| 1 | Item Rate BoQ BoQ_Ver3.0 Item Rate Normal INR Only INR Select, Excess (+), Less (-) Less (-) Tender Inviting Authority: Executive Engineer Electric Division -II JPDCL Jammu Name of Work: Rate contract for Augmentation of 400 KVA to 630 KVA Distribution Substations at different locations within the jurisdiction of Electric Division-II Jammu during the Financial Year 2026-27 Contract No: E-Nit No. 18 of 2026-27 Dated 07-06-2024. Bidder Name : PRICE SCHEDULE(This BOQ template must not be modified/replaced by the bidder and the same should be uploaded after filling the relevent columns, else the bidder is liable to be rejected for this tender. Bidders are allowed to enter the Bidder Name and Values only ) NUMBER # TEXT # TEXT # NUMBER # TEXT # NUMBER NUMBER TEXT TEXT # NUMBER # TEXT# TEXT # NUMBER # NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER # NUMBER # TEXT TEXT NUMBER # NUMBER # DATE NUMBER # NUMBER # TEXT # |
| 2 | Item Description |
| 3 | Augmentation of 11/0.433kV, 400 KVA to 630 KVA , 3-phase Distribution Substation |
| 4 | Supply, Installation & commissioning of 11/0.433 KV, 630 KVA 3-Phase Distribution Transformer with Bi-metallic terminal Connectors, Energy Level: 2, \\"BIS Marked\\" (Copper Wound) alongwith LV Cable Box having detachable Alumnium Gland plate including Transportation (As per latest amendments and IS) Note: Dismantling and Write Back of dismantled 400 KVA Distribution Transformer and allied material to Divisional store at Miran Sahib which includes labour and mechanical carriage charges involved . |
| 5 | Supply, Transportation, Erection of 9 Mtr Long ST Pole (ST-410 SP33) including excavation of pit and back filling of soil & consolidating by ramming, watering etc. Including painting with two coats of Red Oxide and Al. Paint for smooth surface. |
| 6 | Supply & Fixing of Gapless Surge Arrestor,9 kV ,10 kA ,LA with polymer housing, Stn. Type |
| 7 | Supply, Installation, Testing & Commissioning of 11kV GO, AB Switch 3-Phase, 3-Pole, 200 Amp, Vertical Type |
| 8 | Supply, Installation, Testing & Commissioning of 11 kV Horn Gap Fuse Set 3 Phase 200A |
| 9 | Providing & Fixing of Single Phase PVC Cable 630 mm² ,1.1K V Grade, PVC Insulated Stranded Un-Armoured FRLS type alongwith Al. Thimbles for 630 mm² Cable termination with four colored PVC Tapings to distinguish the LT Phases and the Neutral. (2 Ckt) |
| 10 | Providing of Earthing of substation --Excavation of earth pit of dia 650 mm & depth 3000 mm, installation of Earthing pipe of 40 mm Nominal bore & 4mm wall thickness & length 2.5 mtr long as Per IS 1239.GI Strip for neutral earthing of size 25 mm x 3 mm for connection of transformer body,G.O Set & lightening arrestor as per IS 2629/85, GI nuts & bolts,refilled with earth enhancement materials and earth Chamber made of brick masonary with RCC slab cover. |
| 11 | Providing & Fixing of LT Distribution Box with 2No 630Amp Triple Pole MCCB for incomer with adjustable overload release of (80-100%) & switch fuse unit for Out Going 2No Ckts. including Busbar arrangements for Phases & Neutral of EC Grade Aluminium,PVC Insulated Sleeved Busbar of required load handling capacity with colour code for Phases and Neutral differentiation, including Aluminium thimbles of required sizes for proper termination etc. |
| 12 | Construction of Concrete-Cement (1:2:4) Platform (8x8x3) & 3feet below ground level ) for 630 KVA SubStation along with the mesh fencing (with two coats of metal oxide & Al. Paint) around the Periphery. (complete Job) |
| 13 | Providing & Fixing of Danger Plates with Clamps |
| 14 | Providing & Fixing of Anti Climbing device with Clamps |
| 15 | Providing of Cement bottoming 1:2:4 mix as per REC standards 0.5cum/pole Total in Figures 0.0 0.0 Zero Only 4.0 Construction of chamber for 100mm sluice plates item5 10.0 No Quoted Rate in Figures Select 0.0 0.0 Zero Only Quoted Rate in Words INR Zero Only Please Enable Macros to View BoQ information |