|
| 1 | Supply, erection, testing & commissioning of 7 Mtr height hot dip Galvanized (both internal and external surface finish : typically 80 microns) Octagonal security/ street light Poles having top dia 70 mm and bottom dia 130 mm made of 5 mm thick sheet steel plate in single section, continuously tapered profile for stability and aesthetically with base plate (as mentioned in the item given below) The galvanizing shall be as per IS 4759, method of adhesion and life as per BS: 729 equivalent to IS: 4985, steel plates as per BSEN 10025/IS 5986, folding and welding longitudinally as per IS 9595/IS 10178 and withstand wind pressure as per IS:875. Erection of Pole in cement concrete 1:2:4 (1 cement: 2 coarse sand: 4 graded stone aggregate 20 mm nominal size) foundation including excavation and refilling and secured with holding clamps, Anchor bolts, nuts, template etc. as required. Pole should be finished with flush door for connection i/c wiring with 3 x 1.5 Sq. mm PVC insulated/ sheathed copper conductor weather proof cable from flush door to fitting i/c supplying and fixing of suitable size of 1 No. SP MCB, 4 Nos heavy duty line up terminal on Dinbar, mounted on hylem/mica sheet of thickness not less than 6 mm, connection etc. as reqd. Pole should be erected on suitable size cement concrete foundation The Item includes P/F excavation of earth of suitable size as per approved drawing as required with positioning of foundation bolts- 04 nos, j-type foundation bolt with nuts, washer including 01 nos template of 3 mm thick of suitable size with 4 nos suitable size of dia holes, to match with PCD of pole base plate as reqd with 1 nos. 63 mm dia HDPE pipe of 6 Kg. pressure duly bend of 1.0 Mtr./ required length etc. as reqd. The item also includes for work, water curing, plastering etc complete as req. as per approved drawing. (Drawings of poles and its RCC structure shall be got approved before erection) Foundation Base Plate: 220 mm x 220 mm x 12 mm thick having PDC 220 mm made of Hot rolled GI plate as per latest IS and duly welded to the base of the pole etc. as required as per manufacturer specification and as mentioned in the NIT of Make - Crompton /Surya/Utkarsh/ Bajaj. |
| 2 | Supply, erection, testing & commissioning of 11 Mtr height hot dip Galvanized (both internal and external surface finish : typically 80 microns) Octagonal street light Poles having top dia 70 mm and bottom dia 155 mm made of 5 mm thick sheet steel plate in single section, continuously tapered profile for stability and aesthetically with base plate (as mentioned in the item given below) The galvanizing shall be as per IS 4759, method of adhesion and life as per BS: 729 equivalent to IS: 4985, steel plates as per BSEN 10025/IS 5986, folding and welding longitudinally as per IS 9595/IS 10178 and withstand wind pressure as per IS:875. Erection of Pole in cement concrete 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size ) foundation including excavation and refilling and secured with holding clamps, Anchor bolts, nuts, template etc. as required. Pole should be finished with flush door for connection i/c wiring with 3 x 1.5 Sq. mm PVC insulated/ sheathed copper conductor weather proof cable from flush door to fitting i/c supplying and fixing of suitable size of 1 No. SP MCB, 4 Nos heavy duty line up terminal on Dinbar, mounted on hylem/mica sheet of thickness not less then 6 mm, connection etc. as reqd. Pole should be erected on suitable size cement concrete foundation The Item includes P/F excavation of earth of suitable size as per approved drawing as required with positioning of foundation bolts- 04 nos, j-type foundation bolt with nuts, washer including 01 nos template of 5 mm thick of suitable size with 4 nos suitable size of dia holes, to match with PCD of pole base plate as reqd with 1 nos. 63 mm dia HDPE pipe of 6 Kg. pressure duly bend of 1.0 Mtr./ required length etc. as reqd. The item also includes for work, water curing, plastering etc complete as req. as per approved drawing. (Drawings of poles and its RCC structure shall be got approved before erection.) Foundation Base Plate : 300 mm x 300 mm x 16 mm thick having PDC 300 mm made of Hot rolled GI plate as per latest IS and duly welded to the base of the pole etc. as required as per manufacturer specification and as mentioned in the NIT of Make - Crompton /Surya/Utkarsh/ Bajaj. |
| 3 | Supply, erection, testing & commissioning of 3 Mtr height hot dip Galvanized (both internal and external surface finish : typically 80 microns) CONICAL pole having top dia 65 mm and bottom dia 114 mm made of 4 mm thick sheet steel plate in single section, continuously tapered profile for stability and aesthetically with base plate (as mentioned in the item given below) The galvanizing shall be as per IS 4759, method of adhesion and life as per BS: 729 equivalent to IS: 4985, steel plates as per BSEN 10025/IS 2062, folding and welding longitudinally as per IS 9595/IS 10178 and withstand wind pressure as per IS:875. Erection of Pole in cement concrete 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size ) foundation including excavation and refilling and secured with holding clamps, Anchor bolts, nuts, template etc. as required. Pole should be finished with flush door for connection i/c wiring with 3 x 1.5 Sq. mm PVC insulated/ sheathed copper conductor weather proof cable from flush door to fitting i/c supplying and fixing of suitable size of 1 No. SP MCB, 4 Nos heavy duty line up terminal on Dinbar, mounted on hylem/mica sheet of thickness not less then 6 mm, connection etc. as reqd. Pole should be erected on suitable size cement concrete foundation The Item includes P/F excavation of earth of suitable size as per approved drawing as required with positioning of foundation bolts- 04 nos, j-type foundation bolt with nuts, washer including 01 nos template of 5 mm thick of suitable size with 4 nos suitable size of dia holes, to match with PCD of pole base plate as reqd with 1 nos. 63 mm dia HDPE pipe of 6 Kg. pressure duly bend of 1.0 Mtr./ required length etc. as reqd. The item also includes for work, water curing, plastering etc complete as req. as per approved drawing. (Drawings of poles and its RCC structure shall be got approved before erection.) Foundation Base Plate : 220 mm x 220 mm x 12 mm thick having PDC 220 mm made of Hot rolled GI plate as per latest IS and duly welded to the base of the pole etc. as required as per manufacturer specification and as mentioned in the NIT Make - Crompton /Surya/Utkarsh/ Bajaj. |
| 4 | Supply and installation of Single arm bracket having cap made out of 80 mm dia GI pipe (Medium class),300 mm long and arm made out of 40 mm dia GI Pipe (Medium class), 1.0 Mtr long to be welded with cap including fixing the bracket with 04 Nos GI nut on existing pole including connection testing etc as required as per direction of engg-in-charge. |
| 5 | Supply and installation of round bracket (ring type) suitable for mounting four floodlights. The round bracket should be made of 40 dia. (nominal bore) B-Class G.I. pipe on the periphery and four supports (spokes) of 40 mm B-Class G.I. pipe duly welded with a pole cap of 300 mm length at the centre. The pole cap should be of suitable dia for mounting on an existing polygonal pole with a top dia. of 100 mm. The dia. of the round bracket should not be less than 75 cm. The bracket pipes should be suitable for acting as conduits for wires for the wiring of floodlights. The pole cap should have four holes and four numbers of G.I. nuts and bolts for fixing the bracket on the top of the octaonal pole including connection testing etc as required as per direction of engg-in-charge. |
| 6 | Supply and installation of double arm bracket having cap made out of 80 mm dia GI pipe (Medium class),300 mm long and arm made out of 40 mm dia GI Pipe (Medium class), 1.0 Mtr long one side and 1.0 Mtr long another side to be welded with cap including fixing the bracket with 04 Nos GI nut on existing pole including connection testing etc as required as per direction of engg-in-charge. |
| 7 | Supply, Installation Testing and Commissioning of maximum 70 watt energy saving and environmental friendly LED street light made up of pressure die-cast housing with high efficiency prismatic polycarbonate modular secondary lens optics, with IP-66 protection, Lumen efficacy of LED > 140 lm/watt Color temperature 5700 K/6000 K, with in build surge protection device with bottom opening driver cover for easy maintenance etc. as required .(Fittings will be warranted for min 2 years from the date of completion of work necessary certificate in this regard will be provided by the contractor through authorized dealer / stockist from whom it was procured). Make Havells model Endura sundown or equivalent in Philips/Bajaj/Crompton.) |
| 8 | Supply, Installation Testing and Commissioning of maximum 150-watt LED flood light made up of pressure die cost housing with toughened glass on erected octagonal poles with following specification: system wattage: 150 Watt +/- 10% Lamp type LM80 certified, Lens cluster for optimum discrete LEDs. System lumen efficiency ≥ 110 lm/watt, Color temperature 5700 K/6000 K, PF> 0.95 , Rated voltage and frequency-240 Volt , 50 Hz, Aluminium PDC housing, polycarbonate IP Lence with silicon gasket, IP66 protection and 10 KV SPD etc. as required .(Fittings will be warranted for min 2 years from the date of completion of work necessary certificate in this regard will be provided by the contractor through authorized dealer / stockist from whom it was procured). Make Havells or equivalent make Surya/Havells/Philips as per Engg-in-charge |
| 9 | Supply, Installation, Commissioning of post top luminaire having symmetrical beam angle with housing material of Die-cast aluminium, UV protected polycarbonate diffuser, system wattage not exceeding 35W and system lumen output of not less than 3700 lumens with efficacy > 105 lumens/W. CCT of 3000K and CRI>=70 with SDCM<5; luminaire dimensions top Dia 450-455 mm and weight not more than 4.5kgs. Fixture shall operate in a temperature range of 0°C to 50°C. Fixture shall have input voltage for 120-277 VAC. Lifetime should be at least 30,000 burning hours at L70 at 50 degrees centigrade ambient. Fixture shall be equipped with total IP66 protection and mechanical impact of minimum IK10. The LED used in the luminaire shall be SMD type. The Driver should be potted /encapsulated & should be a BIS approved driver and not a printed circuit board without casing, mounted inside the luminaire. The luminaire should be capable of auto shutdown @ 325V and have an auto recovery feature, with THD<10% (at full load). It should have a 10KV series SPD inside the housing. BIS approval for both Driver and the luminaire needs to be submitted for records. Also, LM79 and LM80 reports must be submitted from a NABL accredited laboratory. Driver and luminaire must be of same make (Fittings will be warranted for min 02 years from the date of installation necessary certificate in this regard will be provided by the contractor through authorized dealer / stockist from whom it was procured) Make Surya/Havells/Philips/Crompton/Orient/Bajaj or equivalent make and as per Engg-in-charge |
| 10 | Supply, installation, testing and commissioning of cubical type LT Panel suitable for 415V, 3 Phase, 4 wire 50 Hz AC supply system having front surface area not less than 1.20 sq. mtr. and depth not less than 300 mm fabricated in compartmentalized design from CRCA sheet steel of 2 mm thick for frame work and covers, 3 mm thick for gland plates i/c cleaning and finishing complete with 7 tank process for powder coating in approved shade, having 200 amps capacity extensible type TPN alluminium alloy bus bars of high conductivity, DMC/SMC bus bar supports, with short circuit withstand capacity of 31 MVA for 1 sec., bottom base channel of MS section not less than 100mm x 50mm x 5mm thick, fabrication shall be done in transportable sections, entire panel shall have a common copper earth bar of size 25mm x 5mm at the rear with 2 nos. earth stud, solid connection from main bus bar to switch gears with required size of 200 Amp main Al. bus bars control wiring with suitable size of PVC insulated copper conductor S/C cable, cable alleys, cable gland plates in two half, naming/ numbering, The LT. Panel shall be as per CPWD specification for elect. Sub-station work 2013 (Part-IV) as amended upto date complete with following switch gears and accessories etc as required. Factory inspection certificates of panel to be enclosed. (For street/ security light) Panel Enclosure 14 Gauge (Outdoor) of size 1375 mm (H) x 1200 mm (W) x 400 mm (D)Fitting and Accessories: The following fittings shall be provided and fitted:-1)INCOMING : 160A 4P 50kA MCCB TM Release, Type: DN2-250N, 415V AC, 50Hz - 1 No, Extended Rotary Handle for DN2 MCCB - 1 No, Spreader Terminals - 4 Pole (Set of 8) for DN1, DN2-250 MCCB - 1 Set, 160/5A 15VA Acc. Cl: 1 Ring Type Current Transformer - 3 set, 4 Sq.mm Disconnecting Terminal (Std. Color),Type: KLTD M4NV - 1 Nos, Multifunction Meter (LED display), 3Ph, Parameters: V, A, F, PF, kW, kVA, Old energy, On hours, site selectable kWh/ kVAh, CL: 1, Aux Sup: 90-300V AC/DC, Size: 96X96, With: RS485 - 1 Set, Red Gen Next Pro LED Indicator 22.5 mm, Voltage: 240V AC - 1 No, Yellow Gen Next Pro LED Indicator 22.5 mm, Voltage: 240V AC - 1 No, Blue Gen Next Pro LED Indicator 22.5 mm, Voltage: 240V AC - 1 No, 32A Neutral Link, Channel Mounting, Color: Black/Grey - 1 No, 2A 1P 10kA, C-Curve MCB - 1 No, TIMER CIRCUIT : AC1: 80A 4P Power Contactor, Coil: 240V AC, Type: MCX 13 - 1 No, Time Switch (Astro), Voltage: 110 - 240V AC, 3 Phase - 4 W, 3 Channel, Base/DIN - 1 No, 6A 2P 2Way Local - Remote/ Auto-Manual Switch with Center OFF, 60 Deg. Operation - 1 No, Red Flush Head Push Button 22.5 mm - 1 No, Green Flush Head Push Button 22.5 mm - 1 No, 1NO Contact Block - 1 No, 1NC Contact Block - 1 No, Red Gen Next Pro LED Indicator 22.5 mm, Voltage: 240V AC - 1 No, Green Gen Next Pro LED Indicator 22.5 mm, Voltage: 240V AC - 1 No, 2A 1P 10kA, C-Curve MCB - 1 No, OUTGOING : 63A 4P 18kA MCCB TM Release, Type: DU100D, 415V AC, 50Hz - 1 No, Extended Rotary Handle for DU100D/DU125D/DU100H/DU125HMCCB - 1 No, 63A 4P, Standard Connection Plate (in DMC), Color: Black - 1 No, |
| 11 | Earthing with G.I. earth pipe 4.5 metre long, 40 mm dia including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe etc. with charcoal/ coke and salt as required. (for 7 Block x 1 earthing) |
| 12 | Providing and laying earth connection from earth electrode with 6 SWG dia G.I. Wire in 15 mm dia G.I. pipe from earth electrode including connection with G.I. thimble excavation and re-filling as required. |
| 13 | Providing and fixing 6 SWG dia G.I. wire on surface or in recess for loop earthing as required. |
| 14 | Providing and fixing 6 SWG dia GI. wire on surface or in recess for loop earthing along with existing surface/ recessed conduit/ subnnain wiring/ cable as required. |
| 15 | Supplying and fixing cable route marker with 10 cm X 10 cm X 5 mm thick G.I. plate with inscription there on, bolted /welded to 35 mm X 35 mm X 6 mm angle iron, 60 cm long and fixing the same in ground as required |
| 16 | Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as reqd. 4 X 25 sq. mm (28 mm) |
| 17 | Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as reqd. 4 X 35 sq. mm (32 mm) |
| 18 | Supplying and laying of following size DWC HDPE pipe ISI marked along with all accessories like socket, bend, couplers etc. conforming to IS 14930, Part II complete with fitting and cutting, jointing etc..direct in ground (75 cm below ground level) including excavation and refilling the trench but excluding sand cushioning and protective covering etc., complete as required 63 mm dia (OD-63 mm & ID-51 mm nominal) |
| 19 | Supplying and laying of following size DWC HDPE pipe ISI marked along with all accessories like socket, bend, couplers etc. conforming to IS 14930, Part II complete with fitting and cutting, jointing etc..in the existing trench, complete as required 63 mm dia (OD-63 mm & ID-51 mm nominal) |
| 20 | Supplying and Laying of 4 x 35 sqmm Sqmm one number power Cables multi stranded Aluminium conductor, XLPE Insulated, cores laid up PVC tape / Extruded Inner sheath, unarmoured, extruded PVC Type ST2 sheathed, 650/1100V grade as per IS 7098(Part 1) 1988 with upto date amendments in the existing RCC/ HUME/ METAL/HDPE pipe as reqd. Make- Havells/ KEI/Polycab/ Finolex etc. |
| 21 | Supplying and Laying of 4 x 35 sqmm Sqmm one number power Cables multi stranded Aluminium conductor, XLPE Insulated, cores laid up PVC tape / Extruded Inner sheath, unarmouredr, extruded PVC Type ST2 sheathed, 650/1100V grade as per IS 7098(Part 1) 1988 with upto date amendments in the existing masonry open duct/Loop etc as required. Make- Havells/KEI/Polycab/Finolex etc. |
| 22 | Supplying and Laying of 4 x 25 Sqmm one number power Cables multi stranded Aluminium conductor, XLPE Insulated, cores laid up PVC tape / Extruded Inner sheath, unarmoured, extruded PVC Type ST2 sheathed, 650/1100V grade as per IS 7098(Part 1) 1988 with upto date amendments in the existing RCC/ HUME/ METAL/HDPE pipe as reqd. Make- Havells/ KEI/Polycab/ Finolex etc. |
| 23 | Supplying and Laying of 4 x 25 Sqmm one number power Cables multi stranded Aluminium conductor, XLPE Insulated, cores laid up PVC tape / Extruded Inner sheath, unarmoured, extruded PVC Type ST2 sheathed, 650/1100V grade as per IS 7098(Part 1) 1988 with upto date amendments in the existing masonry open duct/Loop etc as required. Make- Havells/KEI/Polycab/Finolex etc. Please Enable Macros to View BoQ information |