| 1 | M&L for Excavation in trenches, n exc 1.5 m wide and n exc 1.5 m in depth; for foundation etc. or for laying UG cable in trenches in soft soil and getting out all as specified and/or as directed by Engineer-in-Charge. |
| 2 | M&L for Excavation in trenches, n exc 1.5 m wide and exc 1.5 m in depth but n exc 3.0m in depth; for foundation etc. or for laying UG cable in trenches in soft soil and getting out all as specified and/or as directed by Engineer-in-Charge. |
| 3 | M&L for Returning, filling in (soil), including spreading, leveling, watering and well ramming in layers not exc. 25m, complete all as specified and/or as directed by Engineer-in-Charge. |
| 4 | M&L for Removing excavated material to a distance not exc. 50m and depositing where directed at a level not exc. 1.5m above the strating point, complete all as specified and/or as directed by Engineer-in-Charge. |
| 5 | M&L for Sand cushioning to underground cables 8 cm below the cable before laying & 15 cm above the cable after laying, complete all as specified in clause 19.75 of SSR Par-I, complete all as specified and/or as directed by Engineer-in-Charge. |
| 6 | Supply and laying of factory made, machine pressed, unreinforced, pre-cast concrete cable cover class LV type-1 flate size 250mm x 150mm x 40mm, complete all as specified and/or as directed by Engineer-in-Charge. |
| 7 | Labour only for laying of old serviceable cable covers retrieved from excavation complete all as specified and directed by Engineer-in-Charge. |
| 8 | M&L PCC 1:4:8 type D2 using 40 mm graded stone aggregate as in foundation, filling mass concrete including necessary form work complete all as specified and/or as directed by Engineer-in-Charge. |
| 9 | M&L for PCC 1:3:6 type C 1 using 20 mm graded aggregate block masonry with solid block ,exc 10 cm in width and setting in mortar complete for coping of pole including necessary from work and fair finish to the exposed surface area without using extra cement complete all as specified and/or as directed by Engineer-in-Charge. |
| 10 | Material and labour fpr cement concrete in foundation, filling and mass concrete type B2 1:2:4 with using 40mm aggregate complete all as specified and/or as directed by Engineer-in-Charge. |
| 11 | Supply, testing and laying in replacement of XLPE insulated, armoured, haeavy duty electric cables (heavy duty) with stranded aluminium conductor rating 1100 volts grade of size 240 Sqmm 3.5 core laid in trences or passing through pipes.ducts or fixed to walls/poles complete all as specified and/or as directed by Engineer-in-Charge. Note :- Excavation and earth work shall be mearured and paid under respective items. |
| 12 | Supply, testing and laying in replacement of XLPE insulated, armoured, haeavy duty electric cables (heavy duty) with stranded aluminium conductor rating 1100 volts grade of size 120 Sqmm 3.5 core laid in trences or passing through pipes.ducts or fixed to walls/poles complete all as specified and/or as directed by Engineer-in-Charge. Note :- Excavation and earth work shall be mearured and paid under respective items. |
| 13 | Supply, testing and laying in replacement of XLPE insulated, armoured, haeavy duty electric cables (heavy duty) with stranded aluminium conductor rating 1100 volts grade of size 70 Sqmm 3.5 core laid in trences or passing through pipes.ducts or fixed to walls/poles complete all as specified and/or as directed by Engineer-in-Charge. Note :- Excavation and earth work shall be mearured and paid under respective items. |
| 14 | Supply, testing and laying in replacement of XLPE insulated, armoured, haeavy duty electric cables (heavy duty) with stranded aluminium conductor rating 1100 volts grade of size 50 Sqmm 3.5 core laid in trences or passing through pipes.ducts or fixed to walls/poles complete all as specified and/or as directed by Engineer-in-Charge.Note :- Excavation and earth work shall be mearured and paid under respective items. |
| 15 | Supply, testing and laying in replacement of XLPE insulated, armoured, haeavy duty electric cables (heavy duty) with stranded aluminium conductor rating 1100 volts grade of size 35 Sqmm 3.5 core laid in trences or passing through pipes.ducts or fixed to walls/poles complete all as specified and/or as directed by Engineer-in-Charge.Note :- Excavation and earth work shall be mearured and paid under respective items. |
| 16 | Supply, testing and laying in replacement of XLPE insulated, armoured, haeavy duty electric cables (heavy duty) with stranded aluminium conductor rating 1100 volts grade of size 25 Sqmm 2.0 core laid in trences or passing through pipes.ducts or fixed to walls/poles complete all as specified and/or as directed by Engineer-in-Charge.Note :- Excavation and earth work shall be mearured and paid under respective items. |
| 17 | Supply, testing and laying in replacement of XLPE insulated, armoured, haeavy duty electric cables (heavy duty) with stranded aluminium conductor rating 1100 volts grade of size 16 Sqmm 2.0 core laid in trences or passing through pipes.ducts or fixed to walls/poles complete all as specified and/or as directed by Engineer-in-Charge.Note :- Excavation and earth work shall be mearured and paid under respective items. |
| 18 | Supply, testing and laying in replacement of XLPE insulated, armoured, haeavy duty electric cables (heavy duty) with stranded aluminium conductor rating 1100 volts grade of size 10 Sqmm 2.0 core laid in trences or passing through pipes.ducts or fixed to walls/poles complete all as specified and/or as directed by Engineer-in-Charge.Note :- Excavation and earth work shall be mearured and paid under respective items. |
| 19 | Taking down old unserviceable feeder pillar box and supply and fix in replacement feeder pillar box of suitable size with incommer MCCB of cpacity 160 Amps, 415V , with 4 Nos aluminium bus bar strip along with 14 Nos MCB SPN 63 Amps, 240 Volts, C type with Din rail for moounting and necessary wiring for MCB,s complete all as specified and/or as directed by Engineer-in-Charge. |
| 20 | Taking down old unserviceable feeder pillar box and supply and fix in replacement feeder pillar box of suitable size with incommer MCCB of cpacity 125 Amps, 415V , with 4 Nos aluminium bus bar strip along with 14 Nos MCB SPN 63 Amps, 240 Volts, C type with Din rail for moounting and necessary wiring for MCB,s complete all as specified and/or as directed by Engineer-in-Charge. |
| 21 | Taking down old unserviceable feeder pillar box and supply and fix in replacement feeder pillar box of suitable size with incommer MCCB of cpacity 100 Amps, 415V , with 4 Nos aluminium bus bar strip along with 14 Nos MCB SPN 63 Amps, 240 Volts, C type with Din rail for moounting and necessary wiring for MCB,s complete all as specified and/or as directed by Engineer-in-Charge. |
| 22 | Supply & fixing in replacement of tubes light grade of size 80 mm bore galvanised with all fittings and fixed complete to walls and ceiling or laid in floors complete all as specified and/or as directed by Engineer-in-Charge. |
| 23 | Supply & fixing in replacement of tubes light grade of size 50 mm bore galvanised with all fittings and fixed complete to walls and ceiling or laid in floors complete all as specified and/or as directed by Engineer-in-Charge. |
| 24 | Supply and fixing in replacement of Earthing complete with galvanised steel earth plate electrode 60cmx60cmx6mm thick burried directly in groud to a depth not lss than 2.25 mtrs deep below normal ground level with top edge of earth plate not less than 1,5 ntrs below normal ground level connected to galvanised iron strip 32 x 6mm as earthing leads by means of galvanised bolts, nuts, check nuts and washer of galvanised iron or steel complete with 20 mm dia GI Pipe light grade for watering and 40mm dia GI light grade pipe for protection of strip upto test point including test point of strip 50x50x3mm GI, charcoal dust, common salt 15cm all around the earth plate all as shown inelectric plate No.5 of MES SSR Part-I all as specifed or indicated and testing on competion including necessary excavation, earth work PCC pit and with RCC cover of suitable size water funnel with wire mesh complete all as specified and/or as directed by Engineer-in-Charge. |
| 25 | Supply & Installation ,testing and Commissioning in replacement of LT Panel cubical type out door floor mounted weather proof totally enclosed, (CPRI approved) factory made and made out of 3 mm thick CRCA powder coated sheet and angle iron complete with bus bar of copper of suitable size for capacity 600 Amps 3 Phase and Neutral 415 Volts 50 Hz mounted on epoxy type insulators with PCC flooring and angle iron base frame complete all as directed by the Engr-in-charge including fallowing accessories:- a) MCCB 400 Amps Cap 4 Pole 36 KA 415 -1 No for( I/C) b) Change over switch open execution type 400 Amp 4 pole - 01 No c) MCCB 200 Amp cap 3 pole 25 KA 415 Volts - 1 Nos d) MCCB 100 Amp cap 3 pole 16 KA 415 Volts - 3 Nos e) Digital Volt meter with sellector switch(0-500V) - 02 Set f) Digital Amp meter with sellector switch with necessary CT (0-500A) - 02 Set g) LED indicating lamp - 02 Set Note : (i) The Make of Change over and MCCB considered are Havells/Standard/Indo Asian/HPL (ii) The rates deemed to be inclusive of suitable size copper wirinng/copper strips from Main I/C MCCBs to Channge over switch, Change over switch to Main Bus bar and Bus Bar to Outgoing MCCBs complete all as specified and directed. (iii) The design of Panel, Make of complete accessories and drawing of the LT Panel should be submitted by the contractor for pre-approval from the Engineer-in-cfharge before order and execution at site. |
| 26 | Supply & Installation ,testing and Commissioning in replacement of LT Panel cubical type out door floor mounted weather proof totally enclosed, (CPRI approved) factory made and made out of 3 mm thick CRCA powder coated sheet and angle iron complete with bus bar of copper of suitable size for capacity 480 Amps 3 Phase and Neutral 415 Volts 50 Hz mounted on epoxy type insulators with PCC flooring and angle iron base frame complete all as directed by the Engr-in-charge including fallowing accessories:- a) MCCB 320 Amps Cap 4 Pole 36 KA 415 -1 No for( I/C) b) Change over switch open execution type 320 Amp 4 pole - 01 No c) MCCB 160 Amp cap 3 pole 25 KA 415 Volts - 1 Nos d) MCCB 100 Amp cap 3 pole 16 KA 415 Volts - 3 Nos e) Digital Volt meter with sellector switch(0-500V) - 02 Set f) Digital Amp meter with sellector switch with necessary CT (0-500A) - 02 Set g) LED indicating lamp - 02 Set Note : (i) The Make of Change over and MCCB considered are Havells/Standard/Indo Asian/HPL (ii) The rates deemed to be inclusive of suitable size copper wirinng/copper strips from Main I/C MCCBs to Channge over switch, Change over switch to Main Bus bar and Bus Bar to Outgoing MCCBs complete all as specified and directed. (iii) The design of Panel, Make of complete accessories and drawing of the LT Panel should be submitted by the contractor for pre-approval from the Engineer-in-cfharge before order and execution at site. |
| 27 | Taking down old unserviceable street light fitting and supply and fix inrepalcment street light fitiing 35 watt 230 Volt AC outdoor type with hiugh pressure die cast aluminium hiusing and heat resistant complte with driver,lamp cracket with impact and corosion resistant including thermal management in multiple optics complete with IP65/66 protection complete all as specified and/or as directed by Engineer-in-Charge. |
| 28 | Supply and fixing LED flood light fitting 120 watt 230V AC outdoor type with thermal management in multipale optics and equipped with IP 66 protection with impact and corrosion resistant including with driver and lamp complete all as specified and/or as directed by Engineer-in-Charge. |
| 29 | Dismantling old unsv and supply and fixing of cross arms braciing support clamps, back plates fabricated from steel section made out of Fe-0-310/Fe-0-410 including nuts, bolts and washers welding, drilling hole complete with two coats of aluminium paint over one coat of primer complete all as specified and/or as directed by Engineer-in-Charge. |
| 30 | M&L for fixing in replacement of ACSR conductor any size drawn straight horizontal on over head lines on existing poles including binding with insulators. Weight of conductor shall be measured straight horizontal distance between centre of two adjacent poles and calculating weight of conductor of size and length by adding 3% extra for sag ,jointing jumpers,etc. complete all as specified and/or as directed by Engineer-in-Charge. |
| 31 | M&L for fixing in replacement of pin insulator porcelain white, brown or green 100 mm height, 65 mm dia for 1100 volts grade complete all as specified and/or as directed by Engineer-in-Charge. |
| 32 | M&L for fixing in replacement of galvanized steel wire 4mm dia for continuous earth wire complete all as specified and/or as directed by Engineer-in-Charge. |
| 33 | S&F PVC Spacer 2/4 way for LT over head line 1100 V complete all as specified and/or as directed by Engineer-in-Charge. |
| 34 | M&L for fixing in replacement of stay assembly complete with stay plate bow, stay rod of dia 16mm and gavanised iron stay wire stranded of size 7/4mm and accessories as shown in electric plate No 1 of SSR part-I (loop type insulator, stay clamps, excavation and concrete shall be measured separately) complete all as specified and/or as directed by Engineer-in-Charge. |
| 35 | Dismantling old unsv poles and supply and fixing in repair Steel tubular swaged street light poles complete with pole arms 1.2 m & cast iron base plate ,finial taper plug,bolts,nuts and screws as specified type 410 SP-31 9.0 mtr long and painting with two coat of aluminium paint over one coat of primer on exposed surface of pole complete all as specified and/or as directed by Engineer-in-Charge. ( NOTE- Excavation & PCC will be measured and paid separately) Make :- National / Bombay Poles. |
| 36 | M & L spray for painting and numbering of electric poles including street light brackets, cross arms, GOD system, four pole structure,two pole structure, LT panels from out side with two coats of aluminium duco paint after cleaning and preparing the surface of poles of any size complete all as specified and/or as directed by Engineer-in-Charge. Please Enable Macros to View BoQ information |
| 37 | M & L spray for painting and numbering of electric poles including street light brackets, cross arms, GOD system, four pole structure,two pole structure, LT panels from out side with two coats of aluminium duco paint after cleaning and preparing the surface of poles of any size complete all as specified and/or as directed by Engineer-in-Charge. Please Enable Macros to View BoQ information |