| 1 | BoQ_Ver3.0 Item Rate Normal INR Only INR Select, Excess (+), Less (-) Less (-) Tender Inviting Authority: CHIEF ENGINEER (AF) SHILLONG ZONE, SHILLONG. Name of Work: PROVN OF FIREFIGHTING SYSTEM FOR CERTAIN OTM ACCN AT AF STN HASIMARA Contract No: CE(AF)SZ/HAS/ OF 2026-2027 File No: 88483/HAS/E8 Bidder Name : PRICE SCHEDULE : BOQ(This BOQ template must not be modified/replaced by the bidder and the same should be uploaded after filling the relevent columns, else the bidder is liable to be rejected for this tender. Bidders are allowed to enter the Bidder Name and Values only ) NUMBER # TEXT # TEXT # NUMBER # TEXT # NUMBER NUMBER TEXT TEXT # NUMBER # TEXT# TEXT # NUMBER # NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER # NUMBER # TEXT TEXT NUMBER # NUMBER # DATE NUMBER # NUMBER # TEXT # SL No ITEM DESCRIPTION Item Code / Make QTY UNIT ESTIAMTED RATE Addition / Deduction Addition / Deduction Values Currency Convertion against each Item Quoted Currency in INR / Other Currency RATE IN FIGURES TO BE ENTERED BY THE BIDDER RS. P Excise Duty VAT Freight Charges ( Unloading & Stacking) Any Other Taxes/Duties/Levies Other Taxes 2 IIIrd Party i.e DGS&D / RITES etc Inspection Charges @0.34%+Service Tax Less for Cenvat Credit,if any respect of Supplies Under full Excise Duty Category TOTAL AMOUNT Without Taxes TOTAL AMOUNT TOTAL AMOUNT IN WORDS Represent (%) Percentage having Above/ Below ( + or - denomination) the Lump sum pre price inserted by MES |
| 2 | SCHEDULE \\"A\\" Part - I (BUILDINGS/STRUCTURES WORK)Details of Buildings are given here-in-before:- |
| 3 | SCHEDULE \\"A\\" PART- II (SITE CLEARENCE AND AREA DEVELOPMENT) Details of prepriced Schedule is given in tender documents |
| 4 | SCHEDULE \\"A\\" PART- III( INTERNAL ELECTRIFICATION)Details of prepriced Schedule is given in tender documents. |
| 5 | SCHEDULE \\"A\\" PART-IV ( RCC UG SUMP/STATIC WATER TANK )Details of prepriced Schedule is given in tender documents. |
| 6 | SCHEDULE \\"A\\" PART- V (WATER STORAGE TANK WITH RCC STAGING)Details of prepriced Schedule is given in tender documents. |
| 7 | SCHEDULE \\"A\\" PART- VI (PROVN OF HANGING ARRANGEMENT FOR FIRE FIGHTING)Details of prepriced Schedule is given in tender documents |
| 8 | SCHEDULE \\"A\\" PART- VII (ROADS / CULVERTS / HARD STANDING)Details of prepriced Schedule is given in tender documents |
| 9 | SCHEDULE \\"A\\" PART- VIII (AREA DRAINAGE)Details of prepriced Schedule is given in tender documents |
| 10 | SCHEDULE \\"A\\" PART- IX (SEWAGE DISPOSAL)Details of prepriced Schedule is given in tender documents |
| 11 | SCHEDULE \\"A\\" PART- X(FENCING & GATE)Details of prepriced Schedule is given in tender documents |
| 12 | SCHEDULE \\"A\\" PART- XI(EXTERNAL WATER SUPPLY)Details of prepriced Schedule is given in tender documents |
| 13 | SCHEDULE \\"A\\" PART- XII(EXTERNAL ELECTRIFICATION)Details of prepriced Schedule is given in tender documents. |
| 14 | SCHEDULE \\"A\\" PART- XIII(FIREFIGHTING SYSTEM)Details of prepriced Schedule is given in tender documents. |
| 15 | SCHEDULE \\"A\\" PART -XIV (MISCELLANEOUS ITEMS) Note:- This schedule is not pre-priced by MES and the pre-priced rate indicated as \\"Rs 0.00\\" under Col.' F ' signifies this fact only. |
| 16 | INTERNAL ELECTRIFICATIONM&L for earthing complete with galvanised steel earth plate 600mm x 600mm x6mm thick electrode and 4 mm dia galvanised iron wire as earthing lead burried directly in ground vertically (earth pit not less than 2.25mtr deep below ground level) with top edge of the plate not less than 1.5mtr below normal ground level, the earth plate surrounded by adequate quantity of charcoal dust and common salt to a packed thickness of 15 cm on all sides connected to GI wire 4mm dia as earth lead by means of bolts, nuts, check nuts and washers of galvanised iron or steel and connected to board / panel/ test point at the other including necessary earth work in any type of soil, returning filling in and removal of surplus soil, concrete pit in PCC (1:3:6) type C1, pre cast RCC 1:2:4 type BI cover slab 54cm x 54cm x 5cm reinforce with 8mm dia bar TMT @150mm centre to centre both ways with one handle for lifting made out 8mm dia MS bar with wire mesh funnel, 20mm GI tubing medium grade for watering and 15mm GI tubing light grade for protection, test point, testing on completion all as shown in Electrical Plate No 3 of SSR Part-I (2009) complete all as specified and directed. |
| 17 | RCC UG SUMP/STATIC WATER TANKSupply only 250mm x 10mm PVC water stop bar for construction joint in RCC work incluiding all taxes, octroi and fixing in different lacations during construction, complete all as specified and as directed. |
| 18 | WATER STORAGE TANK WITH RCC STAGINGS&F rotational moulded polyethylene three layer water storage tanks (cylindrical vertical with closed top) hoisted and fixed in position all as specified in SSR Part I of 5000 ltr capacity, complete all as specified and directed. |
| 19 | SEWAGE DISPOSALM&L for LLDPE Septic tank designed to carry sewage and water, excavation in any type of soil, PCC 1:4:8 below foundation, vent pipe /shaft connection complete of 2000ltr capacity conventional type, complete all as specified and shown on drawing. |
| 20 | M&L for construction of soakage well excacation, in any type of soil, foundation in PCC 1:3:6 walls of honey comb and solid in M-25 concrete including intercepting chamber, screen chamber, brick work in CM, RCC Cover slab in M-25, filling with broken brick bats, complete of size 1.20mtr dia x 1.50 Mtr deep complete all as specified and directed |
| 21 | EXTERNAL WATER SUPPLYSupply, fixing & testing of 100mm dia. ductile Iron pipe, centrifugally cast (spun) ductile iron pressure pipe with spigot & socket end single socket including specials, class 'k-9' confirming to IS : 8329/2000 and amendment No. 1 suitable for (push on) rubber gasket jointing with inside cement mortar lining and outside zinc coating with finishing layer of black bitumen coating duly ISI marked will be supplied. The standard length of the pipe 5.5 mtr complete with excavation and all other work complete all as specified and as directed |
| 22 | M&L for cutting to existing DI Pipe line of 100 mm dia including taping and fixing tee DI 100 x 100 x50 mm dia branch connection, complete all as specified and as directed. |
| 23 | Construction of brick masonry valve pit of size 600mm x 600mm x 600mm (internal dimensions) with one brick thick wall in cement mortar 1:4 on 100 mm thick P.C.C. 1:4:8 type D2 (using 40mm graded broken stone aggregate) as in foundation lean concrete, including PCC 1:3:6 type C-1 (using 20mm graded crushed stone aggregate) as in bedding and coping and 10mm thick cement plaster in CM (1:4) internally and externally up to 15cm below ground level providing valve pit 40 x 40 x 6mm angle iron frame all-round the fixed point by means of 4Nos holdfast made out of flat iron 40 x 6mm x 150 mm long bent to shape embedded using 150 mm long bolt with anchor plate in PCC block (1:2:4) type B-1 (using 20mm graded crushed stoned aggregate) of size 230 x 200 x 100mm including provision of hinges welded with angle iron frame and MS cover 3mm thick welded to angle 40 x 40 x 6 mm, MS handle of suitable and size welded with MS cover and suitable locking arrangement including 65mm dia pad lock and applying two coats of synthetic enamel paint over a coat of red oxide primer including necessary excavation and earth work in any type of soil complete all as specified and directed. |
| 24 | FIRE FIGHTING SYSTEMSupply and fixing mild steel 'C' class diesel pump exhaust pipe 150 mm dia with one layer of 10 mm thick asbestos rope insulation and including all fitting clamp/ structural steel supports complete all as specified and as directed. |
| 25 | Supply, installation and testing of deluge valve of 100 mm dia, complete all as specified and as directed. |
| 26 | Supply and fixing bulb type gun metal sprinkler head pendent type set to operate at 141 degree C, complete all as specified and as directed. |
| 27 | Construction of brick masonry valve pit of size 900mm x 900mm x 900mm (internal dimensions) with one brick thick wall in cement mortar 1:4 on 100 mm thick P.C.C. 1:4:8 type D2 (using 40mm graded broken stone aggregate) as in foundation lean concrete, including PCC 1:3:6 type C-1 (using 20mm graded crushed stone aggregate) as in bedding and coping and 10mm thick cement plaster in CM (1:4) internally and externally up to 15cm below ground level providing valve pit 40 x 40 x 6mm angle iron frame all-round the fixed point by means of 4Nos holdfast made out of flat iron 40 x 6mm x 150 mm long bent to shape embedded using 150 mm long bolt with anchor plate in PCC block (1:2:4) type B-1 (using 20mm graded crushed stoned aggregate) of size 230 x 200 x 100mm including provision of hinges welded with angle iron frame and MS cover 3mm thick welded to angle 40 x 40 x 6 mm, MS handle of suitable and size welded with MS cover and suitable locking arrangement including 65mm dia pad lock and applying two coats of synthetic enamel paint over a coat of red oxide primer including necessary excavation and earth work in any type of soil complete all as specified and directed. |
| 28 | Supply and fixing double door factory made motor control panel CPRI approved for fire fighting equipment outdoor frame mounted suitable for 415V 3phase 4 wire 50Hz AC supply system as specified .The panel should be powder coated paint for better environmental protection, made of CRCA sheet steel 3.15 mm, including making of foundation of the panel, lugs and gland of suitable size, fixing and connection included complete all as specified and as directed.(a) INCOMING:- (i)250 Amps 4 poles MCCB electronics release type 36 KA, 415 V:- 01 No(ii) Digital voltmeter 96 Sqmm sizes and 0-500 V with phase selection push button:- 01 No(iii) Phase indiaction lamps:- 03 No(iv) Aluminum busbar of 300A rating each:- 04 No(b) OUTGOING:- (i) 160 Amps 4 pole MCCB electonics release 25 KA, 415V:- 2 No (for main fire pump 01 No & 01 No spare)(ii) 25 Amps 4 pole MCCB electonics release 25 KA, 415V:- 03 Nos(iii) 25 Amps MCB SPN 10 KA, 230 V:- 02 Nos (iv) 16 Amps MCB SPN 10 KA, 230V:- 01 No (v) On/Off indicating lamps:- 02 sets(vi) Fully automatic star delta stareter 75 HP for the capacity indiacted for motor complete with single phase preventer relay:- 02 No |
| 29 | (Srl Item No. 27.00 Contd...)(viii) Ammeter digital type of size 96 Sqmm with phase selection with 3 No CTs of suitable ratio and range 0 to 200A:- 02 Nos(ix) Fully automatic star delta stareter 12.5 HP for the motor complete with single phase preventer relay:- 01 No (x) Fully automatic star delta stareter 5 HP for the motor complete with single phase preventer relay:- 02 Nos |
| 30 | S&F battery unit for automatic tripping of suitable capacity at 24 V DC complete with necessary boost/ trickle charge arrangement I/C providing and fixing necessary control system component such as timer, relays and contractors including DC meter etc as required for diesel engine driven pump complete all as specified and as directed. |
| 31 | Earthing complete with galavanised iron plate electrode 60 cm x 60cm x 6mm surrounded by charcoal and salt burried directly in ground vertically in a pit of depth of not less than 2.25 mtr below ground level with top edge of the earth plate at a depth of not less than 1.5 mtr below ground level connected to galvanised iron, earth strip of size 32 x 6 mm protected by galvanised steel pipe 50 mm bore (light grade) and connected to main switch or main control panel board all as shown in electrical plate No 3 of SSR 2020 part I and including necessary excavation and earth work. The rate also include charcoal and salt in alternate layers 20 mm bore GI Pipe (light grade) for watering, protection pipe, funnel, wire mess, PCC Chamber in cement concrete (1:3:6) type C-1, 40 mm thick RCC (1:2:4) type B1 as in cover slab of size 300x300x100 mm with one handle made out of 8 mm dia round bar etc, complete all as specified and as directed.Note:- (i) The rate include earth electrode and protection pipe upto 5m length. (ii) The earthing pit should be provided with proper earth pit and pit cover. Pit cover should be painted with synthetic enamel paint of approved colour and pit number to be marked to be on a GI plate above 45 cm from GL as per colour code followed in AF station. (iii) If the desired earth resistance is not achieved during test as per IS the complete earthing shall be carried out by the contractor at his own cost and no extra claim shall be admissable complete all as specified and as directed. |
| 32 | Supply, installation, testing and commissioning of foam tank bladder type of capacity 450 ltr, complete all as specified and as directed. |
| 33 | Supply, fixing and testing of hand held foam nozzle air aspirated type with hose including necessary connection, complete all as specified and as directed. |
| 34 | Supply, fixing and testing of monitor 63mm dia outlet, complete all as specified and as directed. |
| 35 | Supply and fixing Ceiling Mounted Clean Agent (HFC236fa) Fire Suppression System 5 KG Capacity, Modular type , Fire Class A,B,C & Electric with automatic discharge mechanism, discharge time - Min 8 Sec, complete all as specified and as directed. |
| 36 | Supply and fixing repeater indicator panel for local fire alarm control unit indicating trouble messages, complete all as specified and as directed. |
| 37 | Supply and laying single mode optical fibre cable, 4 core in and including 20mm dia PVC conduit in trenches wall/floor for connecting fire alarm control panels to be installed in different location including joint and jointing materials as required complete all as specified and as directed. |
| 38 | Supply and fixing wall mounted sign board consisting of zinc sulphide luminescent coating on acrylic sheet and of size 150 x 300 mm and arrows on other half and types like FIRE EXIT, STAIR CASE, FIRE ASSEMBLY POINT and other signage, complete all as specified and as directed. |
| 39 | Supply, laying & testing PVC insulated, FRLS, PVC sheathed cable galvanized steel strip or wire armoured, electric control cables (Heavy duty) with stranded copper conductor of size 1.5 sq mm, 2 core, 1100 Volts grade, complete all as specified and as directed. |
| 40 | Supply & fixing 80 ltrs capacity seamless steel cylinder complete with pneumatical valve assembly arrangement, supervisory switch connection for minitoring cylinder pressure, in compliance with Chief Controller of Explosive, Nagpur with electric & pressure operated control heads as per requirement (Master/Slave Actuation Packages) a safety burst disc, and any other accessories to make the cylinder completely operational including Flexible Actuation Hose (directed to a pressure operated control head on each cylinder valve using 1/4 inch actuation hose), container strap, structural supports etc, complete all as specified and as directed. |
| 41 | Supply, testing and commissioning HFC-227ea Gas, factory-filled in the Gas Cylinder/ from a UL-Listed Gas Filling Station, as per the specifications and manufacturer recommendations/ specified design concentration and fill density complete all as specified and as directed. |
| 42 | Supply & fixing discharge nozzles designed to provide the proper flow rate and distribution of gas to total flood hazard area : (180/360 deg. As per requirement) complete all as specified and as directed. |
| 43 | Supply & fixing micro-processor based alarm panel (addressable panel of single loop) for required devices capacity, discharge module with minimum 80 character LCD type display & LED indication for all zones, complete with internal sounder, alarm/fault indications & standby 24 V lead acid batteries with charger. This panel needs to be compatible with the central BMS/BAS System through interface convertors, complete all as specified and as directed. |
| 44 | Supply & fixing gas release panel with 2-Zone Fire detection and 1-Zone gas discharge module with binary switch timer for release delay and potential free contact to relay \\"Gas Release\\" signal panel. This panel needs to be compatible with the Fire Alarm Panel and shall be UL Listed complete all as specified and as directed. |
| 45 | Supply & fixing Electronic Hooter with flashing type multi-Strobe for combined audio + visual alarms, to be wired and located as per instructions, complete all as specified and as directed. |
| 46 | Supply & fixing Abort Switch of approved Pull- Type, as per approved location complete all as specified and as directed. |
| 47 | Supply & fixing Release Switch as per approved location complete all as specified and as directed. |
| 48 | Supply & fixing Key-operated selector switch between the Main and Reserve Gas Banks complete all as specified and as directed. |
| 49 | Supply & fixing addressable Photoelectric/ Ionization Smoke detectors complete with mounting base LED, address switch, as per requirements complete all as specified and as directed. |
| 50 | Supply & fixing 1.5mm X 2 core Fire Survival Armoured cable, with Copper conductor (600/1000V) having Cross linkable Ethylene Propylene Rubber (EPR) insulation with Low Smoke Zero Halogen (LSZH) inner & outer sheath, basic design as per BS- 7846:2009 / IEC 60502 Part-1:2004. Should retain Circuit Integrity @ 8500C for minimum period of 2 Hrs as per BS 8519:2010, BS 8491:2008 Cat.3 (120 mins.), BRE Global – UK Certified or approved Equivalent complete all as specified and as directed. |
| 51 | Supply & fixing MS pipes (seamless piping as per ASTMA 106, Grade 'B' Schedule 40) including all necessary fittings for all low side piping, and MS pipes (seamless piping as per ASTMA 106, Grade 'C' Schedule 80) for Manifold for 2 nos. Cylinders. (1 Working + 1 Standby) including all necessary fittings as per NFPA 2001 guidelines including all structural supports complete all as specified and as directed. |
| 52 | Supply & fixing interface module for communication between Gas Release Panel and specified compatible devices, complete all as specified and as directed. |
| 53 | Making Electrical Connections to the Fire Alarm Main Panel including all necessary material and accessories as per requirements, complete all as specified and as directed. |
| 54 | Supply & fixing Photo-luminiscent Gas Release caution sign boards for approved locations complete all as specified and as directed. |
| 55 | Supply & fixing HCFC Blend E /Halotron type fire extinguisher complete with discharge nozzle/ hose for manual operation ( 5 Kgs Capacity), complete all as specified and as directed. |
| 56 | Supply & fixing MS structural work fabricated from standard section e.g. M.S rounds, angles, channels, plates including cutting to size,drilling, welding fixing and welding to insert plates in RCC structural members including cutting and making good the walls, ceilings and floors, complete all as specified and as directed. |
| 57 | Performing dump test for room of Gas discharge test with nitrogen gas (HFC 227ea gas shall not be used) complete i.e. checking of the Fire detection and alarm system room integrated test (Procedure of testing shall be as per NFPA 2001) complete all as specified and as directed. |
| 58 | Supply of 4 Kg Automatic Direct Low Pressure Fire Suppression Extingusher and Valve Fire Suppression Extingusher can stored pressure type, fitted with pressure Guage, Hydraulic pressure tested to 35 bars, operating pressure 15 bar application on class A,B,C and electrically started fires.Valve: Direct low pressure with integrated ball valve to minimize leakage, integrated position monitoring of valve for open / close position of valve using potential free switch contact. Special key for locking valve position to avoid accidental closure. Operating pressure 15 bars tested upto 35 bar. 2 tube connection and assembly complete all as specified and as directed. |
| 59 | Supply of Pressure switch to monitor pressure in the tube, switch point at 11 Bars complete all as specified and as directed. |
| 60 | Supply of heat sensing tube for pressure guage fitting for Automatic fire detection and suppression system made by special modified polyamide (PA), Color Black or Red, High grade HR quality, UV Stabilized, Inner diameter 4mm, Outer Diameter 6 MM, Melting point approx. 220 Degrees Celsius when heating up with 10 K/Minute, Steady load tested upto Max 80 Degree Celsius. The lowest operating temparature is stipulated at minus 40 D Celcius. Service Pressure at 20 Degree Celcius approx 120 bars. Release Temperature at 15 Bars pressure approx 150 Deg to 180 Deg C (without Flame) complete all as specified and as directed. |
| 61 | Supply of End of line adapter for pressure guage fitting for Automatic fire detection and suppression tube used for fitting at the end of the tube for pressurising and re pressurising the tube. Elastomeric sealings. Copper Nickel Plated. Temaprature Range Ts-20 Deg C till + 60Deg C Maximum working pressure 25 Bars, made as per PED (pressure equipment directive) complete all as specified and as directed. |
| 62 | Supply of End of line Plug for Automatic fire detection and suppresing tube used for fitting at the end to terminate the point. Fitting made by brass nickel plated material with Elatomeric sealings, Temparature range TS-20 Deg C till 60 Deg C, Maximum working pressure 25 Bars, Made as per PED (Pressure Equipment Directive) complete all as specified and as directed. |
| 63 | Supply of T Connection, Brass Nickel Plated, for 4 x 6mm sensor Tube, quick and easy disassembly using special tool, working pressure 15 Bars at 15 Deg Temparature range-40 Deg C till+ 80 Deg C. Elastomeric Sealings, External Diameter tube 6 mm complete all as specified and as directed. |
| 64 | Installation, testing & commissioning includes complete setup of the system, installation of cylinders, response panel on specially designed brackets, Laying of sensor tubes using tube attachments and cable ties, fixing end of line plugs and end of the adpaters, pressurising tube @ 15 Bars using Nitrogen pressurising agent. Supply of all sundary items shall also be part of installation complete all as specified and as directed. |
| 65 | Supply and fixing extinguisher ABC (Map90) stored pressure MS RED Portable capacity 6 Kg as per IS: 2190/15683 complete all as specified and as directed. |
| 66 | Supply and fixing extinguisher CO2 store pressure MS RED Portable capacity 4.5 Kg capacity as per IS: 2190/15683 complete all as specified and as directed. |
| 67 | Supply and fixing extinguisher water type stored pressure MS RED Portable capacity 6 Ltr capacity as per IS: 2190/15683 complete all as specified and as directed. |
| 68 | Supply and fixing Fire Extinguisher mechanical foam (AFFF) stored pressure MS RED portable type suitable of 6 Ltr capacity as IS: 2190/15683 complete all as specified and as directed. |
| 69 | Supply and fixing Fire Extinguisher clean agent (HFC236fa) type stored pressure MS RED Portable suitable of 4 kg capacity as IS: 2190/15683 complete all as specified and as directed. |
| 70 | Supply and fixing Fire Extinguisher mechanical foam (AFFF) stored pressure MS RED portable type suitable of 9 Ltr capacity as IS: 2190/15683 complete all as specified and as directed. |
| 71 | Supply and fixing Extinguisher ABC (Map90) stored pressure MS RED Portable capacity 9 Kg as per IS: 2190/15683 complete all as specified and as directed. |
| 72 | Supply and fixing Fire Extinguisher ABC (Map90) stored pressure MS RED Wheeled capacity 25 Kg as per IS: 2190/16018 complete all as specified and as directed. |
| 73 | Supply and fixing Fire Extinguisher CO2 type stored pressure MS RED wheeled suitable of 22.5 kg capacity as IS: 2190/16018 complete all as specified and as directed. |
| 74 | Supply and fixing Fire Extinguisher wheeled mechanical foam(AFFF) type strored pressure MS RED wheeled suitable of 45 Ltr capacity as IS: 2190/16018 complete all as specified and as directed. |
| 75 | Note:- Schedule of credit (Sch 'A' Part- XV) amount of Rs 4,53,300.00 shall be deducted from the total quoted amount of BOQ. Total in Figures 0.0 0.0 INR Zero Only 4.0 Construction of chamber for 100mm sluice plates item5 10.0 Nos Quoted Rate in Figures Select 0.0 0.0 Zero Only Quoted Rate in Words INR Zero Only Please Enable Macros to View BoQ information |