| 1 | Supply, installation, designing testing at works, installation and commissioning of outdoor type cubical panel box suitable for 3 phase 4 wire 415 volts 50 Hz supply system CRCA sheet steel enclousre panel with febricated with 14/16 SWG CRCA sheet steel and duly powder coated with simns grey and chemical treattment for with front and rear openable provided with suitable gaskit to make dust/vermin proof for IP 65 as per IS 13947 degree of protection, fault rating 50 KA/1 sec including angle iron base frame of size 50x50x6 mm for mounting the panel board at the hieght of 600 mm from FFL etc Makes ( L&T (D Sine) , Legarnd(DPX3), and Schineder (NSX-NS)) including dismentaling of existing LT panel etc as Directed by eng-in- charge. |
| 2 | Moulded case circuit Breakers shall be Micro Processer based type. Fault level for all MCCB and bus bar shall be 50 KA. ICU shall be equal to ICS=100% |
| 3 | Note : |
| 4 | All metering current transformers shall be Class 1, 15 VA. |
| 5 | (Outdoor Type) |
| 6 | Incomer(power panel) |
| 7 | 630 ampre MCCB 4 pole 50 ka Micro Processer based with ROH and spreader link 1 nos |
| 8 | MFM Meter 1 set |
| 9 | Bus Bar |
| 10 | 1000 ampre rating alum busbar of electrplytic grade E 91 with Earth +copper wiring and all accessories |
| 11 | Outgoing |
| 12 | 250 ampre MCCB 4 pole 50 ka Micro Processer based with ROH and spreader link 12 nos |
| 13 | Moulded case circuit Breakers shall be Micro Processer based type. Fault level for all MCCB and bus bar shall be 50 KA. ICU shall be equal to ICS=100% |
| 14 | Note : |
| 15 | All metering current transformers shall be Class 1, 15 VA. |
| 16 | MDB-1 (outdoor Type) |
| 17 | Incomer(power panel) |
| 18 | 400 ampre MCCB 4 pole 50 ka Micro Processer based with ROH and spreader link 1 nos |
| 19 | MFM Meter 1 set |
| 20 | Bus Bar |
| 21 | 630 ampre rating alum busbar of electrplytic grade E 91 with Earth +copper wiring and all accessories |
| 22 | Outgoing |
| 23 | 160 ampre MCCB 4 pole 50 ka Micro Processer based with ROH and spreader link 12 nos |
| 24 | 160 ampre MCCB spreader link |
| 25 | Earthing withGI earth plate 600mm x 600 mm x 6mm thick including accessories and providing masonry enclosure with cover plate having locking arrangement and watering pipe etc. (with charcoal or coke and salt) complete as required for earthing and lightning protection |
| 26 | Providing and fixing 25 mm x 6 mm GI strip from earth electrode as required(10 Meter) each approx |
| 27 | Supply and laying of PVC Power cable 1.1 KV Grade armoured aluminium XLPE cables including earth work, cost of end termination, thimbles and saddles etc. as required. Havells, KEI, Polycab |
| 28 | 3.5C x 185 sq.mm |
| 29 | 3.5C x 240sq.mm |
| 30 | 1 C x 400 sq mm |
| 31 | Construction of platform with concreete base 1:3:6 of (10'- 0\\"X 7'- 0') 5'- 0\\" height 3'- 0\\" above Ground level and 2'- 0\\" Below groung level including excavation shuttering and refilling complete job |
| 32 | Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed steel conduit as required. |
| 33 | 4 x 6 sq mm + 2 x 6 sq mm |
| 34 | 4 x 10 sq mm + 2 x 6 sq mm |
| 35 | Supply laying stringing and binding of LT conductor rabbit including connection testing |
| 36 | Supply laying stringing and binding of LT conductor Dog including connection testing |
| 37 | Supplying and fixing of Mukki clamp complete with nut bolt and all necessary accessories. |
| 38 | Supplying and fixing of U clamp complete with 6\\" GI nut bolt, 4\\" shakle insulator and all necessary accessories. |
| 39 | Supply and fixing of SST pole 9 meter with 1:3:6 cement concrette, foundation including excavation and refilling etc as req Please Enable Macros to View BoQ information |