| 1 | PART-A 11KVline length with 40 mtr span using 55 sqmm AAA conductor & 9 mtr PSC Pole for OLIC/GAIC 9 mtr 300 kg PSC Pole |
| 2 | PSC Pole Clamp (GI) |
| 3 | Sreight Cross Arm 100x50x6mm 9.56 kg/mtr each channel (GI) length 1.2 mtr -2 nos channel (GI) requireed =(2x9.58x1.2) |
| 4 | Fan Plate (I) 50x8mm 2.36 kg/mtr each 0.280 mtr length 8 nos required =(8x2.36x0.280) |
| 5 | Sreight Cross Arm 100x50x6mm 9.56 kg/mtr each channel (GI) length 1.2 mtr -2 nos channel (GI) requireed =(2x9.58x306) |
| 6 | Danger Plate 1 no |
| 7 | Back Clamp for danger plate 25x3 mm Plate (GI) 0.59 kg/mtr Flat(GI) of 0.510 mtr length 2 nos =(2x0.50x0.510) |
| 8 | GI barbed wire anticlimbing device 3 kg per support |
| 9 | Back Clamp for danger plate 25x3 mm Plate (GI) 0.59 kg/mtr Flat(GI) of 0.510 mtr length 2 nos =(2x0.50x0.510) |
| 10 | 11 KV pin insulator polymer |
| 11 | HW fitting(B&S) 70 KN 3 bolt |
| 12 | Disc insulator (B&S) 70 KN polymer |
| 13 | Earthing of support (Coil Type) |
| 14 | No-8 GI wire (Dia 4.6mm) D 131 Kg/mtr - 2 mtr for concreting pole with coil earthing |
| 15 | WEDGE CONNECTOR FOR 55 SQMM CONDUCTOR |
| 16 | POLYCARBONATE BIRD GUARD |
| 17 | GI Nut Bolt & Washer of different sizes (3.55 kg each cut plate) |
| 18 | Black PINT (gib Numbering & Zebra stripping) |
| 19 | Yellow Colour PINT (bib Numbering & Zebra stripping) for Back ground |
| 20 | Civil & Services Concreting Ratio 1.1.5.3 (M20 Grade (500mmx500mmx500mm) 0.375 cu mtr (per pole) |
| 21 | Material for 11KV cut Point with 90 degree Angle 9 mtr 300 kg PSC Pole |
| 22 | PSC Pole Clamp (GI) |
| 23 | Sreight Cross Arm 100x50x6mm 9.56 kg/mtr each channel (GI) length 1.2 mtr -2 nos channel (GI) requireed =(2x9.58x1.2) |
| 24 | Fan Plate (I) 50x8mm 2.36 kg/mtr each 0.280 mtr length 8 nos required =(8x2.36x0.280) |
| 25 | Sreight Cross Arm 100x50x6mm 9.56 kg/mtr each channel (GI) length 1.2 mtr -2 nos channel (GI) requireed =(2x9.58x306) |
| 26 | Danger Plate 1 no |
| 27 | Back Clamp for danger plate 25x3 mm Plate (GI) 0.59 kg/mtr Flat(GI) of 0.510 mtr length 2 nos =(2x0.50x0.510) |
| 28 | GI barbed wire anticlimbing device 3 kg per support |
| 29 | Back Clamp for danger plate 25x3 mm Plate (GI) 0.59 kg/mtr Flat(GI) of 0.510 mtr length 2 nos =(2x0.50x0.510) |
| 30 | 11 KV pin insulator polymer |
| 31 | HW fitting(B&S) 70 KN 3 bolt |
| 32 | Disc insulator (B&S) 70 KN polymer |
| 33 | Earthing of support (Coil Type) |
| 34 | No-8 GI wire (Dia 4.6mm) D 131 Kg/mtr - 2 mtr for concreting pole with coil earthing |
| 35 | WEDGE CONNECTOR FOR 55 SQMM CONDUCTOR |
| 36 | POLYCARBONATE BIRD GUARD |
| 37 | HT Stay Clamp 50x8 mm Flat(GI) 3.14 kg/mtr 0.551 mtr length 2 nos qty required (1 Pair) |
| 38 | HT Stay set (Complete ) |
| 39 | HT Stay Insulator Type-C |
| 40 | 7/10 SWG stay wire 15 kg /stay |
| 41 | GI Nut Bolt & Washer of different sizes (12.291 kg each DP without AB switch) |
| 42 | Black PINT (gib Numbering & Zebra stripping) |
| 43 | Yellow Colour PINT (bib Numbering & Zebra stripping) for Back ground |
| 44 | Civil & Services Fixing of Complete 11kv line comple stay set includes 1. Turn buckle Assembly, 2. Stay rod & Stay Plate, 3. Stay Insulator , 4. Stay Wire, 5. Stay clamp with nuts & bolts BA will do the excavation including excavation, Supply of 0.5 Cum cement concrete foundation 1:2:4 size using 20mm BHG metal with all labour and material as per TPCODL Drawing standard |
| 45 | Concreting Ratio 1.1.5.3 (M20 Grade (500mmx500mmx500mm) 0.375 cu mtr (per pole) |
| 46 | Material for 11KV cut Point with 90 degree Angle 9 mtr 300 kg PSC Pole |
| 47 | PSC Pole Clamp (GI) |
| 48 | 11 KV V Cross Arm(GI) (10.2 Kg each) |
| 49 | Top Bracket 100x50x6 mm GI channel (GI) (2 kg each) |
| 50 | Danger Plate 1 nos |
| 51 | Back Clamp for danger plate 25x3 mm Plate (GI) 0.59 kg/mtr Flat(GI) of 0.510 mtr length 2 nos =(2x0.50x0.510) |
| 52 | GI barbed wire anticlimbing device 3 kg per support |
| 53 | Back Clamp for danger plate 25x3 mm Plate (GI) 0.59 kg/mtr Flat(GI) of 0.510 mtr length 2 nos =(2x0.50x0.510) |
| 54 | 11 KV pin insulator polymer |
| 55 | Earthing of support (Coil Type) |
| 56 | No-8 GI wire (Dia 4.6mm) D 131 Kg/mtr - 2 mtr for concreting pole with coil earthing |
| 57 | GI Nut Bolt & Washer of different sizes (12.291 kg each DP without AB switch) |
| 58 | 55 sqmm AAA Conductor |
| 59 | Black PINT (gib Numbering & Zebra stripping) |
| 60 | Yellow Colour PINT (bib Numbering & Zebra stripping) for Back ground |
| 61 | POLYCARBONATE BIRD GUARD |
| 62 | Civil & Services Concreting Ratio 1.1.5.3 (M20 Grade (500mmx500mmx500mm) 0.375 cu mtr (per pole) |
| 63 | PART-B LINE PROTECTING GUARDING ON SINGLE MPOLE FOR ROAD CROSSING Guarding channel |
| 64 | No-6 GI wire |
| 65 | No-8 GI wire |
| 66 | EYE Bolt (236mm 18mm dia 1.577 kg/mtr |
| 67 | GI Pipe earthing 40mm 3 mtr long |
| 68 | 50x6mm flat (GI) earthing 2.36 kg/mtr (10.7 mtr for raising) 10.7x2.36 |
| 69 | Civil & Services Construction Earthing chamber including installation of earthing pipe Making earthing chamber including excavation ,soil treatment with bentonite powder calculation of earh resistance , including installation of 3 mtr GI pipe 40mm/50mm including welding of Flat (GI) around pipe |
| 70 | MATERIAL FOR DP MOUNTED DSS 9 mtr 300 kg PSC Pole FOR DP |
| 71 | PSC Pole Clamp (GI) |
| 72 | Top channel (GI) GI 100X50X6 MM |
| 73 | Fish Plate(GI) 50x6 mm 2.36 kg/mtr ech 0.280 mtr length 6 nos required =(6x2.38x0.280) |
| 74 | AB switch Mounting channel(GI) 75x40x4.8mm 7.14 KG/mtr each channel (GI) length 3 mtr 2 nos channel (GI) requird 7.14x3x2) |
| 75 | AB switch Mounting channel(GI) 75x40x4.8mm 7.14 KG/mtr each channel (GI) length 0.35 mtr 2 nos channel (GI) requird 79.56x2x0.35) |
| 76 | Channel(GI) support channel(GI) 75x40x4.8mm 7.14 KG/mtr each channel (GI) length 3 mtr 2 nos channel (GI) requird 9.56x2x0.35) |
| 77 | HG/DD Fuse mounting channel(GI) 75x40x4.8 mm GI channel(GI) (810 mm long -2 nos) long (7.14 kg/mtr 2 nos) Each 2 x 3000x7.14=42.84 kg) |
| 78 | Centilever support channel(GI) 75x40x4.8mm 7.14 KG/mtr each channel (GI) (810 mm long -2 nos) long (7.14 kg/mtr 2 nos) Each 2 x 0.810x7.14=11.57 kg) |
| 79 | Centilever support channel(GI) 75x40x4.8mm GI (1282 mm long) 4.5kg/mtr 2 nos (Each 2 x 1.28x4.5=11.54 kg) |
| 80 | Transformer Base GI channel(GI) 100x50x6mm (3000 mm long) (9.56kg/mtr 2 nos (Each 2x3x3000x 9.56=57.36 kg) |
| 81 | Transformer Base GI channel(GI) 100x50x6mm (515 mm long) (9.56kg/mtr 2 nos (Each 2x0.515x9.56=9.85 kg) |
| 82 | Transformer Bearing support Angle(GI) 50x50x6mm GI(580 mm long)4.5 kg/mtr -2 nos) (Each 2x0.580x4.5 kg) |
| 83 | Transformer Belling support Angle(GI) 50x50x6mm GI(515 mm long)4.5 kg/mtr -2 nos (Each kg/mtr -2 nos) (Each 2x0.580x4.5 kg) |
| 84 | LTDB Mounting Angle (GI) 50x50x6mm GI(1000 mm long) 4.5 kg/mtr -2 nos (Each kg/mtr -2 nos) (Each 2x0.580x4.5 kg) |
| 85 | 50x6mm Flat(GI) for eathing 2.36 kg/mtr. For mesh formation 12 mtr for LA and 2.5 mtr For raising 11 mtr for AB switch 2.8 mtr HG Fuse 5x2 mtr for DTR Nutral, (1.3+4.5) mtr For DTR Body 0.500 mtr for LTDB & AB switch operating handle 3 mtr for Fencing) (Each 65.6x2.36=154.81 kg) |
| 86 | 25 KVA 11/0.4 KV(AL) Transformer BIS Energy Loss level II. Alluminium-4 |
| 87 | LT Distribution Box with MCCB Alluminium Busbar of singlr Bay with kit kat fuse for 25 KVA S/S |
| 88 | 55 SSQM AAAC x LPE covered conductor |
| 89 | 4 Cx35mm2 LTxLPE cable (Armoured for 25 KVA Trf. |
| 90 | AB switch (11 KV 400 A 3 pole 50 Hz) |
| 91 | HG Fuse (11 KV 200 A 3 pole) |
| 92 | WEDGE CONNECTOR FOR 55 SQMM CONDUCTOR |
| 93 | POLYCARBONATE BIRD GUARD |
| 94 | Disc insulator (B&S) 70 KN polymer |
| 95 | H.W. FITTING (B&S) 70 KN 3 bolts |
| 96 | Lighting Arrester (12 KV 10KA) Station class-2 |
| 97 | 11 KV pin ibsulator polymer |
| 98 | HT Stay set (Complete ) |
| 99 | HT Stay clamp (1.9 kg/pair) |
| 100 | HT Stay Insulator Type-C |
| 101 | 7/10 SWG stay wire 15 kg /stay |
| 102 | 40mm Nominal bore GI pipe (medium gauge earthing device with 3 mtr long |
| 103 | GI Nut Bolt of Assorted size (25 kg/DSS DP) |
| 104 | GI Barbed wire / Anticlimbing device (3 kg/Pole) |
| 105 | Back clamp for anticlimbing device 25x3 mm flat(GI) 0.59 kg/mtr flat(GI) of 0.510 mtr length 8 nos =(8x0.59x0.510) |
| 106 | Danger Plate 11 KV |
| 107 | Back Clamp for danger plate 25x3 mm Plate (GI) 0.59 kg/mtr Flat(GI) of 0.510 mtr length 2 nos =(2x0.50x0.510) |
| 108 | Name Plate |
| 109 | Structure Numbering and Marking Yellow Colour PAINT (GIS Numbering & Zebra stripping) for Back ground |
| 110 | Black Colour Paint (GIS Numbering & Zebra stripping) |
| 111 | Civil & Services Concreting ratio 1.153(M 20 Grade) (500mmx500mmx667mm)=0.45 Cu mtr(Per Pole) |
| 112 | PCC 1:3:6 |
| 113 | Fixing of stay set with 0.5 cum cement concrete foundation 1:3:6) (M-10 Grade) size 900mmx600mmx900mm )using 40mm BHG metal with all labur and materials except stay set, stay wire ,stay insulator |
| 114 | Construction Earthing chamber including installation of earthing pipe Making earthing chamber including excavation ,soil treatment with bentonite powder calculation of earh resistance , including installation of 3 mtr GI pipe 40mm/50mm including welding of Flat (GI) around pipe |
| 115 | Laying of 4 C x 35 mm2 x LPE Cable |
| 116 | SITC and Errection of GI Fencing with Gate |
| 117 | Supply of AL Lugs suitable for 35 sqmm cable/conductor ,climbing with cable and fixing/concreting include supply and errection of PVC Taps as per voltage requiremnt . |
| 118 | Supply and errection of double Compression Flameproof Type Glanding for armoured Cab,e 3.5/4C 16-35 sqmm including making hole in Base plate and dressing of cable along with vermin. Supply to be done as per TPCODL Spae and approved make dowells. Please Enable Macros to View BoQ information |