| 1 | Servicing of 11 KVA HT Panel Ve VCIB Trolly is pulled out mechanically and after servicing/ cleaning same is inserted back to panel including bushing, moving contact and operating mech etc, as required |
| 2 | Servicing of VCB cleaning of Inner male and female contact with CRC, repairing of operating mech. for smooth operation of VCB after rectification of wring etc. at required. |
| 3 | Dismantling of aluminium bus bar suitable for 800 Amp. & 400 Amp. Load of the main panel and re-fixing the same after tapping with heat shrinkable |
| 4 | Providing and fixing 2.4/30V, DC relay for tripping system 1 incoming & 2 outgoing. The job indules disconnection of relay from the panel, calibration and testing with primary Injection test. The job includes the replacemerit of defective wiring as required at site. (Over current and earth fault realy) |
| 5 | Providing and fixing of Indicating lamp unit with holder. |
| 6 | Testing of PT and replacement of HT funes funes-3 nos |
| 7 | Providing and fixing of power pack of rating AC 220/110 Input, output 24/30 VDC for providing the supply to the tripping system |
| 8 | Providing and fixing of TNC (Trip Neutral control) Switch |
| 9 | Providing and fixing of space heater with thermostat including controlling switch to maintaining the panel moisture free |
| 10 | Providing and fixing of HT CT epoxy moulding heavy duty as per sample |
| 11 | Providing and fixing of Jew/axulary contact as required |
| 12 | Providing and freing of Digital amp, meter with selector switch |
| 13 | Providing and fling of Digital Volt meter 11 KV/110 Vit, CT at 50/5 and 25/5 CT (96x96) with selector switch |
| 14 | Rectification of wiring of panel for protection relay and metering system |
| 15 | Testing of HT panel on load for satisfactory perfonnance |
| 16 | P & F 10 KVAR capacitors in exiting penel complete as read |
| 17 | P & F 15 KVAR capacitors in exiting penel complete as read |
| 18 | Supply & fixing of Capacitor duty contactor (AC Control) 415 V 3Ph 50 Hz, I NO 1 NC sutable for 15 KVAR |
| 19 | P & F of 12 stages intelligent power factor controler realy (IFC) complete as reqd. |
| 20 | Supply of corrugated & chequered rubber mat for electrical purpose exceeding IS: 5424/69 Black or red in 1 M X 2 M of size. 25 mm thickness Please Enable Macros to View BoQ information |