around the laid cable, followed by laying of PCC (Plain Cement Concrete) of required grade for base and protective covering over trench; thereafter, placing and proper alignment of XLPE cable within the complete trench, and covering the trench with brick/CC slab protection including backfilling with excavated earth in layers, watering, ramming and proper compaction complete in all respects; the scope of work includes cost of all labour, materials (bricks, sand, cement, aggregates, water etc.), handling, loading/unloading, carriage, and all Tools & Plants (T&P) required for excavation, laying and finishing works, with all safety precautions, as per standard specifications and directions of site in-charge. and also including restoration of Kaccha/Puccha Road (The Firm will be fully responsible for this work and taking necessary permission), as per direction of site incharge (Rate will be charge as per actual length of work). |
| 54 | Laying and installation of following cable in underground trench in double circuit formation, including careful handling, dressing and alignment of cable along the route as per RESPO/drawing norms and direction of Engineer-in-Charge; laying of cable over prepared sand bed, maintaining proper spacing between circuits, and ensuring identification and phase marking; providing extra length of cable at both ends in loop formation for future jointing/termination (spare cable to be left in loop shape at each end) as specified; covering of cable with sand cushioning, protective bricks/tiles/CC slabs and backfilling of trench with excavated earth in layers, watering, ramming and proper compaction complete in all respects; including supply of all consumables such as sand, bricks, cable markers, route indicators, etc., and all labour, loading/unloading, carriage, handling charges, testing prior to commissioning, and all Tools & Plants (T&P) required for safe and proper execution of work as per standard specifications and site instructions. |
| 55 | 11 KV H.T. XLPE Cable 3x120 sq.mm |
| 56 | 11 KV H.T. XLPE Cable 3x70 sq.mm |
| 57 | Providing & Fixing of G.I. pipe 6\\"dia Class-B over 11KV/33 KV XLPE cable before mounting the cable at double pole. The work includes fitting of clamps, sealing of top and bottom of pipe and one end of pipe is to be burried under earth about 500mm earch including mounting and clamping the cable on double pole structure and making connection with overhead line at both ends, as per direction of site incharge. |
| 58 | Laying , Stringing and final sagging of ACSR Weasel Conductor, as per RESPO/ Drawing Norms and as per direction of site incharge. |
| 59 | Fabrication of Guarding Angle other requisites material for guarding by drawing 02Nos G.I Wire and making loop at suitable distance as per RESPO drawing/Norms by providing holding clamps, 02Nos. Eye bolts made of M.S. round size 12mm dia-100mm long & Cross Arm clamps made of M.S. Flat of size 50X6mm and bolts as per norms of RESPO norms, includes all labour, tools & plants (T&P), fabrication, fitting, alignment, tightening, safety arrangements and all allied works will be provided by contractor, as per departmental standards and directions of the Engineer-in-Charge. as per direction of site incharge. (only Guarding Angle & GI Wire will be provided by Department). |
| 60 | G.I. Wire 4mm/ 8 SWG |
| 61 | G.I. Wire 5mm/ 6 SWG |
| 62 | Grouting & fixing of stay Set (20x1800)mm including all work of excavation, cement concrete in size (0.60x0.60x0.30)m in ratio 1:4:8 cement, sand, 40mm brick ballast as per drg. Including back filling, proper ramming etc and fixing tightening & nozzling of stay wire with stay rod with the poles of required tension as per drawing as per RESPO Drawing/Norms by providing all grouting material and stay clamp made of M.S. Flat of size 50x6mm with proper size bolts & nuts & loops, includes all labour, tools & plants (T&P), fabrication, fitting, alignment, tightening, safety arrangements and all allied works will be provided by contractor, as per departmental standards and directions of the Engineer-in-Charge. |
| 63 | Earthing of supports with MS earth Rod of (20x2540)mm long including excavation of pit and driving M.S. Rod 3.0 M apart from support and 0.5m below the ground level and connection below the earth electrodes with the help of G.I. wire & earthing lugs as per RESPO Drawing/Norms includes all labour, tools & plants (T&P), fabrication, fitting, alignment, tightening, safety arrangements and all allied works will be provided by contractor, as per departmental standards and directions of the Engineer-in-Charge. only earth rod and GI wire will be provided by department. |
| 64 | Providing and fixing of all types of clamps including F-type clamps, holding clamps, cross-arm clamps, LT clamps, etc., along with suitable nuts & bolts, complete in all respects strictly as per RESPO drawings/standard norms and directions of the Site In-charge; the scope of work includes all labour, tools & plants (T&P), handling, installation, alignment, tightening, safety arrangements and all allied works necessary for proper completion of the work as per departmental standards and directions of the Engineer-in-Charge. |
| 65 | F-Bracket with clamp |
| 66 | Holding clamp with Nut & Bolt |
| 67 | Gaurding Angle Clamp |
| 68 | Providing and fixing of Nut & Bolts as per RESPO/Norms and as per direction of site incharge. |
| 69 | Providing and fixing of stone pad 300x300x75 of approved quality and specified size at pole/support locations, including excavation of suitable size pit, preparation of base, dressing, leveling, and proper placement in line and level as per RESPO drawings/standard specifications and direction of Engineer-in-Charge, including refilling, ramming and consolidation to ensure stability; the scope of work includes cost of all labour, loading/unloading, carriage, alignment and all incidental works required for complete execution, and all tools & plants (T&P), equipment and tackles shall be arranged and provided by the contractor at his own cost. |
| 70 | Providing and fixing of danger board of approved design, size and material with proper statutory warning sign and lettering, complete with suitable M.S. clamp, nuts, bolts and washers, to be rigidly mounted on pole/structure at required height ensuring proper alignment and visibility, as per RESPO drawings/standard specifications and direction of Engineer-in-Charge; the work includes drilling of holes, fitting, tightening, handling, loading/unloading, carriage to site, and all incidental works required for complete installation, and the cost includes all labour, consumables and minor accessories, while all tools & plants (T&P), equipment and tackles required for execution shall be arranged and provided by the contractor at his own cost. |
| 71 | Providing, fabricating and fixing of cross bracing using MS angle set of approved size (e.g., 50×50×5/6 mm or as per drawing) for pole/structure strengthening, including cutting, drilling, welding and proper fitting in diagonal position between poles/structure members, complete with suitable nuts, bolts, washers and clamps; ensuring proper alignment, tightening and rigidity of structure. The work includes cost of all materials, labour, tools and plants (T&P), fabrication, carriage, loading/unloading, erection and all incidental works, complete as per standard specifications and direction of Engineer-in-Charge. |
| 72 | Providing and fixing of aluminum binding wire of approved gauge for binding of conductor with insulators and accessories on overhead line, including cutting, tying, wrapping and proper securing to ensure firm and reliable connection as per standard practice; complete with all materials, labour, tools and plants (T&P), carriage, loading/unloading and all incidental works, as per specification and direction of Engineer-in-Charge. |
| 73 | Providing and fixing of barbed wire of approved quality and specification in position, stretched and secured on poles/structures with suitable binding wire, staples, clamps or other approved means, maintaining proper tension, alignment and height as per RESPO drawings/standard specifications and direction of Engineer-in-Charge; the work includes handling, loading/unloading, carriage to site, cutting, jointing, tightening and all incidental works required for complete installation, and the cost includes all labour, consumables and minor accessories, while all tools & plants (T&P), equipment and tackles required for execution shall be arranged and provided by the contractor at his own cost. |
| 74 | Providing and fixing of number plate of approved size, design and material with proper painting/printing of identification number and lettering, to be securely mounted on pole/structure at suitable height ensuring proper alignment and visibility, as per RESPO drawings/standard specifications and direction of Engineer-in-Charge; the work includes drilling of holes, fixing with suitable clamps, nuts, bolts or binding wire as required, handling, loading/unloading, carriage to site and all incidental works necessary for complete installation, and the cost includes all labour, consumables and minor accessories, while all tools & plants (T&P), equipment and tackles required for execution shall be arranged and provided by the contractor at his own cost. |
| 75 | Making and filling of 11KV Cable Jointing Kit, Indoor/outdoor type, after duly plumbing and taping of suitable XLPE Cable, providing, fixing and crimping of proper size good quality lugs, including cost of lugs and tape etc., as per RESPO Norms, and as per direction of site incharge. |
| 76 | 11 KV Cable Box O/D 3x120 XLPE |
| 77 | 11 KV Cable Box O/D 3x70 XLPE |
| 78 | 11 KV Cable Box I/D 3x120 XLPE |
| 79 | jumpering of LT/HT lines for proper energization, including cutting, dressing, binding and fixing of jumpers with suitable connectors/clamps, ensuring proper electrical continuity and safety, complete in all respects strictly as per RESPO drawings/standard norms and directions of the Site In-charge; the scope of work includes all labour, tools & plants (T&P), handling, installation, tightening, safety arrangements and all allied works necessary for proper completion of the work as per departmental standards and directions of the Engineer-in-Charge. |
| 80 | Providing services for cutting/trimming of trees and branches interfering with LT/HT electrical lines, including clearance of vegetation for safe operation and maintenance of lines, complete in all respects as per departmental standards and directions of the Site In-charge; the scope of work includes all labour, tools & plants (T&P), machinery, safety arrangements, cutting, stacking and disposal of cut material, protection of existing utilities, obtaining necessary permissions from concerned authorities, and all allied works required for proper completion of the work as per directions of the Engineer-in-Charge. |
| 81 | safe dismantling of existing/old electrical materials at site, including careful removal without damage to reusable items, and carriage of dismantled materials from site of work to Electricity Store Centre, Hapur, with loading and unloading at both ends over kachha and pakka roads, strictly as per directions of the Site In-charge; the scope of work includes all labour, tools & plants (T&P), handling, transportation, safety arrangements and all allied works necessary for proper completion of the work as per departmental standards and directions of the Engineer-in-Charge. Please Enable Macros to View BoQ information |