| 1 | External Electrification Works of Railway Staff Quarters and Other Service Buildings at Subhramanya Road location, in connection with Railway Electrification works of Mysuru-Hassan-Mangalore section of South Western Railway |
| 2 | Amount after unconditional rebate |
| 3 | Total Of BOQ 3, BOQ 4, BOQ 5 and BOQ 6 |
| 4 | SCHEDULE -\\"A\\" DSR 2025 Electrical Items |
| 5 | SCHEDULE -\\"B\\" KPWD SR 2023-24 - Electrical Items |
| 6 | SCHEDULE - \\"C\\" Market Rate - Electrical Items |
| 7 | SCHEDULE - \\"D\\" DSR 2023 Civil Items |
| 8 | Part A - DSR 2025 - Electrical Items |
| 9 | Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 11 KV grade of following size direct in ground including excavation, sand cushioning, protective covering and refilling the trench etc as required. |
| 10 | Upto 120 sq. mm |
| 11 | Laying of one number additional PVC insulated and PVC sheathed / XLPE power cable of 11 KV grade of following size direct in ground in the same trench in one tier horizontal formation including excavation, sand cushioning, protective covering and refilling the trench etc as required. |
| 12 | Upto 120 sq. mm |
| 13 | Supplying and making indoor cable end termination with heat shrinkable jointing kit complete with all accessories including lugs suitable for following size of 3 core, XLPE aluminium conductor cable of 11 KV grade as required: |
| 14 | 120 sq. mm |
| 15 | Supplying and making outdoor cable end termination with heat shrinkable jointing kit complete with all accessories including lugs suitable for following size of 3 core, XLPE aluminium conductor cable of 11 KV grade as required |
| 16 | 120 sq. mm |
| 17 | Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size direct in ground including excavation, sand cushioning, protective covering and refilling the trench etc as required. |
| 18 | Upto 35 sq. mm |
| 19 | Above 35 sq. mm and upto 95 sq. mm |
| 20 | Above 95 sq. mm and upto 185 sq. mm |
| 21 | Above 185 sq. mm and upto 400 sq. mm |
| 22 | Laying of one number additional PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size direct in ground in the same trench in one tier horizontal formation including excavation, sand cushioning, protective covering and refilling the trench etc as required. |
| 23 | Upto 35 sq. mm |
| 24 | Above 35 sq. mm and upto 95 sq. mm |
| 25 | Above 95 sq. mm and upto 185 sq. mm |
| 26 | Above 185 sq. mm and upto 400 sq. mm |
| 27 | Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required. |
| 28 | 4 X 16 sq. mm (28mm) |
| 29 | 3½ X 50 sq. mm (35mm) |
| 30 | 3½ X 95 sq. mm (45mm) |
| 31 | 3½ X 120 sq. mm (45mm) |
| 32 | 3½ X 185 sq. mm (57mm) |
| 33 | 3½ X 240 sq. mm (62mm) |
| 34 | Supplying and fixing cable route marker with 10 cm X 10 cm X 5 mm thick G.I. plate with inscription there on, bolted /welded to 35 mm X 35 mm X 6 mm angle iron, 60 cm long and fixing the same in ground as required. |
| 35 | Supplying and making straight through joint with heat shrinkable kit including ferrules and other jointing materials for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required. |
| 36 | 4 X 16 sq. mm |
| 37 | 3½ X 50 sq. mm |
| 38 | 3½ X 95 sq. mm |
| 39 | 3½ X 120 sq. mm |
| 40 | 3½ X 185 sq. mm |
| 41 | 3½ X 300 sq. mm |
| 42 | Providing, laying and fixing following dia G.I. pipe (medium class) in ground complete with G.I. fittings including trenching (75 cm deep)and re-filling etc a required |
| 43 | 100 mm dia |
| 44 | Supplying and laying of following size DWC HDPE pipe ISI marked along with all accessories like socket, bend, couplers etc. conforming to IS 14930, Part II complete with fitting and cutting, jointing etc. in the existing trench, complete as required. |
| 45 | 63 mm dia (OD-63 mm & ID-51 mm nominal) |
| 46 | 120 mm dia (OD-120 mm & ID-103 mm nominal) |
| 47 | 160 mm dia (OD-160 mm & ID-135 mm nominal) |
| 48 | Earthing with G.I. earth plate 600 mm X 600 mm X 6 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 Meter long etc. with charcoal/ coke and salt as required. |
| 49 | Earthing with copper earth plate 600 mm X 600 mm X 3 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 Meter long etc. with charcoal/ coke and salt as required. |
| 50 | Part B - KPWD SR 2023-24 -Electrical Items |
| 51 | Supply of LED Streetlight luminaire with pressure die cast aluminium housing body for optimal thermal dissipation. Lamp compartment comprising of anti glare clear diffuser with Injection moulded polycarbonate material, delivering superior light output Rated life Burning Hrs 50000 hr @ Lumen Maintenance of 70%, maximum light intensity should be between 60 degrees to 70 degrees. CCT > 5500K, IP66 optical and electrical compartment & impact resistance of complete luminaire > IK08. Power Factor >0.9 with mains, Surge Protection- Min 5KV along with Over voltage/ Overload, short circuit/ miss-wiring protection. Compatible for pole mounting with outer dia of 40mm to 50mm. Universal Voltage driver to operate wide voltage range from 100V to 270V 50/60Hz application. Compliance to IS 10322/IEC 60598, LM 79 & LM 80 Adherence with RoHS. UL approved MCPCB. Top access street light with single screw to ensure ease of maintenance at the sight site location with minimized minimal tools. LED Light fixture with ........W System Power consumption. LED Efficiency>1301m/w, nominal CRI >75. Luminaire manufacturer should have in-house facility accredited by NABL/CPRI & any Government certified agency & Design & Development facility certified by ISO 9001:2008. Housing with supplier word mark /name shall be Engraved / Embossing on the die cast housing/ Body part. Warranty of 2 Years against any manufacturing defect working under standard electrical conditions as mentioned above should be given by LED manufacturer & Cree/Nichia/ Lumileds/Osram make LED Source. |
| 52 | LED Streetlight 70W |
| 53 | Fixing halogen/metal halide /SVL/IL/LED floodlight fitting over existing pole / wall ceiling including clamps, bolts, nuts and wiring using suitable capacity wires. |
| 54 | Supplying and Fixing of........mm dia class A GI pipe bracket upto 2 ms long bent at suitable angle and fixing to this bracket street light fitting of all capacities to GIor GIorrailor RCC pole/wall using suitable clamps, bolts, and nuts and wiring using suitable capacity wires. |
| 55 | Using 32mm dia G.I.Pipe |
| 56 | GI/ Copper strips for grounding connections, using necessary fixing materials as required. |
| 57 | 50 x 6 mm GI strip |
| 58 | 50 x 6 mm Copper strip |
| 59 | Supplying & Fixing Chemical earthing for grounding. Conduits, IC cut -outs & other equipments back fill compound which is non -corrosive, thermally conductive, potential to permissible limits, superior Fault conduction capacity, non toxic, weather resistance & capable of achieving ohmic value less than one ohm |
| 60 | Using 4ft. Copper bonded rod with backfill compound |
| 61 | Providing 6kg Fire Extinguisher Mono Ammonium Phosphate Powder 90, Stored Pressure Type, Pressure Gauge, Gross Weight 9.40 Kg, empty weight 3.4 Kg, Can Height 480MM, Diameter 160MM, Discharge Time less than 13 Sees, Controllable discharge mechanism (Squeeze grip with easy snap safety seal), Range minimum 4 meters, applicable on Class A,B, C and electrically started Fire, A Rating 3A, B Rating 21B, Can construction : Deep drawn & Co., Mig welded, valve Construciton : Forging and Mechining, Internal Coating of Can: Epoxy powder coating, External Coating of Can: Epoxy Polyster power coating, Sheet metal thickness: 1.60MM, 5 years Warranty with instalert system with Superior quality EPDM Rubber Hosepipe etc., including cost of materials, labour, usage charges of machinery complete as per specifications. complete IS 15683 and CE Approved |
| 62 | Providing 4.5Kg C02 gas valve type Fire Extinugisher, Tro lley Mounted, Easy Weight Management used Unused Mechanism, Gross Weight 19.1 Kg. empty Weight 14.6 Kg. Can Height 860MM Diameter 140MM, Discharge Time less than13 Sees,Controllable discharge mechanism, Applicable on Class 8&C Fire, 8 Rating 138, Can Constuction : Hot spinning/Forging, Valve Construction : Forging & Machining, Internal Coating of Can : Not Applicable, External coating of Can : Spray Painting, Sheet metal thickness : 4.5M M lSI Approved, 1YearWarranty.with instalert system with Superior quality EPDM Rubber Hosepipe etc., including cost of materials, labour, usage charges of machinery complete as per specifications. complete |
| 63 | Supplying of four bucket stand along with buckets, complete. |
| 64 | Supplying of Hand gloves, complete. |
| 65 | Supplying of first aid box, complete. |
| 66 | Supplying of Saftey Mask, complete. |
| 67 | Supplying of First Aid Chart with lamination, complete. |
| 68 | Supplying and installation of Rubber Mat 1 mtr x 1 mtr - 10 mm thick, complete including cost of materials, labour, usage charges of machinery complete as per specifications. |
| 69 | Supply & Fixing of Caution / Danger Boards |
| 70 | Supply |
| 71 | Fixing |
| 72 | 11KV CT (Secondary - 1A) for 3 Phase 4 Wire Metering, Burden: 2.5 VA, 0.2 Accuracy Class |
| 73 | Ratio: 1.25/1A to 2.5/1A |
| 74 | 11kV/√3/110V/√3, 1 Phase metering PT class - 1, 100 VA per Phase for measurement of voltage |
| 75 | GSM modem with connecting cable for remote communicating capabilities |
| 76 | Fixing of Thread Through Meter along with wiring |
| 77 | Fixing of GPRS Modems with Accessories |
| 78 | CT PT Operated ETV Meter 0.2s Accuracy Class with ABT feature and DLMS protocal with ToD with RS 232 Port UNIDIRACTIONAL (Used for HT Installation, LT Metering Cubicle {50-150 KW}) |
| 79 | LT Line Tester |
| 80 | Screw Ddriver 8\\" |
| 81 | Adjustabale Screw Spanner 12\\" |
| 82 | Hi Visibility Reflective Jacket |
| 83 | Hi Visibility Reflective Rain Wear |
| 84 | Part - C -MARKET RATE - Electrical Items |
| 85 | 11KV, HT 3 Way Non DAS VCB Panel |
| 86 | Supply, erection, testing and commissioning of 11KV, 3PH, 50 HZ, 350 MVA, 630 AMPS, OUTDOOR TYPE 3 VCB Panel H.T. Control panel,Comprising of 1 VCB incomer & 2 outgoing VCB's fabricated out of 2 mm Cold Rolled mild steel, metal clad , free standing totally enclosed cubicle type, fully compartmentalised & suitable for operation on 11 KV, 3 phase, 50 Hz AC Earthed system and comprising of the following as per the detail specifications below. |
| 87 | Incoming |
| 88 | VCB Panel consisting of : |
| 89 | a. 3P VACCUM CIRCUIT BREAKER, horizontal drawout, horizondally isolated type, 630 amps 350MVA, 11 kV, 26.3kA with all standard accessories fitted with, shunt trip/closing coil, Motor: 220V / 110V AC motor / hand operated mechanism and operaration counter -1 no |
| 90 | b.Non lockable breaker control (TNC) switch with twistle grip handle and spring return to neutral - 1 set |
| 91 | c.3P, Non directional IDMT 30/c , 1 E/F relay with instantaneuous elements MC 31 A - 1 set |
| 92 | d.Resin cast CT's 15/7.5 vA class 5P 10/1 - 3 nos |
| 93 | e.Resin cast PT's, 3P,100vA class 1 - 1 no |
| 94 | f.Breaker on/off indication lamps - 1 set |
| 95 | g.Voltmeter with selector switch - 1 no |
| 96 | h.Ammeter with selector switch - 1 no |
| 97 | i.Aluminium busbar, suitable rating 3 Phase,Air insulated with heat shrinkable sleevs - 1set |
| 98 | j.Earth 25X3 mm Tin coated copper busbar - 1set |
| 99 | k.Busbar supports resin cast with 33kV die electric and mechanical strength - 1 set |
| 100 | Outgoing |
| 101 | VCB Panel 2 & 3 - - 2Nos , Each Consisting of the following: |
| 102 | a. 3P VACCUM CIRCUIT BREAKER, horizontal drawout, horizondally isolated type, 630 amps 350MVA, 11 kV, 26.3kA with all standard accessories fitted with, shunt trip/closing coil, Motor: 220V / 110V AC motor / hand operated mechanism and operaration counter -1 no |
| 103 | b.Non lockable breaker control (TNC)switch with twistle grip handle and spring return to neutral - 1 set |
| 104 | c.3P, Non directional IDMT 30/c , 1 E/F relay with instantaneuous elements MC 31 A - 1 set |
| 105 | d.Resin cast CT's 15/7.5 vA class 5P 10/1 - 3 nos |
| 106 | e.Breaker on/off indication lamps - 1 set |
| 107 | f.Ammeter with selector switch - 1 no |
| 108 | g.Aluminium busbar, suitable rating 3 Phase,Air insulated with heat shrinkable sleevs - 1set |
| 109 | h.Earth 25X3 mm Tin coated copper busbar - 1set |
| 110 | i.Busbar supports resin cast with 33kV die electric and mechanical strength - 1 set |
| 111 | Compact Sub-station 11kV/433 V, 250KVA |
| 112 | Design, fabrication, Supply, erection, testing and commissioning of Outdoor type package substation (Compact Substation) comprising of 1 No of 11 KV VCB of rating 630 A, MDO type, directly connected with 1 No 11 KV/433 V, 250 KVA copper wound Dry type power distribution transformer and 2 No's of 400A 4P MCCB's microprocessor type or based LT outgoing (operating voltage 433 V), 36 KA, Shunt release, Under voltage release and E/F relay complete with all standard accessories as required and subject to ESCOM requirment / Norms. CSS panel enclouser frabicated out of 2 mm thick CRCA sheet steel and also as per detail specification enclouser |
| 113 | 11 KV/433 V, 250 KVA 'Compact Substation |
| 114 | Main LT Power Panel |
| 115 | Supply, erection, testing and commisioning of Indoor type Main LT Power Panel fabricated out of 16 SWG CRCA sheet steel metal with all aluminium TPN busbars, doors interlock with switches, dead front type design, metal pretreatment of such as derusting, degreasing, phosphating, Powder coated, prime coats and finish paints of approved color with all leads and lift and as directed by the Engineer incharge. The Panel shall be erected with suitable\\" C \\" Channels over the existing Duct and shall comprise of the following. |
| 116 | EB Incomer 1 |
| 117 | i) '400 A 4 pole 36KA MCCB with O/C, S/C, LSI Releases - 1 No |
| 118 | EB Incomer 2 |
| 119 | i) '400 A 4 pole 36KA MCCB with O/C, S/C, LSI Releases - 1 No |
| 120 | Buscoupler |
| 121 | ii) '400 A 4 pole 36 KA MDO MCCB with O/C, S/C, LSI Releases - 1 No |
| 122 | Under Voltage Release - 3 No's |
| 123 | EB 1 & EB 2 Metering Consisting of |
| 124 | RYB phase indication lamps - 2 sets |
| 125 | ACB Indication Lamps ON / OFF / TRIP / CHARGE - 3 Set |
| 126 | MFM Meter - 2 Nos |
| 127 | CT Ratio 400 / 5 A, Class 1.0, Burden 15 VA - 3 no's |
| 128 | Earth Leakage Relay with CBCT - 2 No's |
| 129 | 6 Amps SP MCB for Control Circuits |
| 130 | Phase Failure Relay with Under & Over Voltage Relay setting with Neutral fail Protection. - 3 Sets |
| 131 | ON / OFF ILPB with NO- NC Contactors - 3 Sets |
| 132 | Trip Indication Lamps - 3 Sets |
| 133 | Auto / Manual Selector Switch - 3 Nos |
| 134 | On Delay Timer - 3 Nos |
| 135 | Auxilory Contractors - 3 Sets |
| 136 | INTERLOCK |
| 137 | Electrical Interlock of EB Incomer 1& 2 and Bus Coupler with Auxilary Contractors, Relays, Connectors, Timers, MCB's and other accessories. |
| 138 | Out-going |
| 139 | 200 A 3P+NL MCCB with 25 KA Breaking capacity. O/C & S/C releases - 4 No |
| 140 | 125 A 3P+NL MCCB with 25 KA Breaking capacity. O/C & S/C releases - 3 No |
| 141 | 63 A 3P+NL MCCB with 16 KA Breaking capacity. O/C & S/C releases - 3 No |
| 142 | Suitable Spreder Terminals and Extended Rotary Handles for all MCCB's as required. |
| 143 | ( Note : The Logic Sequence of the Main Panel shall be Designed in such a way that, at any point of time only One Incoming source will be functional) |
| 144 | New 100 KVAR Capacitor Control Panel |
| 145 | Supply, installation, testing and commissioning of Indoor type 100 KVAR Automatic Power factor correction relay ( APFCR ) of 6 stages, fabricated out of 16 SWG CRCA sheet steel metal with all aluminium TPN busbars, doors interlock with switches, dead front type design, metal pretreatment of such as derusting, degreasing, phosphating, Powder Coated, prime coats and finish paints of approved color with all leads and lift and as directed by the Engineer incharge. The Panel shall be erected with suitable\\" C \\" Channels over the existing Duct and shall comprise of the following. |
| 146 | Incoming |
| 147 | 200 A 3P+NL MCCB with 25 KA Breaking capacity. O/C & S/C releases - 1 No |
| 148 | 250 A Aluminium Busbar - 1set (Colour code shall be followed strictly for all phases) with heat shrinkable sleeves and SMC busbar supports) |
| 149 | RYB phase indication lamps - 3 set |
| 150 | VAF Meter - 1 Nos |
| 151 | CT Ratio 400 / 5 A, Class 5, Burden 15 VA - 36 No's |
| 152 | 6 Amps SP MCB for Control Circuit |
| 153 | 6 Stage APFCR Relay |
| 154 | Auto / Manual Selector Switch |
| 155 | Suitable Spreder Terminals and Extended Rotary Handles for all MCCB's as required. |
| 156 | Outgoing: |
| 157 | 25 KVAR Capacitor Bank with 63 Amps TP MCB Switching duty TP contactors , with ON/OFF Push buttons & ON indication lamps complete - 2 Nos |
| 158 | 20 KVAR Capacitor Bank with 40 Amps TP MCB Switching duty TP contactors , with ON/OFF Push buttons & ON indication lamps complete- 1 No |
| 159 | 10 KVAR Capacitor Bank with 32 Amps TP MCB Switching duty TP contactors , with ON/OFF Push buttons & ON indication lamps complete - 3 Nos |
| 160 | LT Metering Cubicle |
| 161 | Supply, installation, testing and commissioning outdoor type LT Metering Cubicle frabcatied of 2 mm CRCA sheet metal with all aluminium TPN busbars, doors interlock with switches, dead front type design, metal pretreatment of such as derusting, degreasing, phosphating, Powder coated, prime coats and finish paints of approved color with all leads for loads sutiable on LT supply from 50 KW to 150 KW having specification & design as per the prototype approval as per CESCOM requirment and approval (Excluding Meter Cost & Modem Cost) |
| 162 | New Domestic LT Power Panel: |
| 163 | Supply, erection, testing and commisioning of Indoor type LT Domestic Power Panel fabricated out of 16 SWG CRCA sheet steel metal with all aluminium TPN busbars, doors interlock with switches, dead front type design, metal pretreatment of such as derusting, degreasing, phosphating, Powder coated, prime coats and finish paints of approved color with all leads and lift and as directed by the Engineer incharge. The Panel shall be erected with suitable\\" C \\" Channels over the existing Duct and shall comprise of the following. |
| 164 | Incoming |
| 165 | 200 A TP +NL MCCB 25 KA breaking capacity with O/C, S/C release - 1 No, |
| 166 | 250 A Aluminium Busbar - 1 set (Colour code shall be followed strictly for all phases) with heat shrinkable sleeves and SMC busbar supports) |
| 167 | RYB phase indication lamps - 1 set |
| 168 | Volt meter with selector switch - 1 No |
| 169 | Ammeter with selector switch - 1 No |
| 170 | Earth Leakage Relay with CBCT - 1 No |
| 171 | 6 Amps SP MCB for Control Circuits |
| 172 | CTS 125/5A Class 1.0 Burden 5VA. |
| 173 | Out-going |
| 174 | 125 A 3P+NL MCCB with 25 KA Breaking capacity. O/C & S/C releases - 2 No |
| 175 | 63 A 3P+NL MCCB with 16 KA Breaking capacity. O/C & S/C releases - 6 No's |
| 176 | Suitable Spreder Terminals and Extended Rotary Handles for all MCCB's as required. |
| 177 | LT Feeder Pillar Panel: |
| 178 | Supply, erection, testing and commisioning of Outdoor type LT Feeder Pillar Panel fabricated out of 14 SWG CRCA sheet steel metal with all aluminium TPN busbars, doors interlock with switches, dead front type design, metal pretreatment of such as derusting, degreasing, phosphating, Powder coated, prime coats and finish paints of approved color with all leads and lift and as directed by the Engineer incharge. The Panel shall be erected with suitable\\" C \\" Channels over the existing Duct and shall comprise of the following. |
| 179 | Incoming |
| 180 | 125 A TP +NL MCCB 25 KA breaking capacity with O/C, S/C release - 1 No, |
| 181 | 150 A Aluminium Busbar - 1 set (Colour code shall be followed strictly for all phases) with heat shrinkable sleeves and SMC busbar supports) |
| 182 | RYB phase indication lamps - 1 set |
| 183 | Volt meter with selector switch - 1 No |
| 184 | Ammeter with selector switch - 1 No |
| 185 | 6 Amps SP MCB for Control Circuits |
| 186 | CTS 125/5A Class 1.0 Burden 5VA. |
| 187 | Out-going |
| 188 | 100 A 3P+NL MCCB with 25 KA Breaking capacity. O/C & S/C releases - 3 No's |
| 189 | 63 A 3P+NL MCCB with 16 KA Breaking capacity. O/C & S/C releases - 2 No's |
| 190 | 32 A 3P+NL MCCB with 165 KA Breaking capacity. O/C & S/C releases - 4 No's |
| 191 | Suitable Spreder Terminals and Extended Rotary Handles for all MCCB's as required. |
| 192 | LT Cable |
| 193 | Supply of 1.1 KV, XLPE or Heat resistant PVC insulated, PVC exutruted Inner Seath Armoured LT UG Cable as per IS-1554 (Part- 1) or IS-7098 Part-1, Armouring strip thickness and resistivity as per IS-3975 |
| 194 | Supply |
| 195 | 240 Sqmm, 3.5 Core (32 GI Strip 4 x 0.8 mm) |
| 196 | 185 Sqmm, 3.5 Core, (28 GI Strips - 4 x 0.8 mm) |
| 197 | 120 Sqmm, 3.5 Core, (23 GI Strips - 4 x 0.8 mm) |
| 198 | 95 Sqmm, 3.5 Core, (21 GI Strips - 4 x 0.8 mm) |
| 199 | 50 Sqmm, 3.5 Core, (18 GI Strips - 4 x 0.8 mm) |
| 200 | 16 Sqmm, 4 Core, (11 GI Strips - 4 x 0.8 mm) |
| 201 | HT UG Cable |
| 202 | Supply of 11 KV, 3 Core, XPLE HT UG Cable with pressure extruded inner sheeth, ROUND WIRE ARMOURED as per IS-7098 (Part-2) Armouring wires dia and Resistivity as per IS-3975 |
| 203 | Supply |
| 204 | 95 Sqmm, (55 GI Wires - 3.15 mm Dia) |
| 205 | Arranging HT Power supply |
| 206 | Arranging required HT Power supply from MESCOM wth Submission of application for Power supply, Obtaining Power sanction, CEIG / CEA Approval from Electrical Inspectorate , Feasibility report, Preparing wiring Diagram, Completion report, Agreement papers as per the requirement of MESCOM, Liasioning and Final Servicing of the Installation with Permanent power supply ( Excluding Deposits & other Charges to be remitted to MESCOM.) |
| 207 | Part D - CIVIL DSR 2023 - Civil Items |
| 208 | Miscellaneous Civil works required at site during the execution such as Earth work, PCC, RCC, Brick masonary, Plastering etc. works as per site requirement as per DSR 2023 Civil. Please Enable Macros to View BoQ information |