| Sr No | Corrigendum Date | Corrigendum | Type | New Submission Date |
|---|---|---|---|---|
| 1 | 30-05-2026 | Extension2 | Date | 05-06-2026 |
| 2 | 21-05-2026 | Extension1 | Date | 29-05-2026 |
| 3 | 21-05-2026 | Extension1 | Date | 29-05-2026 |
| 4 | 07-05-2026 | corrigendum | Other | 29-05-2026 |
| 5 | 07-05-2026 | corrigendum | Other | 05-06-2026 |
| Sl. No. | Item Description |
| 1 | Annual rate contract for “Repairs and Maintenance of 33/11kv Receiving Stations Falling under the jurisdiction of Sub-Transmission Division-II, Rajbagh, Srinagar for the year 2026-27 or till next rate contract. |
| 2 | Disconnecting of damaged11KV VCB Panel/ 33KV C&R Panel/33KV VCB / MOCB from Circuit including dismantling of its accessories complete job (Including shifting of power cables/control cables as and when required as per site requirement and then relaying of same back to its original postion, loading,transportation and unloading & stacking at the divisional store) |
| 3 | Supply,Installation,testing and commissioning of 11KV VCB compatible with existing 11KV VCB Panel. |
| 4 | Supply,Installation,testing and commissioning of 33KV VCB compatible with existing 33KV VCB |
| 5 | Installation,testing and commissioning of 33KV VCB compatible with existing 33KV VCB .,(material to be provided by the department) |
| 6 | Installation,testing and commissioning of 11KV VCB Panel complete ,(material to be provided by the department) |
| 7 | Installation,testing and commissioning of 33KV C&R Panel complete (material to be provided by the department) |
| 8 | Supply,Installation,testing and commissioning of 33KV C&R Panel compatible with existing 33KV VCB . |
| 9 | Supply,installation,testing and commissioning of fresh 11KV C.T by way of Replacement of Damaged/Burnt Out 11 KV C.T of same ratio,type,make and class already installed in panel confirming to IEC 60044-1-2000 standards suitable for 11KV VCB Panels of make already installed at Receiving Stations |
| 10 | Installation,testing and commissioning of fresh 11KV C.T by way of Replacement of Damaged/Burnt Out 11 KV C.T of same ratio,type,make and class already installed in panel confirming to IEC 60044-1-2000 standards suitable for 11KV VCB Panels of make already installed at Receiving Stations, .(material to be provided by the department) |
| 11 | Supply,installation,testing and commissioning of 11KV P.T by way of Replacement of Damaged/Burnt Out 11 KV P.T of same ratio,type,make and class already installed in panel confirming to IEC 60044-1-2000 standards suitable for 11KV VCB panels of make already installed at Receiving Stations |
| 12 | Installation,testing and commissioning of 11KV P.T by way of Replacement of Damaged/Burnt Out 11 KV P.T of same ratio,type,make and class already installed in panel confirming to IEC 60044-1-2000 standards suitable for 11KV VCB panels of make already installed at Receiving Stations, .(material to be lrovided by the department ) |
| 13 | Providing and fixing of Breaker contact set for 11KV VCB by way of Replacement of Damaged/Burnt Out male contact set of same composition,type,make and class already installed in 11KV VCB panel s installed at Receiving Stations |
| 14 | fixing of Breaker contact set for following 11KV VCB by way of Replacement of Damaged/Burnt Out male contact set of same composition,type,make and class already installed in 11KV VCB panel of make already installed at Receiving Stations , including its loading , transportation, unloading and carriage by manual or mechanical means etc complete job.(material to be provided by the department ) |
| 15 | Supply,installation,testing and commissioning of 11 KV Espout Bushing for 11KV VCB Panels by way of replacement of Damaged/Burnt Out 11 KV Espout Bushing of same type,make and class already installed in panel confirming to IEC 60044-1-2000 standards suitable for 11KV VCB panels of make already installed at Receiving Stations |
| 16 | Installation,testing and commissioning of 11 KV Espout Bushing for 11KV VCB Panels by way of replacement of Damaged/Burnt Out 11 KV Espout Bushing of same type,make and class already installed in panel confirming to IEC 60044-1-2000 standards suitable for 11KV VCB panels of make already installed at Receiving Stations .(material to be provided by the department ) |
| 17 | Supply,installation,testing and commissioning of 11 KV Bush with rods for 11KV VCB Panels by way of replacement of Damaged/Burnt Out 11 KV Bush with rods of same type,make and class already installed in panel confirming to IEC 60044-1-2000 standards suitable for 11KV VCB panels of make already installed at Receiving Stations |
| 18 | Installation,testing and commissioning of 11 KV Bush with rods for 11KV VCB Panels by way of replacement of Damaged/Burnt Out 11 KV Bush with rods of same type,make and class already installed in panel confirming to IEC 60044-1-2000 standards suitable for 11KV VCB panels of make already installed at Receiving Stations ,.(material to be provided by the department at Divisional ) |
| 19 | Supply, Installation,testing and commissioning of 11KV Vacuum Interruptor by way of Replacement of Damaged/Burnt Out 11KV Vacuum Interruptor of same composition,type,make already installed in 11kV VCB panel of for 11KV VCB panels of make already installed at Receiving Stations |
| 20 | Installation,testing and commissioning of 11KV Vacuum Interruptor by way of Replacement of Damaged/Burnt Out 11KV Vacuum Interruptor of same composition,type,make already installed in 11kV VCB panel of make already installed at Receiving Stations .(material to be provided by the department at Divisional ) |
| 21 | Supply, Installation,testing and commissioning of 33KV Vacuum Interruptor by way of Replacement of Damaged/Burnt Out 33KV Vacuum Interruptor of same composition,type,make already installed at Receiving Stations |
| 22 | Installation,testing and commissioning of 33KV Vacuum Interruptor by way of Replacement of Damaged/Burnt Out 33KV Vacuum Interruptor of same composition,type,make already installed at Receiving Stations , including its loading , transportation, unloading and carriage by manual or mechanical means etc complete job.(material to be provided by the department ) |
| 23 | Providing & fixing of clamps (A.A) confirming to IS:617 standards (for 33KV VCB,33KV L.A, 33KV Isolator) complete by way of Replacement of Damaged/Burnt Out clampsr of same composition,type,make already installed at Receiving Stations |
| 24 | fixing of with fresh clamps (A.A) confirming to IS:617 standards (for 33KV VCB,33KV L.A, 33KV Isolator) complete by way of Replacement of Damaged/Burnt Out clampsr of same composition,type,make already installed at Receiving Stations including its loading , transportation, unloading and carriage by manual or mechanical means etc complete job.(material to be provided by the department ) |
| 25 | Providing & fixing of GI Channel Iron/Angle Iron/Nuts and Bolts/Clamps etc. |
| 26 | Supply,installation,testing,commissioning of Tripping coils (36V) by way of Replacement of Damaged/Burnt Out Tripping coil of same composition, type, make already installed in 11kV VCB panel of make already installed at Receiving Stations |
| 27 | Installation,testing,commissioning of Tripping coils (36V) by way of Replacement of Damaged/Burnt Out Tripping coil of same composition, type, make already installed in 11kV VCB panel of make already installed at Receiving Stations (material to be provided by the department ) |
| 28 | Supply,installation,testing,commissioning of Closing coils (36V) by way of Replacement of Damaged/Burnt Out Closing coil of same composition, type, make already installed in 11kV VCB panel of make already installed at Receiving Stations |
| 29 | Installation,testing,commissioning of Closing coils (36V) by way of Replacement of Damaged/Burnt Out Closing coil of same composition, type, make already installed in 11kV VCB panel of make already installed at Receiving Stations , including its loading , transportation, unloading and carriage by manual or mechanical means etc complete job.(material to be lrovided by the department at Divisional Stores Karan Nagar) |
| 30 | Supply, Installation,testing and commissioning of 11KV Vacuum Interruptor Housing Assembly by way of Replacement of Damaged/Burnt Out one of same composition,type,make already installed in 11kV VCB panel of make already installed at Receiving Stations |
| 31 | Installation,testing and commissioning of 11KV Vacuum Interruptor Housing Assembly by way of Replacement of Damaged/Burnt Out one of same composition,type,make already installed in 11kV VCB panel of make already installed at Receiving Stations ,(material to be provided by the department ) |
| 32 | Providing and fixing of clamps (Bi-Metallic) confirming to IS: 1285 standards ( for 33KV P.T Clamps,C.T clamps,Transformer Clamps(Both H.V & L.V Side),Pad Clamps) |
| 33 | Fixing of clamps (Bi-Metallic) confirming to IS: 1285 standards ( for 33KV P.T Clamps,C.T clamps,Transformer Clamps(Both H.V & L.V Side),Pad Clamps),(material to be Provided by the department) |
| 34 | Providing and fixing of 33KV Post Insulators by way of replacement of damaged one confirming to IEC 61109/92-93 with latest amendments (porceline type) |
| 35 | Fixing of 33KV Post Insulators by way of replacement of damaged one confirming to IEC 61109/92-93 with latest amendments (porceline type), .(material to be provided by the department at Divisional ) |
| 36 | Providing and fixing of 33K VCB Bushes complete assembly by way of replacement of damaged one confirming to IS:2099 standard (porceline type) |
| 37 | Fixing of 33K VCB Bushes complete assembly by way of replacement of damaged one confirming to IS:2099 standard (porceline type), (material to be provided by the department at Divisional Stores Karan Nagar) |
| 38 | Providing and fixing of 33KV HV Bushes of power transformers complete assembly by way of replacement of damaged one confirming to IS:2099 standards (porceline type) |
| 39 | Fixing of 33KV HV Bushes of power transformers complete assembly by way of replacement of damaged one confirming to IS:2099 standards (porceline type), (material to be provided by the department ) |
| 40 | Providing and fixing of 11KV LV Bushes of transformers complete assembly by way of replacement of damaged one confirming to IS: 2099 standards (porceline type) |
| 41 | Providing and fixing of Rubber O Ring(Kidney washer) for 11KV/33KV Bushings |
| 42 | Fixing of 11KV LV Bushes of transformers complete assembly by way of replacement of damaged one confirming to IS: 2099 standards (porceline type), including its loading , transportation, unloading and carriage by manual or mechanical means etc complete job.(material to be lrovided by the department at Divisional Stores Karan Nagar) |
| 43 | Supply,installation,testing and commissioning of 33KV C.T(3-core) confirming to IEC:185 and IS:2705 (part-1 to 4) standards of ratio 400-200/5-5-5A/ 250-125/5-5-5A) outdoor type |
| 44 | Fixing,installation,testing and commissioning of fresh 33KV CT (3-core) of different ratio confirming to IEC:185 and IS:2705 (part-1 to 4) standards by way of replacement of damaged one (material to be provided by the department) |
| 45 | Supply, installation,testing and commissioning of 33KV P.T of (110V/√3) confirming to IS:3156 (part-I to Part-III) outdoor type |
| 46 | Fixing,installation,testing and commissioning of fresh 33KV PT (110V/√3) confirming to IEC:185 and IS:2705 (part-1 to 4) standards by way of replacement of damaged one (material to be supplied by the department) outdoor type, including its loading , transportation, unloading and carriage by manual or mechanical means etc complete job.(material to be lrovided by the department at Divisional Stores Karan Nagar) |
| 47 | Providing and fixing of 33KV isolator 800 Amps heavy duty confirming to IS:9921 / IEC-62271-102 standards with earthing blade |
| 48 | Providing and fixing of 33KV isolator 800 Amps heavy duty confirming to IS:9921 / IEC-62271-102 standards without earthing blade |
| 49 | Fixing,installation,testing and commissioning of fresh 33KV isolators 800 Amps heavy duty confirming to IS:9921 / IEC-62271-102 standards (material to be supplied by the department) |
| 50 | Providing,Installation,Testing and commissioning of 11KV G.O Set 600 Amps (with earthing blade) heavy duty conforming to latest version of IS - 9921 (part-I to V) with earthing blade by way of replacement of damaged one |
| 51 | Installation,Testing and commissioning of 11KV G.O Set 800 Amps heavy duty conforming to latest version of IS - 9921 (part-I to V) , including its loading , transportation, unloading and carriage by manual or mechanical means etc complete job.(material to be lrovided by the department at Divisional Stores Karan Nagar) |
| 52 | Providing, fixing, installation, testing and commissioning of 11KV Isolators,630amps. conforming to IS 9921/IEC-129 standards with earthing blade |
| 53 | Installation,Testing and commissioning of 11KV Isolators,630amps. conforming to IS 9921/IEC-129 standards (with earthing blade/without earthing blade ) including its loading , transportation, unloading and carriage by manual or mechanical means etc complete job.(material to be lrovided by the department at Divisional Stores Karan Nagar) |
| 54 | Providing and fixing of 33KV Drop out set with porcelaine insulator by way of replacement of damaged one as per latest IS standard with latest amendments therof. |
| 55 | Installation,Testing and commissioning of 33KV D.O. set by way of replacement of damaged one as per latest IS standard with latest amendments therof.,(material to be provided by the department ) |
| 56 | Providing, Installation,Testing and commissioning of 33KV L.A. set (porcelaine type with clamps) by way of replacement of damaged one as per latest IS standard with latest amendments therof.(set of 3 Nos) 1No/phase |
| 57 | Installation,Testing and commissioning of 33KV L.A. set by way of replacement of damaged one as per latest IS standard with latest amendments therof., including its loading , transportation, unloading and carriage by manual or mechanical means etc complete job.(material to be lrovided by the department ) |
| 58 | Oil Toping in 33/11 KV Power Transfromers and 33KV MOCB's , (material to be Provided by the department ) |
| 59 | Providing,installation, testing and commissioning of Winding Temperature meter by way of replacement of damaged one suitable for 33/11 KV, 10MVA/6.3MVA/5.0MVA/1.6MVA Power Transformers |
| 60 | Installation, testing and commissioning of Winding Temperature meter by way of replacement of damaged one suitable for 33/11 KV, 10MVA/6.3MVA/5.0MVA/1.6MVA Power Transformers (material to be Provided by the department ) |
| 61 | Providing,installation, testing and commissioning of Oil Temperature meter by way of replacement of damaged one suitable for 33/11 KV , 10MVA/6.3MVA/5.0MVA/1.6MVA Power Transformers |
| 62 | Installation, testing and commissioning of Oil Temperature meter by way of replacement of damaged one suitable for 33/11 KV , 10MVA/6.3MVA/5.0MVA/1.6MVA Power Transformers,(material to be Provided by the department ) |
| 63 | Providing and fixing of Bush Rods suitable for 33/11KV Power Transformer (10MVA/6.3MA/5.0MVA/1.6MVA) by way of replacement of damaged one 33KV side |
| 64 | Fixing of Bush Rods suitable for 33/11KV Power Transformer (10MVA/6.3MA/5.0MVA/1.6MVA) by way of replacement of damaged one 33KV side,(material to be Provided by the department ) |
| 65 | Providing and fixing of Bush Rods suitable for 33/11KV Power Transformer (10MVA/6.3MA/5.0MVA/1.6MVA) by way of replacement of damaged one 11KV side |
| 66 | Fixing of Bush Rods suitable for 33/11KV Power Transformer (10MVA/6.3MA/5.0MVA/1.6MVA) by way of replacement of damaged one 11KV side,(material to be Provided by the department ) |
| 67 | Supply ,installation,testing and commissioning of 30V,100 AH Maintenance free Battery Bank ( comprising of 15 number batteries of 2volt each) complete with rack ,connectors etc conforming to IEC60896-21/22 standards of Exide/HBL/Luminous/AMAR Raja or equivalent make |
| 68 | Installation,testing and commissioning of 30V,100 AH Maintenance free Battery Bank ( comprising of 15 number batteries of 2volt each) complete with rack ,connectors etc conforming to IEC60896-21/22 standards of Exide/HBL/Luminous/AMAR Raja or equivalent make,(material to be Provided by the department ) |
| 69 | Supply,installation,testing and commissioning of automatic 36V,DC,15amp. (constant current constant voltage ) fully automatic battery charger float cum boost type 2KVA |
| 70 | Installation,testing and commissioning of automatic 36V,DC,15amp. (constant current constant voltage ) fully automatic battery charger float cum boost type 2KVA |
| 71 | Supply,laying,Testing,commissioning of 11KV grade armoured ,Xlpe FRLS Power Cable (with stranded compact circular aluminium with extruded semi conducting compound,Xlpe insulated and overall PVC sheathed cable confirming to IS:7089 (Part-II)-1985 with the latest amendments by way of replacing the damaged cable (including its transportation to divisional Stores) of 11KV switchgear (havells or Glastor or finolex or KEI make) of size |
| 72 | 400mm^² 3-core |
| 73 | 300mm^² 3-core, |
| 74 | 240mm^² 3-core |
| 75 | 185mm^² 3-core, |
| 76 | 150mm^² 3-core |
| 77 | 120mm^² 3-core |
| 78 | Laying,Testing,commissioning of 11KV (E) grade armoured ,Xlpe FRLSH Power Cable (with stranded compact circular aluminium with extruded semi conducting compound,Xlpe insulated and overall PVC sheathed cable confirming to IS:7089 (Part-II)-1985 with the latest amendments by way of replacing the damaged cable (including its transportation to divisional Stores) of 11KV switchgear (havells or Glastor or finolex make) of size,(material to be Provided by the department ) |
| 79 | 400mm^² 3-core |
| 80 | 300mm^² 3-core, |
| 81 | 240mm^² 3-core |
| 82 | 185mm^² 3-core, |
| 83 | 150mm^² 3-core |
| 84 | 120mm^² 3-core |
| 85 | Supply,laying,Testing,commissioning of 11KV grade armoured ,Xlpe FRLS Power Cable (with stranded compact circular aluminium with extruded semi conducting compound,Xlpe insulated and overall PVC sheathed cable confirming to IS:7089 (Part-II)-1985 with the latest amendments by way of replacing the damaged cable (including its transportation to divisional Stores) of 11KV switchgear (havells or Glastor or finolex or KEI make) |
| 86 | 6300mm^² 1-core |
| 87 | 400mm^² 1-core |
| 88 | 300mm^² 1-core, |
| 89 | 240mm^² 1-core |
| 90 | 185mm^² 1-core, |
| 91 | 150mm^² 1-core |
| 92 | 120mm^² 1-core |
| 93 | laying,Testing,commissioning of 11KV (E) grade armoured ,Xlpe FRLS Power Cable (with stranded compact circular aluminium with extruded semi conducting compound,Xlpe insulated and overall PVC sheathed cable confirming to IS:7089 (Part-II)-1985 with the latest amendments by way of replacing the damaged cable (including its transportation to divisional Stores) of 11KV switchgear (havells or Glastor or finolex make),(material to be Provided by the department ) |
| 94 | 630mm^² 1-core |
| 95 | 400mm^² 1-core |
| 96 | 300mm^² 1-core, |
| 97 | 240mm^² 1-core |
| 98 | 185mm^² 1-core, |
| 99 | 150mm^² 1-core |
| 100 | 120mm^² 1-core |
| 101 | Supply,laying,Testing,commissioning of 2.5 mm² Control cable copper Armoured , 1.1 kV Grade, ISI, FRLSH conforming to IS:1554(Part 1),IS 8130,IS ;5831 (Havells or Gloster or finolex make ) |
| 102 | 2Core |
| 103 | 4Core |
| 104 | 6Core |
| 105 | 12Core |
| 106 | Laying,Testing,commissioning of 2.5 mm² Control cable copper Armoured , 1.1 kV Grade, ISI, FRLSH conforming to IS:1554(Part 1),IS 8130,IS ;5831 (Havells or Gloster or finolex make ),(material to be Provided by the department ) |
| 107 | 2Core |
| 108 | 4Core |
| 109 | 6Core |
| 110 | 12Core |
| 111 | Supply,installation,testing,commissioning of 11KV ,3 core heat shrinkable straight through jointing cable kit(outdoor Type) suitable for already installed 11KV Xlpe Power Cable confirming to IS:13573/1993 with latest ammendments if any (3M or RAYCHEM make) by way of replacing damaged staight through jointing kit including its transportation to divisional stores. |
| 112 | 400mm^² 3-core |
| 113 | 300mm^² 3-core, |
| 114 | 240mm^² 3-core |
| 115 | 185mm^² 3-core, |
| 116 | 150mm^² 3-core |
| 117 | 120mm^² 3-core |
| 118 | Installation,testing,commissioning of 11KV ,3 core heat shrinkable straight through jointing cable kit(outdoor Type) suitable for already installed 11KV Xlpe Power Cable confirming to IS:13573/1993 with latest ammendments if any (3M or RAYCHEM make) by way of replacing damaged staight through jointing kit (material to be provided by department |
| 119 | 400mm^² 3-core |
| 120 | 300mm^² 3-core, |
| 121 | 240mm^² 3-core |
| 122 | 185mm^² 3-core, |
| 123 | 150mm^² 3-core |
| 124 | 120mm^² 3-core |
| 125 | Supply, Installation,Testing and commissioning of 11KV cable termination kits (Indoor/ outdoor Type) 3M or Vikchem or Raychem suitable for Xlpe Power Cable by way of replacing damaged Cable kit |
| 126 | 400mm^² 3-core |
| 127 | 300mm^² 3-core, |
| 128 | 240mm^² 3-core |
| 129 | 185mm^² 3-core, |
| 130 | 150mm^² 3-core |
| 131 | 120mm^² 3-core |
| 132 | Installation,Testing and commissioning of 11KV cable termination kits (Indoor/ outdoor Type) 3M or Vikchem or Raychem suitable for Xlpe Power Cable by way of replacing damaged Cable kit (material to be provided by department |
| 133 | 400mm^² 3-core |
| 134 | 300mm^² 3-core, |
| 135 | 240mm^² 3-core |
| 136 | 185mm^² 3-core, |
| 137 | 150mm^² 3-core |
| 138 | 120mm^² 3-core |
| 139 | Supply,installation,testing,commissioning of 11KV , 1core heat shrinkable straight through jointing cable kit(outdoor Type) suitable for already installed 11KV Xlpe Power Cable confirming to IS:13573/1993 with latest ammendments if any (3M or Vikchem or Raychem make) by way of replacing damaged staight through jointing kit |
| 140 | 630mm^² 1-core |
| 141 | 400mm^² 1-core |
| 142 | 300mm^² 1-core, |
| 143 | 240mm^² 1-core |
| 144 | 185mm^² 1-core, |
| 145 | 150mm^² 1-core |
| 146 | 120mm^² 1-core |
| 147 | Installation,testing,commissioning of 11KV , 1core heat shrinkable straight through jointing cable kit(outdoor Type) suitable for already installed 11KV Xlpe Power Cable confirming to IS:13573/1993 with latest ammendments if any (3M or Vikchem or Raychem make) by way of replacing damaged staight through jointing kit (material to be provided by department) |
| 148 | 630mm^² 1-core |
| 149 | 400mm^² 1-core |
| 150 | 300mm^² 1-core, |
| 151 | 240mm^² 1-core |
| 152 | 185mm^² 1-core, |
| 153 | 150mm^² 1-core |
| 154 | 120mm^² 1-core |
| 155 | Supply, Installation,Testing and commissioning of 11KV cable termination kits (Indoor/ outdoor Type) 3M or Vikchem or Raychem suitable for Xlpe Power Cable by way of replacing damaged cable termination kits |
| 156 | 630mm^² 1-core |
| 157 | 400mm^² 1-core |
| 158 | 300mm^² 1-core, |
| 159 | 240mm^² 1-core |
| 160 | 185mm^² 1-core, |
| 161 | 150mm^² 1-core |
| 162 | 120mm^² 1-core |
| 163 | Installation,Testing and commissioning of 11KV cable termination kits (Indoor/ outdoor Type) 3M or Vikchem or Raychem suitable for Xlpe Power Cable by way of replacing damaged cable termination kits (material to be provided by department) |
| 164 | 630mm^² 1-core |
| 165 | 400mm^² 1-core |
| 166 | 300mm^² 1-core, |
| 167 | 240mm^² 1-core |
| 168 | 185mm^² 1-core, |
| 169 | 150mm^² 1-core |
| 170 | 120mm^² 1-core |
| 171 | Disconnecting of Power Transformer from Circuit including dismantling of its accessories complete job (Including shifting of power cables/control cables as and when required as per site requirement and then relaying of same back to its original postion). |
| 172 | 10.0MVA |
| 173 | 6.3MVA |
| 174 | 5.0 MVA |
| 175 | 1.6 MVA |
| 176 | Loading of Power Transformer to the sub station bed / platform i/c manual dragging, rotation etc (if any required) (Complete Job) |
| 177 | 10 MVA |
| 178 | 6.3MVA |
| 179 | 1.6MVA |
| 180 | Lifting of 100/63KVA auxillary Transformer from Transformer bed and loading it on platform truck/crane (including opening of HT/LT connections) complete job (the job includes manual dragging/rotation if required) |
| 181 | Unloading of Power Transformer from the platform truck to receiving station bed i/c manual dragging, rotation etc (if any required) (Complete Job) |
| 182 | 10 MVA |
| 183 | 6.3MVA |
| 184 | 1.6MVA |
| 185 | Carriage of Power Transformer upto 5km (5Kms) |
| 186 | 10 MVA |
| 187 | 6.3MVA |
| 188 | 1.6MVA |
| 189 | 100/63KVA |
| 190 | Carriage of Power Transformer beyond 5km upto 10km |
| 191 | 10 MVA |
| 192 | 6.3MVA |
| 193 | 1.6MVA |
| 194 | 100/63KVA |
| 195 | Carriage of Power Transformer beyond 10km upto 20km |
| 196 | 10 MVA |
| 197 | 6.3MVA |
| 198 | 1.6MVA |
| 199 | 100/63KVA |
| 200 | Carriage of Power Transformer beyond 20km |
| 201 | 10 MVA |
| 202 | 6.3MVA |
| 203 | 1.6MVA |
| 204 | 100/63KVA |
| 205 | Installation, testing & commissioning of Power Transformer ( including assembly viz fixing of bushes, radiators, fans (if any), thermometer, wiring of instruments etc. ) Complete Job (Including shifting of power cables/control cables as and when required as per site requirement and then relaying of same back to its original postion) |
| 206 | 10 MVA |
| 207 | 6.3MVA |
| 208 | 1.6MVA |
| 209 | Unloading of 100/63 KVA auxillary Transformer from platform truck/crane to Transformer bed including Installation, testing & commissioning of 100/63 KVA Auxillary Transformer, fixing of HT/LT connections, the job includes manual dragging/rotation (if required)( Complete job) |
| 210 | Repairing of Re-Setting Links of 11 KV VCB Panel |
| 211 | Repairing of operating shaft of 11 KV VCB Panel |
| 212 | Repairing of Shower Contact of 11 KV VCB Panel |
| 213 | Repairing of Isolating Sockets of 11 KV VCB Panel |
| 214 | Repairing of High Tension Spring of 11 KV VCB Panel |
| 215 | Repairing of Tripping Shaft of 11 KV VCB Panel |
| 216 | Repairing of Rollers of 11 KV VCB Panel |
| 217 | Repairing of Latch Assembly of 11 KV VCB Panel |
| 218 | Repairing of Gear Assembly of 11 KV VCB Panel |
| 219 | Repairing of Tripping Mechanism of 11 KV VCB Panel |
| 220 | Repairing of Spring Charge Motor Assembly of 11 KV VCB Panel |
| 221 | Supply, Installation,Testing and commissioning of Re-Setting Links of 11 KV VCB Panel |
| 222 | Supply, Installation,Testing and commissioning of operating shaft of 11 KV VCB Panel |
| 223 | Supply, Installation,Testing and commissioning of Shower Contact of 11 KV VCB Panel by a fresh One |
| 224 | Supply, Installation,Testing and commissioning of Isolating Sockets of 11 KV VCB Panel |
| 225 | Supply, Installation,Testing and commissioning of High Tension Spring of 11 KV VCB Panel |
| 226 | Supply, Installation,Testing and commissioning of Tripping Shaft of 11 KV VCB Panel |
| 227 | Supply, Installation,Testing and commissioning of Rollers of 11 KV VCB Panel |
| 228 | Replacement of Latch Assembly of 11 KV VCB Panel |
| 229 | Supply, Installation,Testing and commissioning of Gear Assembly of 11 KV VCB Panel |
| 230 | Replacement of Tripping Mechanism of 11 KV VCB Panel |
| 231 | Supply, Installation,Testing and commissioning of Spring Charge Motor of 11 KV VCB Panel |
| 232 | Supply, Installation,Testing and commissioning of Triping Mechanism Complete suitable for of 11 KV VCB Panel of make already installed at Receiving Station |
| 233 | Supply, Installation, Testing and Commissioning of 11 KV Panel equipments/items by way of replacement of damaged one- |
| 234 | Voltmeter 11KV/110V |
| 235 | Ammeter |
| 236 | Selector Switch- 16Amps |
| 237 | LED panel Indicators |
| 238 | Push Button |
| 239 | HRC fuse with Base -16 Amps |
| 240 | Installation, Testing and Commissioning of 11 KV Panel equipments/items by way of replacement of damaged one- Voltmeter 11KV/110V (Material to be supplied by department) |
| 241 | Voltmeter 11KV/110V |
| 242 | Ammeter |
| 243 | Selector Switch- 16Amps |
| 244 | LED panel Indicators |
| 245 | Push Button |
| 246 | HRC fuse with Base -16 Amps |
| 247 | Providing and Panel Control re-wiring with 2.5 sqmm flexible wire, connecting ribs, bunching wire, ferruling, thimbling etc |
| 248 | Panel Control re-wiring with 2.5 sqmm flexible wire, connecting ribs, bunching wire, ferruling, thimbling etc ( (Material to be supplied by department) |
| 249 | Supply,installation,testing and commissioning of Auxilary Relay -30 A by way of Replacement of Damaged/Burnt of type,make and class already installed in panel. |
| 250 | Installation,testing and commissioning of Auxilary Relay -30 A by way of Replacement of Damaged/Burnt of type,make and class already installed in panel. |
| 251 | Supply,installation,testing and commissioning of Auxilary Switch by way of Replacement of Damaged/Burnt of type,make and class already installed in panel. |
| 252 | Installation,testing and commissioning of Auxilary Switch by way of Replacement of Damaged/Burnt of type,make and class already installed in panel. |
| 253 | Supply,installation,testing and commissioning of TNC Switch by way of Replacement of Damaged/Burnt of type,make and class already installed in panel. |
| 254 | Installation,testing and commissioning of TNC Switch by way of Replacement of Damaged/Burnt of type,make and class already installed in panel. |
| 255 | Supply,installation,testing and commissioning of Trip Circuit Supervision Relay by way of Replacement of Damaged/Burnt of type,make and class already installed in panel. |
| 256 | Installation,testing and commissioning of Trip Circuit Supervision Relay by way of Replacement of Damaged/Burnt of type,make and class already installed in panel. |
| 257 | Supply,installation,testing and commissioning of Numerical/Digital Relay by way of Replacement of Damaged/Burnt of same ratio(A.C &D.C),type,make and class already installed in panel.All relays shall conform to the requirements of IS:3231/IEC-60255 and IEC-61850 of (MIT113 ER / Ashida 141A) Operating Voltage 30-36Volts |
| 258 | installation,testing and commissioning of Numerical/Digital Relay by way of Replacement of Damaged/Burnt of same ratio(A.C &D.C),type,make and class already installed in panel.All relays shall conform to the requirements of IS:3231/IEC-60255 and IEC-61850 of (MIT113 ER / Ashida 141A) Operating Voltage 30-36Volts |
| 259 | Supply,Installation,Testing and Commissioning of Scada Compatible Digital Relay by way of Replacement of Damaged/Burnt of same ratio(A.C &D.C) already installed in panel (REF615 & RET620 ABB Make). All relays shall conform to the requirements of IS:3231/IEC-60255 and IEC-61850 of (MIT113 ER / Ashida 141A) Operating Voltage 30-36Volts |
| 260 | Fixing , testing and commissioning of Numerical/Digital Relay (MIT113 / Ashida 141A)/ SCADA Compatible Relay by way of Replacement of Damaged/Burnt of same ratio(A.C &D.C),type,make and class already installed in 11KV VCB panel.(material to be provieded by the department) |
| 261 | Supply,installation,testing and commissioning of master trip relay 24-50 V by way of Replacement of Damaged/Burnt of ,type,make and class already installed in 11KV VCB panel |
| 262 | Installation,testing and commissioning of master trip relay 24-50 V by way of Replacement of Damaged/Burnt of same type,make and class already installed in 11KV VCB panel |
| 263 | On load Filtration of Power Transformer Oil at site. |
| 264 | Providing and fixing of silica gel by way of replacement of old/moisttirized one |
| 265 | Providing and laying of HDPE Pipe Outer Dia 180 mm Inner Dia 152 mm for laying of 11kV XLPE Cable from Power Transformer to Control Room PE63/80/100 PN 3.0-20 |
| 266 | Providing and laying of Earthing Mat (GI Flat 50 mm x8 mm) |
| 267 | Providing and fixing of Earthing Electrode ( 3m long 40mm dia GI pipe) through GI Strip 50x6mm) |
| 268 | Providing and laying of Cement Concreting 1:2:4 usinmg 20mm stone aggregate of nominal size |
| 269 | Clearing jungle including uprooting of rank vegetation, grass, brush wood, trees andsaplings of girth upto 30 cm measured at a height of 1 m above ground level andremoval of rubbish upto a distance of 50 m outside the periphery of the area cleared |
| 270 | Pumping out water caused by springs, tidal or river seepage, broken water mains ordrains and the like. |
| 271 | Providing and Replacing of Electrical Fittings with accessaries of Receiving Station buildings ( lighting pts., fan pts. etc) |
| 272 | Providing and Replacing of Electrical Fittings with accessaries of Receiving Station buildings (heating pts.,etc) |
| 273 | Providing and Replacing of broken window panes 3.5 mm of Receiving Station buildings including fixing of battain comleting the job in all respects |
| 274 | Refilling of fire extinguishers including repair & maintenance of various components in all respects (ABC Dry type) including lifting , carraiage and re-installation at the site. |
| 275 | Refilling of fire extinguishers including repair & maintenance of various components in all respects (CO2) including lifting , carraiage and re-installation at the site. |
| 276 | SITC of Fire Extingiusher Co₂ Type of 4.5 kg capacity for control room |
| 277 | SITC of Fire Extingiusher Co₂ Type of 22.5 kg capacity (Trolley Type) |
| 278 | Providing and fixing of Station M.S Iron chequered Trench covers 6mm/8mm/10mm Please Enable Macros to View BoQ information |
| SR No | FileName | File Description |
| 1 | Click here to download tender document | Tender Documents |
| 2 | Click here to download tender document | Tender Documents |
| 3 | Click here to download tender document | Tender Documents |
| 4 | Click here to download tender document | Tender Documents |