| 1 | Taking down copper/aluminium point wiring (light, fan, socket or power) complete including fixtures and fittings such as switches, ceiling roses, pendants, regulators, sockets, light fitting etc. removing unserviceable materials and making good disturbed surfaces of walls, floors etc. |
| 2 | M & L for point wiring with 1100 Volts grade 1.5 sqmm PVC insulated FRLSH unsheated cable with multistandred copper conductor conforming to IS: 694:1990 (for phase, Neutral and and Earth) in and including Non metalic PVC rigid condiut medium grade ISI mark with all accessories concealed in wall/ ceiling/floor / road etc, with cast iron / pressed steel terminal box of sutaible size duly painted inner & outside by anticorrosive paint, including plastic laminated sheet 1.6 mm thick for mounting switches, socket cover with fitting screw washer, including cutting chasses in wall/floor/roof for fixing of conduit and making good the distributed surfaces using cement plaster, levelling with existing surface complete all as specified and as directed for following-One light/ fan/ bell point controlled by one switch |
| 3 | M & L for One Light/ Fan point on same switch circuit board with other switches complete all as specified and directed by Engr-In-Charge |
| 4 | M & L 5 Amp socket outlet point on same board complete all as specified and directed by Engr-In-Charge |
| 5 | M & L 5 Amp socket outlet point independent but near switch board complete all as specified and directed by Engr-In-Charge |
| 6 | One light point controlled by two way switch complete all as specified and directed by Engr-In-Charge |
| 7 | All as per Item no 2 above here in before but with 2.5 sqmm size wire for power point concealed in wall complete all as specified and directed by Engr-In-Charge |
| 8 | M & L for point wiring with 1100 Volts grade 1.5 sqmm PVC insulated FRLSH unsheated cable with multistandred copper conductor conforming to IS: 694:1990 (for Phase, Neutral and and Earth) in and including Non metalic PVC rigid condiut medium grade with ISI mark of appropriate size with all accessories concealed in wall/ ceiling/floor etc, with GI flush in box/terminal boxes of sutaible size, including front plate for mounting of modular switch/ socket and combined cover plate with fitting screw washer, including cutting chasses in wall/floor/roof for fixing of conduit and flush in box and making good the distributed surfaces matching with existing complete all as specified and as directed for following-One light/ fan/bell/ point controlled by one switch |
| 9 | M & L for One Light/ Fan point on same switch circuit board with other switches complete all as specified and directed by Engr-In-Charge |
| 10 | All as per Item No 3 above here in before but for Modular type Socket 6/10 Amp of two module in independent board, 230 volts complete all as specified and directed by Engr-In-Charge. Make: |
| 11 | All as per Item No 3 above here in before but for Modular type Socket 6/10 Amp of two module on same board, 230 volts complete all as specified and directed by Engr-In-Charge. |
| 12 | All as per Item no 3 above here in before but for Modular type socket 16A of Two Module but with size 2.5 sqmm wire for power point concealed in wall complete all as specified and directed by Engr-In-Charge |
| 13 | M & L for point wiring with 1100 Volts grade 1.5 sqmm PVC insulated FRLSH unsheated cable with multistandred copper conductor conforming to IS: 694:1990 (for phase, Neutral and and Earth) in Existing condiut all accessories concealed in wall/ ceiling/floor / road etc, with cast iron / pressed steel terminal box of sutaible size duly painted inner & outside by anticorrosive paint, including plastic laminated sheet 1.6 mm thick for mounting switches, socket cover with fitting screw washer, including cutting chasses in wall/floor/roof for fixing of conduit and making good the distributed surfaces matching with existing complete all as and as directed for following-One light/ fan/bell point controlled by one switch |
| 14 | M & L One Light/ Fan point as same switch circuit board with other switches complete all as specified and directed by Engr-In-Charge |
| 15 | M & L 5 Amp socket outlet point on same board complete all as specified and directed by Engr-In-Charge |
| 16 | M & L 5 Amp socket outlet point independent but near switch board complete all as specified and directed by Engr-In-Charge |
| 17 | All as per Item no 4 above here but with 2.5 sqmm size wire for power point in existing conduit complete all as specified and directed by Engr-In-Charge |
| 18 | M & L for point wiring with 1100 Volts grade 1.5 sqmm PVC insulated FRLSH unsheated cable with multistandred copper conductor conforming to IS: 694:1990 (for phase, Neutral and Earth) in casing caping medium grade with all accessories, including cast iron / pressed steel terminal box of sutaible size duly painted inner & outside by anticorrosive paint, including plastic laminated sheet 1.6 mm thick for mounting switches, socket cover with fitting screw washer, including cutting chasses in wall for fixing of terminal boxes for mounting switch/sockets and making good the distributed surfaces using cement plaster, levelling to match with existing surface complete all as and as directed for following- One light/ fan/bell point controlled by one switch |
| 19 | M & L One Light/ Fan point as same switch circuit board with other switches complete all as specified and directed by Engr-In-Charge |
| 20 | M & L 5 Amp socket outlet point on same board complete all as specified and directed by Engr-In-Charge |
| 21 | M & L 5 Amp socket outlet point independent switch board complete all as specified and directed by Engr-In-Charge |
| 22 | All as per Item no 5 above but with cable 2.5 sqmm wire for power point in casing caping medium grade of appropriate size complete all as specified and directed by Engr-In-Charge |
| 23 | S&F for switch piano, flush type single pole, one way 5 Amps, 230 Volts complete all as specified and directed by Engr-In-Charge. |
| 24 | S&F for switch piano, flush type single pole, two way 16 Amps, 230 Volts complete all as specified and directed by Engr-In-Charge. |
| 25 | M&L for switch socket outlet 2 in1, 5pin, 5Amp with mounting arrengement on two/ four holes complete all as specified and as directed by Engr-in-charge. |
| 26 | M&L for switch socket outlet 2in1, 6pin, 5/15Amp multipurpose with mounting arrengement on two/ four holes complete all as specified and as directed by Engr-in-charge . |
| 27 | S&F for Modular type switch one way 6/10 Amps, 230 volts matching with existing complete all as specified and directed by Engr-In-Charge. |
| 28 | S&F for Modular type switch one way 16 Amps, 230 volts, matching with existing complete all as specified and directed by Engr-In-Charge. |
| 29 | S&F for Modular type Socket 6/10 Amps, 230 volts matching with existing complete all as specified and directed by Engr-In-Charge. |
| 30 | S&F for Modular type Socket 16 Amps, 230 volts, matching with existing complete all as specified and directed by Engr-In-Charge. |
| 31 | S&F for Modular type fan regulator 1/2 module as reqd matching with existing, 230 volts complete all as specified and directed by Engr-In-Charge. |
| 32 | S & F of stepped type electronic fan regulator flush type complete all as specified and as directed by Engr-In-Charge. |
| 33 | S&F for Modular type bell push switch one way 6/10 Amps, 230 volts matching with existing complete all as specified and directed by Engr-In-Charge. |
| 34 | S&F Bell push piano type, 5 Amps complete all as specified and directed by Engr-In-Charge. |
| 35 | S&F for Ceiling rose surface mounted with three terminals, PVC/Polycarbonate isolated body complee all as specified and directed by Engr-in-Charge. |
| 36 | S&F Call bell AC, 230 Volts matching with existing sample complete all as specified and directed by Engr-In-Charge. |
| 37 | S&F in replacement of single pole and neutral enclosure with a two pin and earth plug and socket complete with one single pole MCB of capacity 20/32 Amps as reqd all as specified and directed . |
| 38 | S&F MCB, DB Double door type, made out of CRCA mild steel sheet flushed in wall, SPN 4 way with 200 Amps rated bus bar , 240 volts IP-43, with PVC MCB blanking plates, stove enamelled, dust and vermin proof suitable for incorporation of MCB's and isolators etc including taking down complete all as specified and as directed. |
| 39 | All as per item no 21 above but for SPN 8 Way DB complete all as specified and directed by Engr-In-Charge. |
| 40 | All as per item no. 21 above but for TPN 4 way DB 415 Volts complete all as specified and directed by Engr-In-Charge. |
| 41 | S & F in replacement VTPN DB - Dobule Door made out of CRCA mild steel sheet flushed in wall, TPN 4 way with 200 Amp rated bus bar, 415 volt with PVC MCB blanking plate, stove enamelled for incorporated of MCBs, insulators and MCCB of capacity upto 125 Amps TP/FP etc, complete all as specified and as directed by engineer in charge. |
| 42 | Supply and fixing in replacement of MCB TPN 415 Volt 63 Amps Complete all as specified and as directed by Engr-in-Charge. |
| 43 | Supply and fixing in replacement of MCB SPN 6 - 40 Amps, 240 Volts Complete all as specified and as directed by Engr-in-Charge. |
| 44 | Supply & fixing in replacement of MCB SP 06-40 Amp, AC, 240 volts, Complete all as specified and as directed by Engr-in-Charge. |
| 45 | S& F in replacement of Capacitor of rating 2.5/3.15 mfd 230 V complete all as specified and as directed by Engr-In-Charge. |
| 46 | S&F in replacement of Heating element 1500/2000Watt round/triangular type as reqd matching with existng at site complete all as specified and directed by Engr-In-Charge. |
| 47 | S&F in replacement of Thermostat for 25/50 Ltr cap geyser and making connection |
| 48 | S&F in replacement of PVC connection 15 mm bore with PTMT nuts of length 450mm |
| 49 | S&F in replacement of PVC connection 15 mm bore with PTMT nuts of length 600mm |
| 50 | S&F in replacement of 5 Amp switch socket with junction box complete all as specified and as directed by Engr-In-Charge. |
| 51 | S&F in replacement of 15 Amp switch socket with junction box complete all as specified and as directed by Engr-In-Charge. |
| 52 | S&F in replacement PVC insulated FRLS unsheathed multistranded copper cable1.5 sqmm complete all as specified and as directed by Engr-In-Charge. |
| 53 | S&F in replacement PVC insulated FRLS unsheathed multistranded copper cable 2.5 sqmm complete all as specified and as directed by Engr-In-Charge. |
| 54 | S&F in replacement PVC insulated FRLS unsheathed multistranded copper cable 4.0 sqmm complete all as specified and as directed by Engr-In-Charge. |
| 55 | S&F in replacement PVC insulated multistranded flexible 3 core copper wire 1.5 sqmm complete all as specified and as directed by Engr-In-Charge. |
| 56 | S&F in replacement PVC insulated aluminium stranded conductor cable 2 core 6 sqmm complete all as specified and as directed by Engr-In-Charge. |
| 57 | S&F in replacement PVC insulated aluminium stranded conductor cable 2 core 10 sqmm complete all as specified and as directed by Engr-In-Charge. |
| 58 | Supply and Fixing in replacement of PVC Casing caping of size 18 mm x 8 mm with clips locking, complete all as specified and as directed by Engr-In-Charge. |
| 59 | Supply and Fixing in replacement of PVC Casing caping of size 20 mm x 12 mm with clips locking, complete all as specified and as directed by Engr-In-Charge. |
| 60 | S&F in replacement of flush metal GI Box for Modular type switch and sockets flush in wall including cutting chasses to wall for fixing of box and making good to disturbed surface suitable for mounting 4 nos switch one module complete all as specfied and directed by Eng-In-Charge. |
| 61 | S&F in replacement of modular switch and socket mounting/cover plate with frame suitable for 4 module metal GI Box for modular type switches and sockets complete all as specified and directed by Engr-In-Charge. |
| 62 | S&F in replacement of flush metal GI Box for Modular type switch and sockets flush in wall including cutting chasses to wall for fixing of box and making good to disturbed surface suitable for mounting 6 nos switch one module complete all as specfied and directed by Eng-In-Charge. |
| 63 | S&F in replacement of modular switch and socket mounting/cover plate with frame suitable for 6 module metal GI Box for modular type switches and sockets complete all as specified and directed by Engr-In-Charge. |
| 64 | S&F in replacement pole mounted light fitting for outdoor use Post top laltern/Garden Light with aluminum die cast base suitable for mounting on 40mm dia pole/pipe and polycarbonate white diffuser suitable for and including 9W LED lamp with B22 base of color as decided including B22 lamp holder complete all as specified and directed by Engr-In-Charge. |
| 65 | S&F in replacement of surface mounted Mirror light LED batten 2 feet 10 W color as decided with all accessories as required flexible copper 2 core wire from fitting to ceiling rose complete all as specified and as directed by Engr-in-Charge. |
| 66 | S&F in replacement of surface & wall mounted LED batten 4 feet 20 W color as decided including flexible copper 2 core wire from tube light fitting to ceiling rose required length with all accessories all specified and as directed by Engr-in-Charge. |
| 67 | S&F in replacement LED weather proof bulk head light fitting of shape and size as per site requirment of wattage upto 10 watt matching with existing unserviceable light fitting with mounting clamp, LED driver holder, LED lamps etc including connecting up to in celling rose complete all as specified and as directed by Engr-in-Charge. |
| 68 | S&F in replacement LED downlighter light fitting of shape and size as per site requirment of wattage 15 to 20 watt matching with existing unserviceable light fitting with mounting clamp, LED driver holder, LED lamps color as decided at site etc including connecting up to in celling rose complete all as specified and as directed by Engr-in-Charge. |
| 69 | S&F in replacement LED recess/surface mounting as reqd 2x2 fittings 600 mm x 600 mm,35/36 watt, 220 V AC recessed type with deffuser glare free light complete with driver, holders & LED lamp of colour as decided suitable for roof ceiling including connecting up with driver three core flexible copper conductor cases of suitable size complete all as specified and as derected by Engr-in-Charge |
| 70 | S&F in replacement building protection light fitting to be mounted on pole/bracket of minimum 35W, 230 V AC outdoor type with high pressure die cast aluminum hosing and heat resistant complete with driver, corrosion resistant including optics for scattering light complete all as specified and directed by Engr-In-Charge. |
| 71 | S&F in replacement LED inverter batten tube light fitting 4 ft 20 watts complete all as specified and as directed by Engr-In-Charge. |
| 72 | S&F in replacement wall mounting light fitting in plastic body with lamp holder fancy B22 base and diffiuser sutaible for and including 9w LED Lamp of colour as decided with mounting provision complete all as secified as directed by Engr-in-Charge. |
| 73 | S&F in replacement ceiling fan motor of 1200 mm sweep complete with rotor, stator, outer body including 3 nos fan blades, down rod and other connected accessories matching with existing complete all as specified and as directed by Engr- in- Charge. |
| 74 | S&F in replacement Exaust fan motor of 250 mm sweep plastic body complete with rotor, stator, outer body and other connected accessories including mounting frame matching with existing complete all as specified and as directed by Engr- in- Charge. |
| 75 | S&F in replacement Exaust fan motor of 300 mm sweep metal body complete with rotor, stator, outer body and other connected accessories including mounting frame matching with existing complete all as specified and as directed by Engr- in- Charge. |
| 76 | S&F in replacement Exaust fan motor of 400 mm sweep metal body complete with rotor, stator, outer body and other connected accessories including mounting frame matching with existing complete all as specified and as directed by Engr- in- Charge. |
| 77 | Supply, laying, testing and commissioning of LT under ground cable XLPE in repair insulated armoured, heavy duty, elelctric cable, size 10 Sqmm 2 Core with stranded aluminium conductor, 1100 Volts grade conforming to IS -7098 (Part-I) 1988 fixed with saddle and clamps complete with cable ends connection with proper thimbles nut bolts washer including taking down of existing cables Complete all as specified and as directed by Engr-In-Charge. |
| 78 | All as per item No.60 above but of size 16 Sqmm x 4 core |
| 79 | Supply and fix in repair electric water heating tank system, storage type with plastic body inner tank and heating element upto 2 KW storage capacity 25 litre, repair safety valve, thermostate, NRV, inner tank, outer body connection pipe etc.including connecting up with three core copper conductor cable to 15Amps plug top including dismatling and refixing complete all as specified and directed. |
| 80 | M&L sub main wiring surface type with two runs of single core, PVC insulated, unsheathed multi standard copper conductor cable of size 6 Sqmm, 1100 volts grade (FRLS) and one run of 6 Sqmm PVC insulated multi stranded copper conductor for earth continuity conductor drawn through concealed/ casing caping/ PVC conduit as required at site including taking down complete all as specified and as directed by Engr-In-Charge. (Note :- Two runs of 6 Sqmm cable, one run of 6 Sqmm continuity earth wire and one run of PVC conduit with all necessary accessories will be measured as one length). |
| 81 | M&L sub main wiring surface type with two runs of single core, PVC insulated, unsheathed multi standard copper conductor cable of size 4 Sqmm, 1100 volts grade (FRLS) and one run of 4 Sqmm PVC insulated multi stranded copper conductor for earth continuity conductor drawn through concealed/ casing caping/ PVC conduit as required at site including taking down complete all as specified and as directed by Engr-In-Charge. (Note :- Two runs of 4 Sqmm cable, one run of 4 Sqmm continuity earth wire and one run of PVC conduit with all necessary accessories will be measured as one length). |
| 82 | S & F LED Land Scape not less than 8W made up of pressure die cast aluminium housing and LEDs as a light source prewired with electronic driver suitable for 8 watts light fitting with IP 65 protection with Surge protection device for protection of LED driver, lumen efficacy of light fitting shall be not less than 100 lm/W. with pole of height upto 1 mtr including mounting arrangements on floor/ Earth using PCC of appropriate ration as required including taking down old unserviceable light fitting.complete all as specified and directed by Engr-in-charge. |
| 83 | M & L earthing complete with GI earth plate Electrode 60 cm x 60 cm x 6 mm thick burried directly in ground (earth plate not less than 2.25 Metre deep below ground level) with top edge of the plate not less than 1.5 metre below normal ground level connected to galvanished earth wire 4.0 mm dia by means of bolts, nuts check and washers of GI or steel all as shown in electrical plate No. 3 of SSR Pt -I connected to earthing test point all as specified or indicated including GI pipe 15 mm dia light grade for earth wire protection, necessary excavation, earth work in any type of soil, PCC chamber and RCC cover slab, connecting lead wire from test point to DB including taking down old earthing material complete all as specified & as directed by Engr-In-Charge. Please Enable Macros to View BoQ information |