| 1 | Supplying of following sizes of PVC insulated & PVC sheathed /XLPE steel armoured aluminum conductor power cable of 1.1KV grade etc complete as reqd. |
| 2 | 4 x 16 Sq. mm. |
| 3 | 3.5 x 25 sq. mm |
| 4 | Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size direct in ground including excavation, sand cushioning, protective covering and refilling the trench etc as required. |
| 5 | Upto 35 sq. mm |
| 6 | Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size in the existing RCC/ HUME/ METAL pipe as required. |
| 7 | Upto 35 sq. mm |
| 8 | Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size on wall surface as required. |
| 9 | Upto 35 sq. mm (clamped with 1mm thick saddle) |
| 10 | Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required. |
| 11 | 4 x 16 Sq. mm. |
| 12 | 3.5 x 25 sq. mm |
| 13 | Supplying and making straight through joint with heat shrinkable kit including ferrules and other jointing materials for for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required. |
| 14 | 4 x 16 Sq. mm. |
| 15 | 3.5 x 25 sq. mm |
| 16 | 4 x 35 Sq. mm (including upto 50 sq.mm) |
| 17 | SITC of outdoor-type wall mounted electricity meter box, (nominal size: 420mm W x 550mm H x 240mm D) conforming to IP 55 standards, fabricated of 18 SWG (1.2mm) CRCA MS sheet pre-treated via seven-tank hot phosphating process followed by corrosion-resistant powder-coated finish from all sides, double-door arrangement with concealed hinges, EPDM sealing gaskets, viewing window with 5mm toughened glass, screened air louvers, locking facility, MV danger notice, complete with internal DIN rail mounting and earthing arrangements as per GED approved specifications, including transportation, handling, meter shifting, wiring connections, co-ordinating with GED for supply connection, etc. The Panel shall include following features:1) Sloping rain canopy with projections: sides - 50 mm, rear - 25 mm, front - 100 mm, with drip edge, beyond doorline for effective rain water protection of door seals, hinges, etc.2) Heavy-duty MS mounting brackets to ensure a minimum 38mm clearance from the wall surface, fixed using 304-grade Stainless Steel (SS) expansion bolts. 3) Provided with internal 35mm x 7.5mm pre-slotted DIN rail (200 mm length) |
| 18 | Supplying and fixing 5 amps to 32 amps rating, 240/415 volts, \\"C\\" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. |
| 19 | Triple pole |
| 20 | Providing and fixing 25 mm X 5 mm G.I. strip on surface or in recess for connections etc. as required. |
| 21 | Connection with Copper link, with Single Core FRLS Copper PVC Insulated Flexible Cable for voltage grade upto 1100V with copper lug on both end having length approx 0.5 mtr. of 10 Sq.mm size including testing commisioning etc. as required. |
| 22 | Providing and fixing of 63 Amp capacity TP&N disconnector fuse switch unit inside the existing panel board with ISI marked HRC fuses including drilling holes in cubicle panel, making connections, etc. as required. |
| 23 | Earthing with G.I. earth plate 600 mm X 600 mm X 6 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal/ coke and salt as required. |
| 24 | Providing and laying of 40mm dia medium class G.I. pipe in ground complete with G.I. fittings incl trenching and refilling etc as reqd |
| 25 | Providing and laying 100 mm dia G.I. pipe (medium class) in ground complete with G.I. fittings including trenching and re-filling etc as required Please Enable Macros to View BoQ information |