| 1 | Wiring for sub main wiring with following sizes of PVC/ insulated copper conductor wires in the surface/ recessed PVC / MS conduit along with PVC insulated copper conductor earth wire as required complete with connections, testing and commissioning etc. as per specifications and drawings. |
| 2 | 4x6 sq. mm with 2 x 6.0sq. mm earth wire |
| 3 | 4x10 sq. mm with 2 x 6.0sq. mm earth wire |
| 4 | 4x16 sq. mm with 2 x 6.0sq. mm earth wire |
| 5 | Supply, installation, designing testing at works, installation and commissioning of outdoor type cubical panel box suitable for 3 phase 4 wire 415 volts 50 Hz supply system CRCA sheet steel enclousre panel with febricated with 14/16 SWG CRCA sheet steel and duly powder coated with simns grey and chemical treattment for with front and rear openable provided with suitable gaskit to make dust/vermin proof for ip 54 as per IS 13947 degree of protection, fault rating 50 KA/1 sec including angle iron base frame of size 50x50x6 mm for mounting the panel board at the hieght of 600 mm from FFL etc ( L&T, Legarnd and schineder) including dismentaling of existing LT panel etc as Directed by eng-in- charge. |
| 6 | Moulded case circuit Breakers shall be thermal magnetic trip type. Fault level for all MCCB and bus bar shall be 50 KA. ICU shall be equal to ICS=100% |
| 7 | Note : |
| 8 | All metering current transformers shall be Class 1, 15 VA. |
| 9 | MDB-1 (Indoor Type) |
| 10 | Incomer |
| 11 | 160 A 4P 36K MCCB – 1No. |
| 12 | R,Y,B phase indicating lights with control fuses - 1 set |
| 13 | Bus Bar |
| 14 | 250 A 415V, 50Hz, 3ph, 4 wire Aluminium Bus bar |
| 15 | Outgoing |
| 16 | TPN 63 amp 8 no |
| 17 | TPN 40 amp 8 no |
| 18 | SPN 40 amp 6 no |
| 19 | SPN 63 amp 6 no |
| 20 | Moulded case circuit Breakers shall be thermal magnetic trip type. Fault level for all MCCB and bus bar shall be 50 KA. ICU shall be equal to ICS=100% |
| 21 | Note : |
| 22 | All metering current transformers shall be Class 1, 15 VA. |
| 23 | MDB-1 (Indoor Type) |
| 24 | Incomer |
| 25 | 250 A 4P 36K MCCB – 1No. |
| 26 | R,Y,B phase indicating lights with control fuses - 1 set |
| 27 | Bus Bar |
| 28 | 400 A 415V, 50Hz, 3ph, 4 wire Aluminium Bus bar |
| 29 | Outgoing |
| 30 | TPN 63 amp 8 no |
| 31 | TPN 40 amp 8 no |
| 32 | SPN 40 amp 6 no |
| 33 | SPN 63 amp 6 no |
| 34 | Moulded case circuit Breakers shall be thermal magnetic trip type. Fault level for all MCCB and bus bar shall be 50 KA. ICU shall be equal to ICS=100% |
| 35 | Note : |
| 36 | All metering current transformers shall be Class 1, 15 VA. |
| 37 | MDB-1 (Indoor Type) |
| 38 | Incomer |
| 39 | 125 A 4P 36K MCCB – 1No. |
| 40 | R,Y,B phase indicating lights with control fuses - 1 set |
| 41 | Bus Bar |
| 42 | 250 A 415V, 50Hz, 3ph, 4 wire Aluminium Bus bar |
| 43 | Outgoing |
| 44 | TPN 63 amp 6 no |
| 45 | TPN 40 amp 6 no |
| 46 | SPN 40 amp 4no |
| 47 | SPN 63 amp 4no |
| 48 | Supply and laying of PVC Power cable 1.1 KV Grade armoured aluminium XLPE cables including earth work, cost of end termination, thimbles and saddles etc. as required. |
| 49 | 3.5 C X 120 SQ MM |
| 50 | 3.5 C X 240 SQ MM |
| 51 | Earthing withGI earth plate 600mm x 600 mm x 6mm thick including accessories and providing masonry enclosure with cover plate having locking arrangement and watering pipe etc. (with charcoal or coke and salt) complete as required for earthing and lightning protection |
| 52 | Providing and fixing 25 mm x 6 mm GI strip from earth electrode as required(10 Meter) each approx |
| 53 | Repairing of 150 KVA oil cooled servo voltage stablizer 3 phase by way of replacing of Dimmer/veriable (3nos) and complete rewinding of copper coil (3nos) including cost of old material and replacing of synchronizing motor 10KG(3nos) motor network,bacalite plate,microsoft switch(3nos),wiring for auto control micro procerror card(3nos), bearing variable socket (3nos), volt meter 96 mm 300 volt(3nos),front plate, push button(6nos) togal switch (6nos) and indicator 12 nos complete job |
| 54 | Repairing of 5 HP motor( mono block pump set ) by way of complete rewinding etc as requried |
| 55 | Providing and fixing of following rating and breaking capacity and Pole MCCB with thermal magnetic trip type and terminal spreaders in existing cubicle panel board including drilling holes in cubicle panel making connections, etc. as requried ( L&T, Legarnd and schineder) |
| 56 | 250 ampre MCCB 4 pole 36 ka thermal magnetic trip type with spreader link |
| 57 | 200 ampre MCCB 4 pole 36 ka thermal magnetic trip type with spreader link |
| 58 | 400 ampre MCCB 4 pole 36 ka thermal magnetic trip type with spreader link Please Enable Macros to View BoQ information |