| 1 | Dismantling cross-arms of M.S channel or angle sections etc. complete all as specified and directed. |
| 2 | Dismantling old insulator complete all as specified and directed. |
| 3 | Dismantling stay assembly complete.(demolition of concrete, etc. and excavationmeasured separately) |
| 4 | Dismantling of old un-serviceable ACSR conductor of any size and make from LT over head line complete all as specified and directed. |
| 5 | Taking out the existing RCC pole carefully with removing electric connection including earth work and dismantling of PCC pole all as specified and directed by the Engr-in- charge |
| 6 | Excavating in trenches not exceeding 1.5m wide and not exceeding 1.5 m in depth for foundation of pole,laying of cables etc in Hard and dense soil and getting out. |
| 7 | Excavating in trenches not exceeding 1.5m wide and exceeding 1.5 m but not exceeding 3.00m in depth for foundation of pole, laying of cables etc in hard/dense soil and getting out. |
| 8 | Returning filling in including spreading, leveling, watering and well ramming in layer not exc 25 cm. |
| 9 | Removing excavated material not exc 50 mtr and depositing where directed at a level not exc. 1.5 m above the starting point. |
| 10 | M&L for providing dry river sand as in sand cushioning to UG cable including punning gently all as directed. Note : Depth after punning shall be measured and paid. |
| 11 | M&L for plain cement concrete 1:4:8 type D-2 using 40mm graded stone aggregate in foundation of PCC poles/struts all as specified and directed. |
| 12 | M&L for plain cement concrete 1:3:6 type C-2 using 40mm graded stone aggregate in foundtion of pole/stay assembly etc including necessary form work, all as specified and directed. |
| 13 | M&L for plain cement concrete 1:2:4 type B-1 using 20mm graded stone aggregate for padestal/coping around poles, including necessary form work, finishing even and smooth without using extra cement, all as specified and directed. |
| 14 | Supply and laying sub class old 'B' burnt bricks laid as cable protection cover complete all as specified and directed. |
| 15 | M&L for steel tubular swaged poles complete with cast iron base plate, finial taper plug, bolts, nuts and screws, type 410 SP-31 (09 Mtr long) including two coats of bituminous paint internally and externally for the portion embedded in concrete and two coats of aluminium paint over one coat of red oxide primer to external/exposed surfaces complete all as specified and directed . Note:- (i) Excavation/PCC will be measured and paid separately under relevant items (ii) writing letters pole no and figures in white enamel of black Roman, Italic or Indian of 10 cm height including circular back ground with black enamel paint of two coats incl white circular border over steel |
| 16 | Supply and fix LT junction box for street light, FRP type with hinged type door and locking arrangement, off white colour, of size 300 x 200 x 105mm (internal) comprising of suitable size Aluminium busbar 3 rows with terminals,1 No bakelite base neutral link and 01 No earthing terminal bolt and nut and connecting up cables with aluminium terminal lugs all as specified and as directed . |
| 17 | Supply and fixing LED street light fitting 70 Watt 230 V AC outdoor type with high pressure diecast aluminum hosing and heat resistant including taking dowo old complete with driver, lamp bracket with impactand corrosion resistant including thermalmanagement in multiple optics complete withIP 66 protection complete |
| 18 | Supplying & laying, XLPE insulated PVC inner sheathed, 6 Sqmm, 2 core, armoured with galvanised steel strip or wire heavy duty underground cable with aluminium multi stranded conductor, 1100 volt grade, laid in trenches/duct, passing through pipe/duct or fixed on pole and connecting and testing complete all as specified and directed. |
| 19 | All as per item No 18 above but cable of size 10 sqmm 2 core . |
| 20 | All as per item No 19 above but cable of size 10 sqmm 4 core . |
| 21 | All as per item No 19 above but cable of size 16 sqmm 4 core . |
| 22 | All as per item No 19 above but cable of size 35 sqmm 3.5 core |
| 23 | All as per item No 19 above but cable of size 50 sqmm 3.5 core |
| 24 | S&F, in repair, FRP insulated and PVC sheathed copper conductor cable of size 1.5 Sqmm, 3 core, 1100 volts grade, multistranded, passing throuth existing pipe, fixed on pole/wall from juntion box to street light fitting complete all as specified and directed. including taking down old |
| 25 | Supply, installation, commissoning and testing, in repair, feeder pillar board, Kiosk type, LT(415 Volts, 50 Hz , 3-phase, 4 wire supply) plinth mounted, factory made, compartment type,outdoor type, weather and vermin proof (Protection Class IP-54) made out of 50m x 50mm x 5mm angle iron frame and 3.15 mm thick MS Sheet CRCA sheet powder coated with front & back hinged opening, rubber lining, locking arrangement, painted externally and internally with two coats of synthetic enemell gray paint (First Quality) over a coat of red oxide primer, grouting panel through angle iron 0.45 mtr in ground and 0.3 mtr over the ground including excavation & earth work in any type of soil and PCC (1:3:6) type C-2 using 40mm graded stone aggregate complete comprising of the followings:- (a) Incoming supply:- (i) Aluminium bus bar chamber 300 amps rating of 04 strip - 01 No (ii) MCCB, thermal and meganitic setting, 4 pole AC 415volts, 160 Amp rating, 35 KA rupturing capacity - 01 No (iii) Digital type voltmenter 0-500 V with selector switches - 01No (iv) Digital type Amp meter 0-300A with selecter switch with CT ratio 400/5A - 01 No (v) Indicatiing lamp Neon type for R-Y-B - 3 Nos (b) Outgoing supply:- (i) MCCB, thermal and meganitic setting, 4 pole AC 415volts, 125 Amp rating, 25 KA rupturing capacity - 02 No. (iii) MCCB, thermal and meganitic setting, 4 pole AC 415volts, 100 Amp rating, 25 KA rupturing capacity - 03No. (iv) Time switch, single phase, 230 volts with 24 hours time setting, current rating 16 Amps and with AC relay type ML-3 and with MCB TPN, C curve 32 Amp, three phase including internal connections - 02 Nos. (v) MCB SPN, C-curve, 32 Amps, AC 230 Volt - 03 No including internal connections |
| 26 | M&L, earthing complete with galvanized steel earth plate electrode of 60 cm x 60 cm x 6mm thick buried directly in ground [earth pit not less than 2.25 metre deep below normal ground level] with top edge of the plate not less than 1.5 m below normal ground level, connected to galvanized earth strip of 25x4 mm by means of bolts, nuts, check nuts and washers of galvanized iron or steel all as shown in electrical plate No. 3 of MES SSR Part I connected to earth test point using earth strip of 32X6mm as earth lead all as specified and testing on completion including provision of earth lead protected by 40 mm dia light grade GI pipe & watering pipe shall be 20 mm bore medium grade GI pipe including all excavation and earth work in any type of soil, PCC pit with RCC cover, char coal, salt, funnel etc complete. |
| 27 | S&F, in repair, GI pipe, 50mm bore, light grade, laid below road/fixed along the poles / walls with necessary clamping,,including taking down old etc complete all as per specified and directed. |
| 28 | S&F, in repair, GI pipe, 40mm bore, light grade, laid below road/fixed along the poles / walls with necessary clamping,including taking down old etc complete all as per specified and directed. |
| 29 | S&F, in repairs, bracket made out of light grade, Galvanised steel tube, 35mm bore, 1.2 Mtr length, bent to 120 degree for fixing street light fitting at the top, fixed to pole with necessary clamps made out of FI 40mm x 4mm with nuts & bolts including preparation of steel surfaces & apply two coat of synthetic enamel paint over red oxide prime rincluding taking dowo old complete all as specified and directed. |
| 30 | Dismantling old unserviceable Steel poles/Rcc poles/struts, any size complete all as specified and directed. |
| 31 | Taking out sub class burnt bricks from the trenches and stacking at site serviceable /unserviceable bricks for reuse. |
| 32 | Laying only sub class brunt bricks as cable protection cover all as directed. |
| 33 | Supply and laying sub class old 'B' burnt bricks laid as cable protection cover complete all as specified and directed. |
| 34 | Supply and fix LT junction box for street light, FRP type with hinged type door and locking arrangement, off white colour, of size 300 x 200 x 105mm (internal) comprising of suitable size Aluminium busbar 3 rows with terminals,1 No bakelite base neutral link and 01 No earthing terminal bolt and nut and connecting up cables with aluminium terminal lugs all as specified and as directed . |
| 35 | Taking out and relaying the existing PVC/XLPE, 1100 volts grade, LT UG electric cable of size 6/10 sqmm x 2 ,4 core with glands, cable protection pipes etc., complete from the trenches/fixed on wall removing the unserviceable fault cable and carefully stacking the serviceable cable for reusing all as specified and directed by the Engr-in- charge Note:- Excavation and Earth work shall be measured and paid separately under appropriate items all as per existing make |
| 36 | Supply and fixing LED street light fitting 45 Watt 230 V AC outdoor type with high pressure diecast aluminum hosing and heat resistant including taking dowo old complete with driver, lamp bracket with impactand corrosion resistant including thermalmanagement in multiple optics complete withIP 66 protection complete |
| 37 | S&F, in repairs, bracket made out of light grade, Galvanised steel tube, 35mm bore, 1.2 Mtr length, bent to 120 degree for fixing street light fitting at the top, fixed to pole with necessary clamps made out of FI 40mm x 4mm with nuts & bolts including preparation of steel surfaces & apply two coat of synthetic enamel paint over red oxide prime rincluding taking dowo old complete all as specified and directed. |
| 38 | S&F, in repair, FRP insulated and PVC sheathed copper conductor cable of size 1.5 Sqmm, 3 core, 1100 volts grade, multistranded, passing throuth existing pipe, fixed on pole/wall from juntion box to street light fitting complete all as specified and directed. including taking down old Please Enable Macros to View BoQ information |