| 1 | WORK NAME |
| 2 | P/laying P.V.C /XLPE insulated & P.V.C. sheathed cable of 1.1 k.v. grade with armoued aluminum conductor of IS 1554 P-1/7098 P-I of Group I of approved make in ground as per IS : 1255 including excavation of 30 cm x 75 cm size trench, 25 Cm thick under layer of sand, 11nd class bricks covering, refilling earth compaction of earth making necessary connection testing etc. as required of size Group-I 10sqmx4core.(Armoured) |
| 3 | 6sqm x 4core |
| 4 | 25sqm x 3.5core (Armoured) |
| 5 | Supplying and making one end termination with heavy duty single compression brass gland SIBG type, aluminium lugs duty crimped with crimping tool, PVC tape etc for following size of armoured PVC insulated & PVC sheathed XLPE aluminium conductor cable of 1100Volt grade as required of size. 4core x 10.0sqmm. |
| 6 | 4 x 6.0 sq.mm |
| 7 | 3.5 core x 25.0 sq.mm |
| 8 | Providing & Laying P.V.C. / XLPE insulated & P.V.C. sheathed Unarmoured Copper cable confirming to IS:1554 P-I / IS :7098 P - I of 1.1 KV with electrolytic grade Copper made of copper rods confirming to IS 613-1964, of purity >99.7 %, Inner / outer sheath confirming to IS:5831 in existing RCC / Hume / Stoneware / PVCpipe/ open duct/cable trench / Cable tray (with cable tie) including testing etc. as required of following size. OEM must have it's own in house NABL accrediated Laboratory for testing procedure as per IS:10810 For additional technical parameters of product / work refer Annexure 'A' attached with this BSR 2.5 sq.mm x 3 core |
| 9 | 4 sq.mm x 4 core |
| 10 | Supplying and making one end termination with heavy duty single compression brass gland SIBG type, heavy duty Copper/Bimetallic lugs duly crimped with crimping tool, PVC tape etc for following size of Armoured PVC insulated & PVC sheathed/ XLPE aluminium conductor cable of 1100 volt grade as required of size. 3 x 2.5 sq.mm |
| 11 | 4 x 4.0 sq.mm |
| 12 | Supplying and drawing FR PVC insulated & unsheathed flexible copper conductor ISI marked (IS:694) of 1.1KV grade and approved make in existing surface or recessed conduit/casing capping including making connections etc. as required. 1x6.0 sq.mm. Group 1 |
| 13 | 1 x 10.0 sq.mm |
| 14 | Supplying and making end termination with heavy Copper / Bimetallic lugs ( Pin / ring type ) duly crimped with crimping tool, PVC tape etc of following size. 16.0 Sq.mm 6.0 Sq.mm |
| 15 | 10.0 Sq.mm |
| 16 | P/F Nut & Bolts. |
| 17 | SITC of quick make and quick break 3 pole current limiting MCCB having following current rating, short circuit breaking capacity at 440/415 V, 50 Hz; O/L & S/C settings and conforming to IS 60947-2 / IEC 60947-2 with front face and centralised adjustable, line load interchangeability, having positive isolation capability, provision for UVR , shunt trip , earth fault trip, push ( test ) to trip, including making connections with lugs & spreaders, etc. as required. 160 Amp , 25 kA, adjustable O/L & fixed S/C setting, Ics = 100 % Icu |
| 18 | SITE of Wall/free standing floor mounted dust and vermin proof compartmentalized cubical panel made out of CRCA sheet, required hardware, duly treatd for derusting in 7 tank process with dephosphating and with power coating on both side of panel in desired shade. The panel having PU/neoprene rubber gasket of not less than 3mm thickness, separate detachable gland plate M.S. base channel hinged door with locking arrangement for equipment/switchgear thickness of sheet shall not be less than 1.6mm upto 600mm length/width of any compartment and be of 2.0mm above 600mm. Load bearing structure shall be of 2.0mm thick sheet supported by base M.S. Channel if required. Side walls and cable alley compartment having bolted type doors with detachable extension type structure.(Only outer area on all sides shall be measured & panel to be fabricated from CPRI approved fabricator) |
| 19 | P&F paper phenolic resin bonded laminates comfirming to IS :2036-1995 for boxes/frames including making holes for switches fet, with brass screws, washers/zinc plated nut and bolts as required. 9.0mm thick. |
| 20 | Supply and fixing of aluminium/copper bus bar by means of SMC/DMC type insulator, high tensile nuts and bolts spring washers in existing panel including bending cutting in required shape and size and colour coding with heat shrinkable PVC sleeves. Electrolytic grade aluminium bus bar. |
| 21 | Plate Earthling as per IS: 3043 with G.I Earth plate of size 600 mm x 600 mm x 6.0 mm by embodying 3 to 4 mtr. below the ground level with 25 mm dia G.I. “B” Class watering Pipe including all accessories like nut bolt reducer nipple wire meshed funnel and C.C. finished chamber covered with hinged type with locking arrangement C.I Cover C.I Frame of size 300 mm x 300 mm complete with alternate layers of salt and coke/ charcoal testing of earth resistance as required. |
| 22 | S&F laying following size earth wire/ in horizontal or Vertical run in ground/ surface/ recess including riveting, soldering, saddles, making connection etc. as required. 10 SWG G.I. ( Hot Dipped ) Wire |
| 23 | GI strip 25mmx3mm( Hot Dipped)size. |
| 24 | P&F of mechanical/ digital time switch having following day/ week programme and min. 100 hous reverse and AC1 rating of 16 to 20 amp including making connections, programming rtc. As reqd . 1 day reverse (mech. Type) Group1 |
| 25 | P&F 240/415V AC MCB with positive isolation of breaking capacity not less than 10KA (B/C/D tripping characteristic) ISI marked IS 8828(1996)1/ conforming to IEC 60898 in existing board/sheets including making connections with lugs, testing etc. as reqd. Four pole MCB 80 A rating. Group 1 |
| 26 | Single pole MCB 6A to 32A rating Group1 |
| 27 | P&F 240/115 V isolator conforming to IS: 13947-111/ IEC 60947-3 on existing board/ sheet including making connections, testing etc. As required Four pole isolator 63 A rating Group1 |
| 28 | P&F of ac operated heavy duty 230/440 Volt power contactor conforming to IS:13947-4-1/EC;947-4-1having provision of mechanical interlocking Din rail mounting type including making connections testing etc. as required. 3 pole power contractor with following AC3 Rating 95 Amp |
| 29 | SF of 110/220 V, LED (22.5 mm dia ) Indicating lamp with integral circuit, terminal block, including connection etc. as required.Red/yellow/Green colour Group1 |
| 30 | S&F following sizes (dia) of ISI marked medium duty PVC conduit along with accessories in surface/ recessed using saddles, clamps, fastener as required including cutting the wall covering conduit and making good the same as required 25mm |
| 31 | 20 mm |
| 32 | P & F Recessed / Surface Mounting heavy duty horizontal type sheet steel Distribution board Phophatised/powder painted complete with suitable rating insulated copper bus bar, shorting link, neutral link, earth link, and din bar, masking sheet, conforming to IS13032 & IS8623 including making internal DB terminations with copper lugs testing etc. as required. Double door Three phase 8 way |
| 33 | Metal door (single phase) 12 way |
| 34 | Metal door (three phase ) 4 way |
| 35 | Providing and Fixing of IP65 Protectd polycarbonate/ polysterene fuse box moulded with inside knock outs of following size with hinged cover, trasparent window, PU gasket, locking arrangement, duly holded with 2 nos. pole clamps of 20mmx3mm flat with nut and bolts, complete with. The box shall be provided with Din rail, 4/8way 10.0/16.0 sq.mm heavy duty connector, earth terminal, complete in all respect.225mmx225mmx100mm |
| 36 | P/L of Double wall corrugated HDPE pipe confirming to IS:14930 P-I&2 with HDPE coupler at 1mtr Depth below the ground for laying cable and back filling the trench, conpaction of earth as required of Gemini or IS:14930 marked make outerDia/Inner dia. 50/55mm |
| 37 | S & Laying following size B Class GI pipe confirming to IS:1239 P-1 (1990) with accessories for laying earth conductror/strip/cable in ground/surface/recess as required 100mm dia. |
| 38 | Supply & fabrication steel structure with ms channel/ angle/joist/ISMB/sheet etc. including welding rivetting cutting nut & bolt painting etc as required. |
| 39 | Providing and laying in position cement concrete including curing compaction etc. complete in specified grade excluding the cost of centering and shuttering-All work upto plinth level. 1:3:6 (1 cement: 3 coarse sand: 6 graded stone aggregate 20mm nominal size). |
| 40 | Plaster on new surface on walls in cement sand mortar 1:6 including racking of joint etc. complete fine finished :20mm thick |
| 41 | Supplying and fixing of CE certified and UL listed GI wire mesh cable tray made from spot welded steel wire hot dipped galvanised between 60 and 80 microns of zinc as per BS 729 including horizontal and vertical bends, reducers, tees, cross members and other OEM made accessories like wall clamp, hold down clamps, Earthing terminal, brackets as required, and duly suspended from the ceiling with electro-zinc coated TF rods, etc. as required of following sizesAll as per pre approved by Engineer in-charge. For additional technical parameters of products/ work , refer Annexure \\"A\\" attached with this BSR . 200 mm x 50 mm x 6 mm |
| 42 | Providing & applying Lime kara1:2 (1lime cream:2 Zikkipowder) grinding mortar with grinding mill /manually on lime base, on ceiling and all flat surface in two coats. First coat applying 3mm to 4mm thick and curing properly at least 7days, second finishing coat done after 7 days of previous coat as per traditional practice.(thickness not more than 6 mm.) |
| 43 | Aluminium T or L sections |
| 44 | PART B - NON - BSR ITEMS Supply, Installation, Testing and Commissioning of LED Round Flood Light of 25W power consumption, suitable for outdoor architectural and area lighting applications. The luminaire shall have a die-cast aluminium housing with powder-coated finish, inbuilt visor, IP66 protection and IK07 impact resistance, designed to withstand harsh weather conditions. It shall operate on 100–280VAC, 50–60Hz input voltage with power factor ≥0.90 and THD ≤10%. The fixture shall deliver a luminous flux of ≥2000 lm with luminous efficacy ≥80 lm/W in 3000K mono colour output. Optical system shall be of PC/PMMA material with 7° beam angle (customizable as per site requirement) ensuring uniform illumination. The LED light source shall be from reputed makes such as Osram, Seoul, Refond, Lattice Power, Bridgelux or equivalent, with a rated life of ≥50,000 hours at junction temperature ≤85°C (maximum allowable 90°C). The fitting shall include inbuilt driver with ON/OFF operation and surge protection device, capable of reliable performance within -10°C to +50°C operating temperature and 0–95% humidity. The overall dimensions of the luminaire shall be Dia.181mm x H.162mm (±10% tolerance, subject to manufacturer’s design). The scope of work shall include complete supply of all accessories, mounting arrangements, necessary IP-rated connectors (to ensure warranty validity), wiring connections, installation at site, testing of functionality, and commissioning as per specifications and directions of the Engineer-in-Charge. |
| 45 | Supply, Installation, Testing and Commissioning of LED Linear Wall Washer of 40W power consumption, with dimensions 1030mm x 48mm x 99mm (±10% tolerance, subject to manufacturer’s design), suitable for outdoor façade and architectural lighting applications. The luminaire shall have an extruded aluminium body with die-cast end caps, powder-coated finish, IP66 protection and IK07 impact resistance, designed to withstand harsh weather conditions. It shall operate on 100–280VAC, 50/60Hz input voltage with power factor≥0.90 and THD ≤15%. The fixture shall deliver a luminous flux of ≥3200 lm with luminous efficacy ≥80 lm/W in 3000K mono colour output. Optical system shall be of high-efficiency PC/PMMA material with 15°x30° beam angle (customizable as per site requirement). The LED light source shall be from reputed makes such as Osram, Seoul, Refond, Lattice Power, Bridgelux or equivalent, with a rated life of ≥50,000 hours at junction temperature ≤85°C (maximum allowable 90°C). The fitting shall include inbuilt driver with ON/OFF operation, surge protection of 4kV (optional 10kV), capable of reliable performance within -10°C to +50°C operating temperature and 0–95% humidity. The scope of work shall include complete supply of all accessories, mounting arrangements, necessary IP-rated connectors (to ensure warranty validity), wiring connections, installation at site, testing of functionality, and commissioning as per specifications and directions ofthe Engineer-in-Charge. |
| 46 | Supply, Installation, Testing and Commissioning of 50W LED Flood Light suitable for outdoor architectural and area lighting applications, with die-cast aluminium housing and powder-coated finish, IP66 protection and IK08 impact resistance; operating on 100–280VAC, 50–60Hz with power factor >0.90 and THD <10%; The fixture shall deliver a luminous flux ≥6500 lm with luminous efficacy ≥100 lm/W in 3000K mono colour output; provided with PC/PMMA optics having 60° beam angle (customizable as per site requirement) ensuring uniform illumination. The LED light source shall be from reputed makes such as Osram, Seoul, Refond, Lattice Power, Bridgelux or equivalent with rated life≥50,000 hours at junction temperature ≤85°C (maximum allowable 90°C); integrated driver with ON/OFF operation, surge protection device 4kV (optional 10kV), and reliable performance within -10°C to+50°C operating temperature; overall dimensions approx. L300mm xW.146 x H.87mm (±10% tolerance, subject to manufacturer’s design); The scope of work shall include complete supply of all accessories, mounting arrangements, necessary IP-rated connectors (to ensure warranty validity), wiring connections, installation at site, testing of functionality, and commissioning as per specifications and directions of the Engineer-in-Charge. |
| 47 | Supply of 24V IP67 Flexible/ linear strip 10W/mtr WW Please Enable Macros to View BoQ information |