| 1 | Excavation in trenches not exceeding 1.5m wide and not exceeding 1.5 m in depth for laying of pipe etc and getting out in hard soil, complete all as specified and/or as directed by Engr-in-Charge. |
| 2 | M&L for Sand cushioning to underground cables 8 cm below the cable before laying & 15 cm above the cable after laying, complete all as specified in clause 19.75 of SSR Part-I, complete all as specified and/or as directed by Engr-in-Charge. |
| 3 | Supply and lay of factory made, machine pressed, unreinforced, pre-cast concrete cable cover class LV type-1 flat size 250mm x 150mm x 40mm, complete all as specified and directed |
| 4 | Labour only for laying of old serviceable cable covers retrieved from excavation complete all as specified and directed by Engineer-in-Charge. |
| 5 | M & L for returning, filling in including spreading leveling watering and well ramming in layers not exc. 25 cm thick complete all as specified and directed.(Surplus soil if any shall not be removed but left over the trench) |
| 6 | M & L for removing surplus soil to a distance not exc. 50 M and depositing where directed at a level not exceeding 1.5 Mtr above the starting point complete all as specified and/or as directed by Engr-in-Charge. |
| 7 | Supply, laying and testing in replacement of XLPE insulated, armoured, haeavy duty electric cables (heavy duty) with stranded aluminium conductor rating 1100 volts grade of size 50 Sqmm 3.5 core laid in trences or passing through pipes ducts or fixed to walls/poles complete all as specified and/or as directed by Engineer-in-Charge. |
| 8 | Supply, laying and testing in replacement of XLPE insulated, armoured, heavy duty electric cables (heavy duty) with stranded aluminium conductor rating 1100 volts grade of size 10 Sqmm 4.0 core laid in trences or passing through pipes ducts or fixed to walls/poles completer all as specified. |
| 9 | Material and labour for fixing GI trunk of size 100mm x 40mm on wall for the purpose holding LT XLPE cable of size upto 25 Sqmm 4.0 core including suitable no of hold fasterns to fix trunk on wall complete all as specified and/or as directed by Engineer-in-Charge. |
| 10 | M & L spray for painting and numbering of electric poles with two coats of aluminium duco paint after cleaning and preparing the surface of poles of any size complete all as specified and/or as directed by Engineer-in-Charge. |
| 11 | Supply and fixing LED street light fitting 70 Watt 230 V AC outdoor type with high pressure die cast aluminum hosing and heat resistant complete with driver, lamp bracket with impact and corrosion resistant including thermal management in multiple optics complete with IP 65/66 protection complete all as specified and/or as directed by Engineer-in-Charge. |
| 12 | Supply and fix in replacement PVC insulated round flexible copper conductor 2.5 sqmm 2.0 core copper conductor 1100 volts including conduit ofo size 20mm dia and securingn with pole complete all as specified and/or as directed by Engineerr-in-Charge. |
| 13 | Taking down old unserviceable bollard of any type and supply and fix LED bollard 10 watt Warm white of 1.0 meter height operated on 230 Volts AC complete all as specified and/or as directed by Engineer-in-Charge. |
| 14 | Taking down old unserviceable feeder pillar box and supply and fix in replacement feeder pillar box 415V, with 4 Nos aluminium bus bar complete all as specified and/or as directed by Engineer-in-Charge. |
| 15 | Taking down old unsereviceable looping box and supply and fix FR/PVC pole junction box for loop out of size 200 x 180 mm including one SP MCB 10 Amps and necessary fixing arrangement complete all as specified and directed. |
| 16 | Taking dowon old unserviceable street light timer and supply and fix street timer set three phase 25KW workingn based on astronomical timer along with contractor, MCCB, ON/OFF switch, Manual/automatic selector switch in enclosure and mounting bracket, nut bolts, washer complete all as specified and/or as directed by Engineer-in-Charge. |
| 17 | Supply & fix, install testing and commissioning of LT panel board (indoor type) cubical shape, 3 phase, 4 wire, copper bus bar rating 400 Amps for phases and 200 Amps for neutral made out of CRCA sheet , 3.15 mm thick ,factory fabricated , CPRI approved , powder coated ,dust and vermin proof , provn for ventilation , angle iron frame and four legs of 50x50x6mm thick angle iron ,4 ft long grouted on PCC foundation of height not less than 30 cm from the ground level , grouting properly ,and of suitable size to accomodate the items mentioned below all as specified and comprising of following including necessary cable connections to the MCCBs ,Voltmeter,Ammeter and cable lugs etc . (i) 4 Pole MCCB 320 Amp, 50 Hz, 415 V with rupturing capacity 35 KA -01 No (Incomer)(ii) 3 Pole MCCB 100 Amp, 50 Hz, 415 V with rupturing capacity 35 KA -04 Nos (outgoing). (iii) MCB SPN 63 Amps -01 No. (iv) Voltmeter,digital type 0- 400 Volt,with selector switch -01 set (v) Ammeter Digital type 0-100Amps, with selector switch and CT'-1set (vi) Phase indicating lamps LED type ( red , yellow, blue) -01 sets |
| 18 | Deduct Schedule of Credit of Rs (-) 65193.00 (Minus) as listed in Schedule 'A' (Contd). Contract Sum shall be arrived after deducting the credit amount.Note :- Tenderers will not quote against this item being a firm amount. Please Enable Macros to View BoQ information |