| 1 | Supply & Earthing Requisites for X Ray Unit |
| 2 | 2.2.1:Providing and fixing following rating and breaking capacity MCCB withthermomagnetic release and terminal spreaders in existing cubicle panel boardincluding drilling holes in cubicle panel. making connections. etc. as required.100 A, 16KA |
| 3 | OD11216/2026-2027:Supplying and fixing following rating, four pole, (three phase and neutral), 415volts, residual current circuit breaker (RCCB), having a sensitivity current 30milli Amperes in the existing MCB DB complete with connections, testing andcommissioning etc. as required.100 amps |
| 4 | 2.13.3:Supplying and fixing following rating, four pole, 415 volts, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required.100 amps |
| 5 | 2.4.1:Supplying and fixing following way, horizontal type three pole and neutral, sheet steel, MCB distribution board, 415 volts, on surface / recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator)4 Way (4+12) Double door |
| 6 | 90.12.7.28:Supply, laying and clamping of 1 no. PVC insulated and PVC sheathed armoured aluminium power cable, 1.1 KV grade of the following sizes using clamps noted along with the cables, spacing of clamps not exceeding 60cms, making good the damages , colour washing etc. as required.3.5 core 35 sq mm with factory made clamp |
| 7 | 9.1.21:Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.3 1/2X 35 sq. mm (32mm) |
| 8 | 5.2:Earthing with G.I. earth pipe 4.5 metre long, 40 mm dia including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe etc.(but without charcoal/ coke and salt) as required |
| 9 | 90.16.1.6:Supply and drawing bare earthing conductors of the following sizes along with wiring/ cables and giving connection as required6.00 mm copper conductor (4 SWG) |
| 10 | 5.14:Providing and fixing 25 mm X 5 mm copper strip on surface or in recess for connections etc. as required. |
| 11 | Plug points |
| 12 | 1.21.1:Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/ recess including cutting the wall and making good the same in case of recessed conduit as required.20 mm |
| 13 | 1.17.3:Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.3 X 1.5 sq.mm |
| 14 | 1.17.12:Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.3 x 2.5 sq. mm |
| 15 | 1.23.1:Supplying and fixing following piano type switch / socket on the existing switch box/ cover including connections etc. as required.5/6 amps switch |
| 16 | 1.23.4:Supplying and fixing following piano type switch / socket on the existing switch box/ cover including connections etc. as required.3 pin 5/6 amp socket outlet |
| 17 | 1.23.3:Supplying and fixing following piano type switch / socket on the existing switch box/ cover including connections etc. as required.15/16 amp switch |
| 18 | 1.23.5:Supplying and fixing following piano type switch / socket on the existing switch box/ cover including connections etc. as required.6 pin 15/16 amp socket outlet |
| 19 | OD29420/2026-2027:Supplying and fixing following size/ modules, surface type PVC/Polycarbonate gang box along with cover plate for modular switches in recess as required.12 Module (200mmX150mm) |
| 20 | OD29426/2026-2027:Supplying and fixing following size/ modules, surface type PVC/Polycarbonate gang box along with cover plate for modular switches in recess as required.6 Module (200mmX75mm) |
| 21 | Electrical Inspectorate Charges |
| 22 | OD21911/2026-2027:Preparation and submission of all necessary drawings and documents to the Electrical Inspectorate for obtaining scheme approval and equipment energization clearance, including payment of all applicable statutory charges. Please Enable Macros to View BoQ information |