| 1 | Day to day maintenance of feeder pillars and its accessories along with checking of pump sets as per inventory, terms and condition attached. |
| 2 | Lifting out of submersible pump set from the exiting bore well up to the required depth along with existing G.I. pipes and accessories etc. i/c dismantling of G.I pipe and disconnecting the sub. cable etc. complete as reqd. |
| 3 | Lowering & commissioning of sub. pump set in the existing bore well up to the required depth along with existing G.I pipe and sub. cable etc., water proof jointing of sub. cable, Replacement of reqd. nuts- bolts, washers and packing, nipple, reducer, connection, testing etc. complete as reqd. |
| 4 | Supplying/Replacement of PVC insulated copper conductor flat submersible cable of size 1 x 3 x 2.5 sq. mm i/c connection testing etc. compete as reqd. |
| 5 | Repairing & rewinding of sub. motors of following capacity with cartage, dismantling, reassembling i/c supply & replacememt / repairing of damaged parts of motors and making good for operation i/c connection, testing, painting etc. complete as reqd. a) 3 HP to 5 HP, 3 Ph. sub motors. |
| 6 | b) Upto 2 HP, 3 Ph./1Ph. sub motors. |
| 7 | a) 6 HP to 7.5 HP, 3PH. Sub. motor |
| 8 | Repairing of sub. pump of the following stages & dia with cartage, dismantling, reassembling, supply & replacement / repairing of damaged parts of pump and making good for operation i/c testing, painting etc. complete as reqd. a) 6\\"dia submersible pump sets upto 5 stages. |
| 9 | b) 6\\"dia submersible pump sets 6 stages & upto 8 stages |
| 10 | c)Upto all stages 4\\" dia submersible pump sets |
| 11 | Repairing & rewinding of 3 Phase, mono block sub. Pump set with cartage, Dismantling, Reassembling, Supplying & replacement/Repairing of damaged parts of pump set i/c bearing& bush and making good for operation i/c connection, testing, painting etc. complete as required.a) 5HP/7.5HP |
| 12 | Supplying & replacement of following control gear / accessories in the existing installation for electric panel boards, motor starters, connection, testing etc. as reqd. a) 63 AMP TPN MCB (C -Series). |
| 13 | b) Single phase preventor with auto-reset feature |
| 14 | C) 32 AMP TP&N MCB (C-Series). |
| 15 | e) 0-30 AMP Ammeter (96mm x 96mm square dial flush mounted) |
| 16 | f) 0-500 Volt Voltmeter(96mm x 96mm square dial flush mounted) |
| 17 | g) DOL Starter suitable up to 7.5 HP pump set with relay range 9-14 amp. |
| 18 | h) Thermal Overload relay with range 9-14 amp. |
| 19 | i) Contactor block for up to 7.5 HP DOL Starter |
| 20 | j) Operating coil/No volt coil 400/440 Volt 50 Hz |
| 21 | j) 4 Pole MCCB 100 Amp. 30 K.A. |
| 22 | Taken out of fallen & stuck sub. pump set from the existing bore well up to all depth along with sub. cable, G.l Pipe etc. complete as reqd. |
| 23 | Supplying and making straight through joint with heat shrinkable kit including ferrules and other jointing materials for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 kV grade as required. a) 4 X 25 sq. mm |
| 24 | b) 4 X 50 sq. mm |
| 25 | Supplying of following size XLPE insulated & PVC sheathed, aluminum conductor armoured power cable of 1.1 kV grade, connection testing etc. as reqd. a) 4 x 25 sq mm. |
| 26 | b) 4 x 50 sq mm |
| 27 | Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 kV grade of following size in the existing RCC/ HUME/ METAL pipe as required. a) Upto 35 sq. mm |
| 28 | b) Above 35 sq. mm and upto 95 sq.mm. |
| 29 | Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 kV grade of following size direct in ground including excavation, refilling the trench etc. as required, but excluding sand cushioning and protective covering. a) Upto 35 sq. mm |
| 30 | b) Above 35 sq. mm and upto 95 sq.mm. |
| 31 | Repairing of existing feeder pillar i/c replacment of 2 mm thick CRCA sheet in front / side door with welding of hinges, gasketted cover, handle, locking arrangement painting with both sides etc as reqd. |
| 32 | Repairing of existing panel foundation with brick, cement mortar and plastering the same including disconnection of existing cable and reconnection etc. complete as reqd. |
| 33 | Repairing of existing wiremesh protection frame including supplying & fixing of 8 SWG M.S. wiremesh (of size 75mm x 25mm) with M.S. angle iron base frame (of size 35mm x 35 mm x 5 mm), cutting, welding, painting, making locking arrangement etc. complete as reqd. |
| 34 | Supplying and laying of following size DWC HDPE pipe ISI marked along with all accessories like socket, bend, couplers etc. conforming to IS 14930, Part II complete with fitting and cutting, jointing etc.direct in ground (75 cm below ground level) including excavation and refilling the trench but excluding sand cushioning and protective covering etc., complete as required. a)63 mm dia (OD-63 mm & ID-51 mm nominal) |
| 35 | Hire charges for cable fault locating machine to locate the fault in the existing underground LG cable etc. as reqd. |
| 36 | Digging out of 1 no. faulty PVC insulated, PVC sheathed/XLPE power cable laid in ground and relaying of the same after removing of the cable fault i/c refilling and redressing of the trench etc. as reqd. |
| 37 | Supplying, Replacement (Dismantling the existing feeder pillar), testing and commissioning of floor mounted L.T. feeder pillar (pump panel) cubical type double door of size 1000 mm x 900mm x 300 mm deep with general arrangement made out of 2mm thick M.S. CRCA sheet having hinged gasket covers and screwed knobs with double locking arrangement and rain protection covers (100 mm), supported with MS angle iron legs and bottom frame of size 35mm x 35mm x 5mm x 1mtr. long grouted with 1:3:6 CC foundation and should be 0.7 mtr. above ground level. Legs should be covered with brick walls, duly 1:4 cement plaster, connections, inter connections with suitable size of FRLS PVC insulated copper conductor using thimbles, ferrules wherever required, painting, numbering, earth studs including supply and fixing of following accessories complete as required(as per drawing approved by Engineer-in-charge) .(a) 125 Amps. 4 pole MCCB, 36 K Amp.--1No.(b) 3 phase DOL submersible pump starter & C-Curve TP MCB with suitable relay range of 13 to 22 Amp. --- 1 Set.(c) 32 Amps. DP MCB ('C'-Series)------1No.(d) 32A TP & N MCB (C-series)----2 No.(e) Danger notice plate -----1 No(f) Lifting hook on the top of feeder pillar ---1Set.(g) AI. Bus Bar 150 amp. 4 strip, 300 mm long with sleeve and nut bolts-----1 Set.(h) Ammeter (0-100Amp) 96mm X 96mm square type ---1 No.(i) Voltmeter (0-500 Volt) 96mm X 96mm square type with selector switch ---1 No.(j) Phase Indicating Lamp Set with fuses ----1 Set. |
| 38 | Supplying, Replacement (Dismantling the existing feeder pillar), testing and commissioning of floor mounted L.T. feeder pillar (meter panel) cubical type double door of size 1000 mm x 900mm x 300 mm deep with general arrangement made out of 2mm thick M.S. CRCA sheet having hinged gasketted covers and screwed knobs with double locking arrangement and rain protection covers 100 mm, supported with MS angle iron legs and bottom frame of size 40mm x 40mm x 6mm x 1mtr. long grouted with 1:3:6 CC foundation and should be 0.7 mtr. above ground level. Legs should be covered with brick walls, duly 1:4 cement plaster, connections, inter connections with suitable size of FRLS PVC insulated copper conductor using thimbles, ferrules wherever required, painting, numbering, earth studs including supply and fixing of following accessories complete as required (as per drawing approved by Engineer-in-charge) . (a) Incomer 250 Amps. 4 pole MCCB, 36 K Amp.--1No. (b) Neutral link - 2 nos. (c) 32 Amps. DP MCB ('C'-Series)------1No. (d) 32A TP MCB (C-series)----1 No. (e) 63 amp TPN MCB-----2 nos. (e) Danger notice plate -----1 No (f) Lifting hook on the top of feeder pillar ---1Set. (g) AI. Bus Bar 250 amp. 4 strip, 300 mm long with sleeve and nut bolts-----1 Set. (h) Ammeter (0-100Amp) 96mm X 96mm square type ---1 No. (i) Voltmeter (0-500 Volt) 96mm X 96mm square type with selector switch ---1 No. (j) Phase Indicating Lamp Set with fuses ----1 Set (k) Suitable space for energy meter along with bakelite sheet ---- 1 no. |
| 39 | Supplying, Replacement (Dismantling the existing feeder pillar), testing and commissioning of floor mounted L.T. feeder pillar (distribution panel) cubical type double door of size 1000 mm x 900mm x 300 mm deep with general arrangement made out of 2mm thick M.S. CRCA sheet having hinged gasketted covers and screwed knobs with double locking arrangement and rain protection covers 100 mm, supported with MS angle iron legs and bottom frame of size 35mm x 35mm x 5mm x 1mtr. long grouted with 1:3:6 CC foundation and should be 0.7 mtr. above ground level. Legs should be covered with brick walls, duly 1:4 cement plaster, connections, inter connections with suitable size of FRLS PVC insulated copper conductor using thimbles, ferrules wherever required, painting, numbering, earth studs including supply and fixing of following accessories complete as required (as per drawing approved by Engineer-in-charge) .(a) Incomer 250 Amps. 4 pole MCCB, 36 K Amp.--1No.(b) Neutral link - 2 nos.(c) 32 Amps. DP MCB ('C'-Series)------2Nos.(d) Danger notice plate -----1 No(e) Lifting hook on the top of feeder pillar ---1Set.(f) AI. Bus Bar 250 amp. 4 strip, 300 mm long with sleeve and nut bolts-----1 Set.(g) Ammeter (0-100Amp) 96mm X 96mm square type ---1 No.(h) Voltmeter (0-500 Volt) 96mm X 96mm square type with selector switch ---1 No.(i) Phase Indicating Lamp Set with fuses ----1 Set(j) Incomer 125 Amps. 4 pole MCCB, 36 K Amp.-- 3Nos. |
| 40 | Supplying and replacement of submersible pump sets (water filled motor) operating on 3 phase, 415 Volts, 50 Hz of following specification including lifting of dismantle Pump set & Lowering of new submersible pump set in the existing bore well up to the required depth along with existing G.I. pipes and sub. Cable etc. water proof, jointing of sub. cable, Replacement of reqd. nuts- bolts, washers and packing, nipple, reducer, connection, testing etc. complete as reqd . a) Approximate Head Range (m)-44 m - 99 m b) Approximate Discharge Range (L / min)-100 L / min - 233 L / min c) Capacity – 5 HP d) No. of stages - 17 e) Delivery Size- 50 mm |
| 41 | Supplying and replacement of submersible pump sets (water filled motor) operating on 3 phase, 415 Volts, 50 Hz of following specification including lifting of dismantle Pump set & Lowering of new submersible pump set in the existing bore well up to the required depth along with existing G.I. pipes and sub. Cable etc. water proof, jointing of sub. cable, Replacement of reqd. nuts- bolts, washers and packing, nipple, reducer, connection, testing etc. complete as reqd . a) Approximate Head Range (m)- 55 m - 150 m b) Approximate Discharge Range (L / min)-50 L / min - 150 L / min c) Capacity – 5 HP d) No. of stages - 11 e) Delivery Size- 50 mm |
| 42 | Supplying of sewage treated water submersible pump set duly coupled with suitable rating 3 phase , 415 volt, SO Hz, 3000 RPM Submersible Motor . The pump set shall be suitable for following duties:- ... i)Capacity : 3 HP i)Discharge : 640-100 LPM ii) Head Range :10-18 mtr iii)Liquid: Sewage iv)Solid handling Capacity : 35 mm v) Outlet Size: 50 mm |
| 43 | Supplying and replacement of vertical check valve made up of gunmetal having size 50 mm including S/F of thread , connection testing etc. as required. |
| 44 | Supplying & replacement of following dia cast iron double flanged swing type non return valve as per IS 5312 (part 1&2) PN 1.0, body & disc : C.I , body ring: Bronze, hinge pin: AISI 410 testing etc. complete as required.a) 65 mm dia |
| 45 | b) 50mm dia. |
| 46 | Supplying and Replacement of Following size double flanged of \\"B\\" class heavy Duty GI Pipe conforming to IS:1239 including welding, Fitting like Elbows, tees, Flanges, Tapers, Nuts, Bolts, Gaskets etc.a)40 mm dia. |
| 47 | b) 50 mm dia |
| 48 | c) 65 mm dia. |
| 49 | Painting of existing wire mesh protection frame & feeder pillar of different size with 2 Nos. of enamel paint coating including primer, cleaning etc. complete as required. |
| 50 | Earthing with G.I. earth pipe 4.5 meter long, 40 mm dia. including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe etc. with charcoal/ coke and salt as required. |
| 51 | Providing and fixing 25 mm X 5 mm G.I. strip on surface or in recess for connections etc. as required |
| 52 | Supplying, Fabrication, replacement and Installation of wire mesh protection frame for existing feeder pillar made out of 8 SWG M.S wire mesh size (75mmX25mm rectangle nominal) of following size with M.S angle iron base frame 35mm X 35mm X 5mm angle iron and with M.S strip support of size 35mm X 5mm in cross and 0.5mtr long legs support of same angle (as per drawing attached), i/c door in front portion, supplying and fitting of go down lock i/c locking arrangement, painting and grouting of angle iron frame with lugs in CC 1:3:6 foundation etc. as approved by Engineer- in-charge etc. complete as regd. (a) 2 mtr (H) X 1.5 mtr (W) X 1.0 mtr (D) Please Enable Macros to View BoQ information |