| 1 | Supplying, laying, jointing, testing and connecting in replacement of XLPE insulated PVC outer seathed and (earthed) PVC inner sheath, galvanised steel strip or wire armoured, electric power cable (heavy duty) with aluminum conductors, 11 KV(E) grade and conforming to IS : 7098 and, of size 150 sqmm, 3 core, laid in trenches / ducts / encased in GI pipe / fixed to pole, complete all as specified and directed by Engr-in-charges. Note : Earth work, protection pipe and Cable Joints etc shall be measured and paid separately. |
| 2 | Supply and fixing in replacement of GI Pipe light grade 80 mm dia with necessary accessories/ fittings bracing with pole/wall by FI clamps made with 32x6mm for cable protections/pole for crossing of culverts/nallah/road and complete all as specified and directed by Engr-in-charges. |
| 3 | M&L for Cutting the road / hard standings and excavating in trenches not exceding 0.40 mtr wide and not exc 0.80 mtr deep across the road for laying cable including making good the excavated portion by means of PCC 1:2:4, type B1 using 20mm graded stone aggregate complete all as specified and directed by Engr-in-charges. |
| 4 | Material and labour plain cement concrete (1:3:6) type C-2 using 40 mm graded stone aggregate as in base of the pole or in any situation complete all as specified and directed by Engr-in-charges. |
| 5 | Material and labour plain cement concrete (1:2:4) type B-1 using 20 mm graded stone aggregate as in coping of the pole or in any situation including necessary form work complete all as specified and directed by Engr-in-charges. |
| 6 | Excavation in trenches in any type of soil not exc 1.5 mtr in depth and 1.5 mtr wide and getting out for laying of cables. complete all as specified and directed by Engr-in-charges. |
| 7 | All as per ser No-6 above but depth exc 1.5 mtr but not exc 3.00 mtr complete all as specified and directed by Engr-in-charges. |
| 8 | M&L for tibba sand filling in trenches dry and and clean sand unwashed including punning around cable for protection of under ground cable complete all as specified and directed by Engr-in-charges. Note :- Only punned thickness will be measured for payment purpose. |
| 9 | M&L for laying jodhpur stone quarry stone slab cover 25 to 30cm in width, 60cm long and 40 to 50 mm thick laid in trenches and abutting each other with gap between adjacent slab not exceeding 10mm over sand covered under ground cables complete all as specified and directed by Engr-in-charge. |
| 10 | Returning and filling in including spreading, leveling , watering and well ramming in layers not exceeding 25 cm thick of excavated earth complete all as specified and directed by Engr-in-charges. |
| 11 | Removal of surplus soil to a distance not exceeding 50 mtr and depositing at a leval not exceeding 1.5 mtrs above the starting point complete all as specified and directed by Engr-in-charges. |
| 12 | Supply and fixing the HT Cable route indicator made by Jodhpur stone well finished and marking of letter \\"DANGER HT 11KV\\", size 100mmx100mm, 75cm long, 15cm grouted with 1:3:6 PCC foundation below the ground level and 60cm of marker will be elevated on ground the embossed letters of \\"DANGER HT 11 KV\\" will be painted with post office red colour and with black colour background and complete all as specified and directed by Engr-in-charges. |
| 13 | Supply and fix Cable jointing kit for 33 KV (Earthed) grade cable for outdoor termination heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured Aluminium conductor cable of size 95 Sqmm to 120 Sqmm complete all as specified and directed by Engr-in-charges. |
| 14 | All as per Ser No 13 above but suitable for 3 core 240-300 sqmm cable complete all as specified and directed by Engr-in-charges. |
| 15 | Supply and fix outdoor type heat shrinkable end termination cable joint kit including all material and accessories suitable for 3 core 95 sqmm XLPE armoured aluminium conductor cable of 11000 Volt grade all as per manufactuer recommendation complete all as specified and directed by Engr-in-charges. |
| 16 | All as per Ser No 15 above but suitable for 3 core 120 sqmm cable complete all as specified and directed by Engr-in-charges. |
| 17 | All as per Ser No 15 above but suitable for 3 core 150 sqmm cable complete all as specified and directed by Engr-in-charges. |
| 18 | All as per Ser No 15 above but suitable for 3 core 185 sqmm cable complete all as specified and directed by Engr-in-charges. |
| 19 | Supply and fix straight through heat shrinkable cable joint kit including all material and accessories suitable for 3 core 95 sqmm XLPE armoured aluminium conductor cable of 11000 Volt grade all as per manufactuer recommendation complete all as specified and directed by Engr-in-charges. |
| 20 | All as per Ser No 19 above but suitable for 3 core 120 sqmm cable complete all as specified and directed by Engr-in-charges. |
| 21 | All as per Ser No 19 above but suitable for 3 core 150 sqmm cable complete all as specified and directed by Engr-in-charges. |
| 22 | All as per Ser No 19 above but suitable for 3 core 185 sqmm cable complete all as specified and directed by Engr-in-charges. Please Enable Macros to View BoQ information |
| 23 | All as per Ser No 19 above but suitable for 3 core 185 sqmm cable complete all as specified and directed by Engr-in-charges. Please Enable Macros to View BoQ information |