| 1 | Running maintenance and operation of sewage treated water booster pump sets and accessories at following pump houses as per inventory, Terms & Condition attached.a) At Rithala Site no.3 Pump House No-1 |
| 2 | b) At Rithala Site no.3 Pump House No-2 |
| 3 | c) At Sec-24 Near petrol station Pump House |
| 4 | d) At sec-24 pkt-9 deep vihar House |
| 5 | e) At sec-23 Pump House |
| 6 | Painting & numbering/ naming of electrical installation (booster pump sets, CI/MS/GI pipe, valves, panel etc. complete) inside the pump house as reqd. |
| 7 | Dismantalling of existig damaged booster pump foundation upto required level and recasting the same after repairing and replacement of foundation bold, steel bar including fixing of existing base frame, dismentaling & refixing of booster pump sets etc. complete as reqd. |
| 8 | Repairing & rewinding of 3 phase, 415V, 1440 RPM, 60 HP, induction motor duly coupled with sewage treated water pump set i/c supplying & replacement of suitable ball bearing-2 Nos. (SKF), Connection Plate-1 No. i/c dismantling, cartage, refixing, connection, testing etc. complete as reqd. |
| 9 | Repairing and Rewinding of 3 phase, 415 volt, 1440 RPM, 40 HP induction motor duly coupled with sewage treated water pump set i/c supplying and replacement of suitable ball bearing 2- Nos. (SKF)connection plate 1- Nos. i/c Dismantling ,cartage ,refexing, connection, testing ,painting etc, complete as required |
| 10 | Repairing and servicing of sewage treated water pump set (model SHM 100/26 Kirloskar make) i/c supplying and replacement of following parts i/c dismantling and labour, cartage, refixing. commissioning, testing etc. complete as reqd. a) Remetaling & repairing of pump shaft i/e turning & grinding etc. ---1 Job b) S/R of ball bearing (No. 6309)--2 Nos.(SKF) c) S/R of gland sleeve S.S --1 set. d) S/R of gland plate --1 set. e) S/R of Gland stud--2 No. f) S/R Impeller nut-----1 No. g) S/R of complete set of body studs-- 1 set. |
| 11 | Supplying & replacement of overload coil, brass finger, oil of oil immerged star delta starter etc complete as reqd. |
| 12 | Supplying & replacement of oil immerged star delta starter upto 100 HP capacity suitable for booster pump operation of upto 60 HP capacity including connection, testing etc. complete as reqd. |
| 13 | Supplying & replacement of following control gear / accessories in the existing installation for electric panel boards, motor starters, connection, testing etc. as reqd.a) 4 Pole MCCB 250 Amp. 36 K.A.(DSR 2.2.16) |
| 14 | b) 400 A, 50 kA, FPMCCB(DSR 2.2.18) Please Enable Macros to View BoQ information |