| 1 | S&F in replacement of aluminium bus bar PVC insulated in RED,yellow,Blue & Black colours of rating 400 Amps complete all as specified and as directed. |
| 2 | S&F in replacement of aluminium bus bar PVC insulated in RED,yellow,Blue & Black colours of rating 600 Amps complete all as specified and as directed. |
| 3 | S&F in replacement of insulator of appropriate size with existing one complete all as directed by Engr-in-Charge |
| 4 | M&L taking down shutdown the LT panel and disconnecting the power cable for necessary repair and servcing of ACB 630Amps including necessary spare parts and testing complete including all as specified and directed. |
| 5 | S&F in replacement of Junction feeder Panel enclousure suitable for single MCCB for CRCA sheet, CPRI approved IP-54 duly painted with epoxy based powder coated paint, including base channel, of size 600x600x450 mm incl fixing of 630Amps MCCB 4 pole 50KA suitable for out door type double door locking arrangement comprising of its accessories, cable gland with hinged door, bus chamber with bolted double door etc dust & vermin proof construction attractive powder coated fixed/groutning on PCC foundation 45cm above ground level including all necessary excavation complete all as specified and directed. |
| 6 | S&F in replacement of Junction feeder Panel enclousure suitable for single MCCB for CRCA sheet, CPRI approved IP-54 duly painted with epoxy based powder coated paint, including base channel, of size 600x600x450 mm incl fixing of 250Amps MCCB 4 pole 50KA suitable for out door type double door locking arrangement comprising of its accessories, cable gland with hinged door, bus chamber with bolted double door etc dust & vermin proof construction attractive powder coated fixed/groutning on PCC foundation 45cm above ground level including all necessary excavation complete all as specified and directed. |
| 7 | Disconnecting & Taking out old U/S joints & Supplying, Fixing, Jointing & testing for provision of end termination joint Kits, heat shrinkable eppoxy tube with epoxy jointning materials suitable for XLPE ,LT Cable 1100 Volts grade indoor , for size 240sqmm to 400sqmm 3.5Core all as specified and directed by engr-in- Charge. (Make;- M.SEAL/DENSON/Raychem) |
| 8 | S&F in replacement of digital Multifunctional meter as per matching to existing including all accessories and wiring complete all as specified and as directed. Make:- AE/L&T. |
| 9 | S&F in replacement of power factor meter digital type for frequency range (45-65 Hz) as per matching to existing one including all accessories and wiring complete all as specified and as directed. Make:- AE/L&T. |
| 10 | M&L for dismantling old LT APFC panel and supply, installation, testing & commissioning floor mounted compartmentewise factory made Indoor cubical LT APFC panel made of 2.0 mm thick CRCA sheet with aluminium bus bar suitable for 500 Amp, CPRI approved duly painted with epoxy based powder coated paint, including base channel, inter connection control wiring name plate for each switch gears, danger plate, earth bus bar as per IS 5039. comprising of compartments for 250 KVAR (50+50+25+25+25+25+25+10+10+5) in shape of round capacitors and its accessories, cable gland with hinged door, bus bar chamber with bolted door etc dust & vermin proof construction attractive powder coated complete all as specified and as directed. Note:- supply and fixing Switchgears/ Capacitors/Contactors/Relay connected accessories and other required accessories will be paid seperately. |
| 11 | (a) MCCB 500Amps 3Pole 36KA fixed type DN3- 6300 |
| 12 | (b)Spreaders -1 No |
| 13 | (c ) APFC Relay 11 Stages -1 No |
| 14 | (d) DIGITAL MultiMeter inbuilt Selector Switches -1 No |
| 15 | (e ) LED Red,Yelow, Blue Indicator Set -1 No |
| 16 | (f) A/M Switch - 11 Nos |
| 17 | (g) LED Indicating Lights - 11 Nos |
| 18 | (h) Capcitor Banks MPP-H 10 KVAR Round Type - 03 Nos |
| 19 | (i) Capcitor Banks MPP-H 25 KVAR Round Type 08Nos |
| 20 | (j) Capacitor Duty Contactor MO 12.5 - 03Nos |
| 21 | (k) Capacitor Duty Contactor MO C25 - 08 Nos |
| 22 | (l) MCB 25A 3P, 10KA - 03 Nos |
| 23 | (m) MCB 63A 3P, 10KA - 08 Nos |
| 24 | Supply & Fixing in replacement of installation, testing and commissioning factory made, floor mounted outdoor type LT panel board suitable for 415 Volts, 3 Phase, 4 wire, 50 Hz, AC supply system, CPRI approved manufactures having bus bar chamber with insulated Aluminium bus bar 400Amp rated, four wire system, colour coded for each phase of rating as per under for phase and neutral, insulated on epoxy type insulators. The panel shall be dust and vermin proof, IP-54 class protection and made 3.15 mm of outer body and inner body 2.00 mm thick CRCA MS sheet , powder coated finish over one coat of red oxide primer on outside surface and painted inside with two coats of red oxide primer, both side opening type, including internal wiring with PVC insulated solid copper conductor cable, IS-694 marked, 1100 volts grade of appropriate size (but not less than 2.5 sqmm) including grouting of panel 30 cm above ground level by providing 60 cm long angle iron frame of size 40x40x5mm, welded on all the four corners, embedded in pcc 1:2:4 using 20 mm stone aggregate upto 30 cm complete all as specified and directed including the following accessories:- (Make :- CPRI Approved) (a) MCCB Thermal magnetic based 200Amps 4 pole , 35 KA, 415 Volt (Incomer) - 01 No(b) MCCB Thermal magnetic based 63Amps 4 pole ,25 KA, 415 Volt (Ougoing) - 04 Nos(c) MCB TPN 40 Amps \\"C\\" Curve breaking capacity 10KA - 02Nos(d) Digital Ammeter with CT's and Selector switch-01 Set(e) Digital Voltmeter with selector switches - 01Nos(f) Digital Multifuntional Meter with selector switches - 01No(g) Indicating lamp LED Type-RYB-01 Set |
| 25 | S&F in replacement of Junction box SMC KIOSK box water proof IP-54 of size 140x140x95 mm incl fixing of terminal connector 100A 4 pole suitable for in and out connection of 3 core 2.5sqmm cable fixed to termination box to ligt fittings complete. Make : HENSEL/SYNTEX |
| 26 | Supply and Repair/Replacement of Laying in trenches or passing through pipe, 120 Sqmm 3.5 core LT XLPE cable with stranded aluminium conductor heavy duth for 1100 volts grade cross sectional area complete all as specified and as directed. |
| 27 | Supply and Repair/Replacement for 250 AMP MCCB, 4 pole 415 volt, AC 50 Hz, 4 pole, 25 KA with adjustable type against over load and short circuit conditions incl neutral adjustment of capacity suitable of Existing panel board for replace of unserviseble MCCB complete all as specified and directed. Make : Havells/ Legrand/L&T/C&S |
| 28 | Supply and Repair/Replacement for 200 AMP MCCB, 4 pole 415 volt, AC 50 Hz, 4 pole, 25 KA with adjustable type against over load and short circuit conditions incl neutral adjustment of capacity suitable of Existing panel board for replace of unserviseble MCCB complete all as specified and directed. Make : Havells/ Legrand/L&T/C&S |
| 29 | Supply and Repair/Replacement for 63 AMP MCCB, 4 pole 415 volt, AC 50 Hz, 4 pole, 25 KA with adjustabletypeagainst over load and short circuit conditions incl neutral adjustment of capacity suitable of Existing panel board for replace of unserviseble MCCB complete all as specified and directed. Make : Havells/ Legrand/L&T/C&S |
| 30 | M&L in Replacement earthing complete with galvanized steel earth plate electrode of size 600 x 600 x 6 mm thick buried directly in ground to a depth not less than 2.25 mtr below the normal ground level with top edge of earth plate not less than 1.50 mtr below the normal ground level and connected to GI strips 25 x 4 mm by means of nut, bolt & washer and protected by 40mm dia GI pipe light grade and watering pipe of 20mm dia GI pipes light grade and connected to earth test point including necessary excavation, earth work, PCC chamber (1:3:6) type C-1 and 40 mm thick RCC pit cover in RCC (1:2:4) type B-1 using 6 mm dia MS round bars @ 150 mm C/C both ways all as shown in electrical plate No. 3 of SSR Part-I all as specified and directed. |
| 31 | M&L for Cement Concrete 1:4:8 (40mm Graded Stone Aggregate) as in Foundation of Panel, etc. including Formwork (as/if required), complete all as specified and as directed. |
| 32 | Supply and Repair/Replacement of 300Watt flood light Energy saving, environmental friendly, long life, exclusive innovative die-cast aluminium IP66 flood light, suitable for highlighting architectural facade and general purpose lighting. highmast/basket ball court/squach court/batmittan court light etc complete all as specified and directed including taking down the u/s flood light fittings. |
| 33 | Supply and Repair/Replacement of Laying in trenches or passing through pipe,25 Sqmm 4 core LT XLPE cable with stranded aluminium conductor heavy duth for 1100 volts grade cross sectional area complete all as specified and as directed. |
| 34 | Supply and lay Double Walled Corrugated (DWC) Pipes of dia 50mm having corrugation on the outer wall and plain surface on the inner wall confirming to IS14930 (Part-II) for protection of UG cables size 50 mm outer dia laid in trenches/ road/ drain or fixed along wall, poles or laid under floor all as spd and as directed by Engr-In-Charge. |
| 35 | Supply and Repair/Replacement for Cable with copper conductor PVC round sheathed (flexible) 3 core 4 sqmm industrial cable complete all as specified and directed by Engineer-in-Charge. |
| 36 | Supply and Repair/Replcement for weather proof flat twin core 6 sqmm multistrand Aluminium conductor cable with PVC conduit of dia 25mm with accessories complete all as specified and directed by Engineer-in-Charge. |
| 37 | Excavation in trenches n.exc 1.5 m wide and n.exc 1.5 m deep and getting out hard/dense soil for taking out / laying of UG cable.LT of any size complete all as specified and as directed. |
| 38 | Returning and filling in trenches incl spreading, levelling watering and raming in layer n.exc 25 cm complete all as specified and directed. |
| 39 | Removing of excavated mtrls n.exc 50 m and depositing where directed at a level n.exc 1.5 m above the starting point. |
| 40 | Material and labour for Detecting the gas leakage, rectifying the defects by vacumizing and charging fresh mafron gas and commissioning and testing the Water cooler of Capacity 40/80 Ltrs. |
| 41 | Ditto all as per item No. 27 above but of Water cooler 120/315 Ltrs. Capacity. |
| 42 | Ditto all as per item No. 27 above but of Refrigerator 165/180/230 Ltrs. Capacity. |
| 43 | Ditto all as per item No. 27 above but of Refrigerator 260/280/310/350 Ltrs. Capacity. |
| 44 | Ditto all as per item No. 27 above but of Deep Freezer of 260/280/310/350/500 Ltrs. Capacity. Please Enable Macros to View BoQ information |
| 45 | Ditto all as per item No. 27 above but of Deep Freezer of 260/280/310/350/500 Ltrs. Capacity. Please Enable Macros to View BoQ information |