| 1 | S&F in replacement sheet metal enclosures 240 volt with suitable rated bus bar for double door IP-43 DB's suitable for one MCB SPN as incoming and 6 MCB SP as out going SPN 8 way complete incl dismentaling of unservceable DB complete all as specified and directed. |
| 2 | S&F in replacement sheet metal enclosures 240 volt with suitable rated bus bar for double door IP-43 DB's suitable for one MCB SPN as incoming and 10 MCB SP as out going SPN 12 way complete incl dismentaling of unservceable DB complete all as specified and directed. |
| 3 | S&F replacement sheet metal enclosures 415 volt TPN 4 way with 200 Amp rated bus bar, double door IP-43 DB's suitable for one No 63 to 100 Amp 10 KA TPN MCCB as incoming complete incl dismentaling of unservceable DB all as specified and directed by Engr-in-charge. |
| 4 | Supply and Fix in replacement 240V,10KA , MCB Single pole\\"B\\" series and current carrying capacity 6-32 Amps ISI marked incl dismantaling old unserviceable MCB SP . |
| 5 | Supply and Fix in replacement MCB Single pole & neutral \\"C\\" series upto 63. Amps ISI marked incl dismantaling old unserviceable MCB SPN complete all as specified and directed. |
| 6 | Supply and fixing in replacement MCB TPN C Curve 100 Amp,415 V Make incl disntaling of old unserviceable TPN MCB complete all as specified and directed. |
| 7 | Supply and fixing in replacement MCB TPN C Curve 63 Amps 415V Make incl disntaling of old unserviceable TPN MCB complete all as specified and directed. |
| 8 | Supply and fixing in replacement MCB TP C Curve 63 Amps 415 V Make incl dismantaling of old unserviceable TP MCB complete all as specified and directed. |
| 9 | M&L in repairs sub main wiring with PVC insulated and unsheathed 4x 6.0 Sq mm single core multistrandred copper conductor cable(FRLS) passing through in and including PVC conduit (25MM) surface on walls with all required accesries of conduit ISI marked and conduit accessaries fixed on surface of wall, ceiling etc, making good the distrurbed surface, incl 6 Sq mm single core copper conductor cable PVC insulated and unsheathed as earth wire. Note :- four runs of cable 6 Sqmm (FRLS) and One run of 6 Sqmm copper conductor(FRLS) along with conduit shall be measured as one unit length including taking down old UNSV submain wiring complete all as specified and directed. |
| 10 | M & L in replacement Earthing complete with galvanised steel earth plate electrode 60 x x60cm x 6 mm thick, buried directly in ground (earth pit not less than 2.25 metres deep below ground level) wih top edge of the plate not less than 1.5 metres below normal/hard/dense ground level, connected to galvanised earth lead wire 4.0mm dia by means of bolts, nuts, check nuts and washers of galvanised iron or steel all as shown in elevtrical plate No. 3 connected to earthing test point all as specified or indicated including testing on completion . Note : Rates are deemed to be included for necessary earth work , earth pit with RCC cover of size 300X300 x25 mm etc complete all as specified and directed. |
| 11 | M&L for Earthing complete with Chemical earthing with copper earth plate 90x60cmx5mm & copper earth strip 32x6 mm strip, buried directly in ground (earth pit not less than 2.25 metres deep below ground level) with top edge of the plate not less than 1.5 metres below normal ground level, connected to copper earth strip 50x6mm strip means of bolts, nuts, check nuts and washers of copper all as shown in electrical plate No. 3 connected to earthing test point all as specified or indicated including testing on completion, Note : Rates are deemed to be included for necessary earth work, earth pit with RCC cover of size 300X300x25mm etc., complete all as specifed and as directed. |
| 12 | Supply and fix copper strip 20 x 3.15mm with saddles and fixing screws, insulators rawal plugs etc for conductor for roof and fixed on wall upto test point complete all as specified and directed. . |
| 13 | M&L in repairs sub main wiring with PVC insulated and unsheathed 2x 4 Sq mm single core multistrandred copper conductor cable(FRLS) passing through in and including PVC conduit (25 MM) surface on walls with all required accesries of conduit ISI marked and conduit accessaries fixed on surface of wall, ceiling etc, making good the distrurbed surface, incl 4 Sq mm single core copper conductor cable PVC insulated and unsheathed as earth wire. Note :- Two runs of cable 4 Sqmm (FRLS) and One run of 4 Sqmm copper conductor(FRLS) along with conduit shall be measured as one unit length including taking down old UNSV submain wiring complete all as specified and directed. |
| 14 | M&L in repairs sub main wiring with PVC insulated and unsheathed 2x 6 Sq mm single core multistrandred copper conductor cable(FRLS) passing through in and including PVC conduit (25 MM) surface on walls with all required accesries of conduit ISI marked and conduit accessaries fixed on surface of wall, ceiling etc, making good the distrurbed surface, incl 6 Sq mm single core copper conductor cable PVC insulated and unsheathed as earth wire. Note :- Two runs of cable 6 Sqmm (FRLS) and One run of 6 Sqmm copper conductor(FRLS) along with conduit shall be measured as one unit length including taking down old UNSV submain wiring complete all as specified and directed. |
| 15 | M&L in repairs sub main wiring with PVC insulated and unsheathed 4x 10 Sq mm single core multistrandred copper conductor cable(FRLS) passing through in and including PVC conduit (25 MM) surface on walls with all required accesries of conduit ISI marked and conduit accessaries fixed on surface of wall, ceiling etc, making good the distrurbed surface, incl 4 Sq mm single core copper conductor cable PVC insulated and unsheathed as earth wire. Note :- four runs of cable 10 Sqmm (FRLS) and One run of 10 Sqmm copper conductor(FRLS) along with conduit shall be measured as one unit length including taking down old UNSV submain wiring complete all as specified and directed. Please Enable Macros to View BoQ information |
| 16 | M&L in repairs sub main wiring with PVC insulated and unsheathed 4x 10 Sq mm single core multistrandred copper conductor cable(FRLS) passing through in and including PVC conduit (25 MM) surface on walls with all required accesries of conduit ISI marked and conduit accessaries fixed on surface of wall, ceiling etc, making good the distrurbed surface, incl 4 Sq mm single core copper conductor cable PVC insulated and unsheathed as earth wire. Note :- four runs of cable 10 Sqmm (FRLS) and One run of 10 Sqmm copper conductor(FRLS) along with conduit shall be measured as one unit length including taking down old UNSV submain wiring complete all as specified and directed. Please Enable Macros to View BoQ information |