| 1 | Less Credit old pumping machinery |
| 2 | Less credit old transformer |
| 3 | Less Credit old non clog pumping machinery including panel board, cables etc., complete 6000 LPM 65 Mtr. Head 150 BHP |
| 4 | LT CABLE ALLUMINIUM: Supply, erection, testing and commissioning of IS marked 3.5 core Cables, Solid Aluminum conductor up to 10sqmm and balance stranded conductor, XLPE Insulated, cores laid up, PVC Inner sheathed, Armoured (Aluminium wire for single core up to 70sqmm and balance Aluminium strip, Glavanised wire for cables up to2x10sqmm, 3x10sqmm, 4x6sqmm and balance all galvanized steel strip) extruded PVC type ST2 Outer sheathed, 650/1100V grade as per IS7098 (Part-1) 1988 with up to date amendments along with all accessories complete in all respect. Make: Indian Cables Ltd./ Finolex / Havells / Polycab / RR Cables / CAPP / Gloster / Universal / Fort Gloster Industries Ltd./ Asian Cables Corporation Ltd. 300 Sqmm size |
| 5 | Supply, erection, testing and commissioning of Horizontal motor pumping set for Raw water having head 20.00 m as per indicated requirements of discharge in LPM and power capacity in BHP Make: KSB, CRI, Kirlosker, Crompton Greeve, Lubi (800 LPM 7.50 HP) complete in all respect as per approved NIT. |
| 6 | Copper Cable Supply and jointing three core flat cables of approved make with bare bunched copper conductor insulated and sheathed with PVC for Pumping machinery /fountain lights etc with voltage grade 1100 volts marked with IS:694, 1990 including cost of jointing, materials as well as carriage, loading, unloading etc. complete in all respect up to the entire satisfaction of Engineer- in-Charge.Three Core 95 sqmm copper cable |
| 7 | Supplying, erection, testing and commissioning of horizontal motor pumping set for raw water having head 80.00 m as per the indicated requirements of discharge in LPM and power capacity in BHP as per IS marked.Discharge Capacity (LPM) 7000 Power Capacity (BHP) 225 |
| 8 | PANEL BOARDS FOR MOTOR:- Supply Erection,Testing and Commissioning of wall mounted electrical LT Panel board of 1200 x 900 mm x 400 mm, fabricated from SWG CRCA sheet duly stolen with suitable angle iron frame work and completely powder coated of suitable size deep having following item for 2 Non pumping set) STAR DELTA STARTER :- 1.Main MCCB (ABB/LandT/SCHNEIDER - 01 nos 2. Controlling MCB - 01 nos 3.THERMAL OVER LOAD RELAY (ABB/LandT/SCHNEIDER) - 01 nos 4. AUXILARY CONTACTOR (ABB/LandT/SCHNEIDER) - 03 nos 5.START/STOP PUSH BUTTON(SCHNEIDER/ SALZAR/SEIMENS) 6. EMERGENCY SWITCH (SCHNEIDER/SALZAR/SEIMENS) - 01 nos 7. DIGITAL VAF METER (SECURE/SELEC/TECHNO/ABB) - 01 nos 8.CT RATIO - 100/5 (AE/KAPPA/LandT) - 01 nos 9. CAPACITOR BANK AS PER LOAD REQUIREMENT 10. CHANGE OVER SWITCH AS PER LOAD (SCHNEIDER/ SALZAR/SEIMENS) - 01 nos 11.SELECTOR SWITCH(SECURE/SELEC/TECHNO/ABB) - 01 nos 12. SINGLE PHASE PREVENTER (SECURE/ SELEC/ TECHNO/ ABB) -01 nos 13. ELCB BREAKER (ABB/ LandT/ SCHNEIDER) 7000 LPM x 80 mtr. Head. |
| 9 | PANEL BOARDS FOR MOTOR: - Supply Erection, Testing and Commissioning of wall mounted electrical LT Panel board, fabricated from SWG CRCA sheet duly stoten with suitable angle iron frame work and completely powder coated of suitable size deep having following item for 1 Non clog submercible pumping)START DELTA STARTER :- 1. Main MCCB (ABB/LandT/SCHNEIDER - 01nos2. Controlling MCB - 01nos3.THERMAL OVER LOAD RELAY (ABB/LandT/SCHNEIDER) - 01 nos4. AUXILARY CONTACTOR (ABB/LandT/SCHNEIDER) - 03 nos5. START/STOP PUSH BUTTON (SCHNEIDER/SALZAR/SEIMENS)6. EMERGENCY SWITCH (SCHNEIDER/SALZAR/SEIMENS) - 01 nos7. DIGITAL VAF METER (SECURE/SELEC/TECHNO/ABB) - 01 nos8.CT RATIO - 100/5 (AE/KAPPA/LandT) - 01 nos9. CAPACITOR BANK AS PER LOAD REQUIREMENT10. CHANGE OVER SWITCH AS PER LOAD (SCHNEIDER/SALZAR/SEIMENS) - 01 nos11. SELECTOR SWITCH (SECURE/SELEC/TECHNO/ABB) - 01 nos12. SINGLE PHASE PREVENTER (SECURE/SELEC/TECHNO/ABB) -01 nos13. ELCB BREAKER (ABB/LandT/SCHNEIDER)1650 LPM x 40 mtr. |
| 10 | PANEL BOARDS FOR MOTOR: - Supply Erection, Testing and Commissioning of wall mounted electrical LT Panel board, fabricated from SWG CRCA sheet duly stoten with suitable angle iron frame work and completely powder coated of suitable size deep having following item for 1 Non clog submercible pumping)DOL Starter :- 1.Main MCCB(ABB/LandT/ SCHNEIDER), Controlling MCB - 2nos2.THERMAL OVER LOAD RELAY (ABB/LandT/SCHNEIDER) - 01nos3. AUXILARY CONTACTOR (ABB/LandT/SCHNEIDER) - 01nos4. START/STOP PUSH BUTTON (SCHNEIDER/SALZAR/SEIMENS) - 1each5. EMERGENCY SWITCH (SCHNEIDER/SALZAR/SEIMENS) - 01 nos6. DIGITAL VAF METER (SECURE/SELEC/TECHNO/ABB) - 01 nos7. CT RATIO - 100/5 (AE/KAPPA/LandT)8. CAPACITOR BANK AS PER LOAD REQUIREMENT9. CHANGE OVER SWITCH AS PER LOAD (SCHNEIDER/SALZAR/SEIMENS)10. SELECTOR SWITCH (SECURE/SELEC/TECHNO/ABB)11. SINGLE PHASE PREVENTER(SECURE/SELEC/TECHNO/ABB) 800 LPM x 20 mtr |
| 11 | PANEL BOARDS FOR MOTOR: - Supply Erection, Testing and Commissioning of wall mounted electrical LT Panel board, fabricated from SWG CRCA sheet duly stoten with suitable angle iron frame work and completely powder coated of suitable size deep having following item for 1 Non clog submercible pumping)START DELTA STARTER :- 1. Main MCCB (ABB/LandT/SCHNEIDER - 01nos2. Controlling MCB - 01nos3.THERMAL OVER LOAD RELAY (ABB/LandT/SCHNEIDER) - 01 nos4. AUXILARY CONTACTOR (ABB/LandT/SCHNEIDER) - 03 nos5. START/STOP PUSH BUTTON (SCHNEIDER/SALZAR/SEIMENS)6. EMERGENCY SWITCH (SCHNEIDER/SALZAR/SEIMENS) - 01 nos7. DIGITAL VAF METER (SECURE/SELEC/TECHNO/ABB) - 01 nos8.CT RATIO - 100/5 (AE/KAPPA/LandT) - 01 nos9. CAPACITOR BANK AS PER LOAD REQUIREMENT10. CHANGE OVER SWITCH AS PER LOAD (SCHNEIDER/SALZAR/SEIMENS) - 01 nos11. SELECTOR SWITCH (SECURE/SELEC/TECHNO/ABB) - 01 nos12. SINGLE PHASE PREVENTER (SECURE/SELEC/TECHNO/ABB) -01 nos13. ELCB BREAKER (ABB/LandT/SCHNEIDER)1250 LPM x 20 mtr |
| 12 | PANEL BOARDS FOR MOTOR: - Supply Erection, Testing and Commissioning of wall mounted electrical LT Panel board, fabricated from SWG CRCA sheet duly stoten with suitable angle iron frame work and completely powder coated of suitable size deep having following item for 1 Non clog submercible pumping)START DELTA STARTER :- 1. Main MCCB (ABB/LandT/SCHNEIDER - 01nos2. Controlling MCB - 01nos3.THERMAL OVER LOAD RELAY (ABB/LandT/SCHNEIDER) - 01 nos4. AUXILARY CONTACTOR (ABB/LandT/SCHNEIDER) - 03 nos5. START/STOP PUSH BUTTON (SCHNEIDER/SALZAR/SEIMENS)6. EMERGENCY SWITCH (SCHNEIDER/SALZAR/SEIMENS) - 01 nos7. DIGITAL VAF METER (SECURE/SELEC/TECHNO/ABB) - 01 nos8.CT RATIO - 100/5 (AE/KAPPA/LandT) - 01 nos9. CAPACITOR BANK AS PER LOAD REQUIREMENT10. CHANGE OVER SWITCH AS PER LOAD (SCHNEIDER/SALZAR/SEIMENS) - 01 nos11. SELECTOR SWITCH (SECURE/SELEC/TECHNO/ABB) - 01 nos12. SINGLE PHASE PREVENTER (SECURE/SELEC/TECHNO/ABB) -01 nos13. ELCB BREAKER (ABB/LandT/SCHNEIDER)2200 LPM x 30 mtr |
| 13 | Operation and Maintenance for complete scope of work mentioned in the DNIT as well as all existing infrastructure during first year of defect liability period after Successful trial run |
| 14 | Operation and Maintenance during 1st year after defect liability period. |
| 15 | Operation and Maintenance during 2nd year. |
| 16 | Operation and Maintenance during 3rd year. |
| 17 | Operation and Maintenance during 4th year |
| 18 | Operation and Maintenance during 5th year |
| 19 | Item Description HSR Item |
| 20 | H.S.R. Items DNIT Name :Various Villages:- Pump House No.5, Replacement of existing pumping machinery at PumpHouse No.5, Siwani Canal for raw water arrangement for Group of 6 No. water works i.e. Mithi, Matani, Morka, Mandholi Khurd, Siwach and Garwa, Tehsil Siwani, District Bhiwani,`Supplying, erection, testing and commissioning of pumping machinery, DG Set,Transformer, and construction of pump chamber at Pump House No.5 Hariyawas, Siwani Canal Operation and Maintenance during defect liability period of 12 months after successful completion of 3 Months trial run and thereafter for 5 years and all other works contingent thereto Please Enable Macros to View BoQ information |